Alarm of the
generator
Generator’s
Check that the cooling water pump is rotating.
temperature is too high.
→
Start the pump.
Check that the valve of the cooling water
Generator’s
line is open.
pressure is too high.
→
Open the valve.
Check that the discharge pressure of cooling
water pump is normal.
→
If not, there may be the clogging of
strainer, air leak in the pipe line, etc.
High concentration of absorbent
Correct the above causes and restart the
Chiller. If it still gives you the
“CHILLER ALARM”, check the following and
contact Carrier service agent.
1) Temperature of chilled water inlet
and outlet
2) Temperature of cooling water inlet
and outlet
3) Temperature and pressure of generator
4) Is the chilled water setting point too low?
→
Correct it to specified setting point.
5) There may be the fouling of heat
transfer tube in the water (especially,
cooling water) line.
36