3-7. MAINTENANCE MESSAGE
3-7-1. Maintenance message
When a trouble which could disturb an efficient operation of the Chiller is predicted,
it provides you with the forewarning.
3-7-2. How it is shown
It provides you with a comment on the data display as follows when a trouble is predicted.
Table 3-2 Maintenance message
Data code
Data name
Display
Means
★
H-01
Operate purge pump
Operate purge pump.
★
H-03
Clean cooling water tubes
Fouling of cooling water tubes.
★
H-04
Check cooling water system
Check the cooling water pump,
cooling tower, etc.
☆
H-06
Purge tank high pressure
Purge tank pressure is high.
☆
H-07
Cooling water tubes foul
Fouling of cooling water tubes.
☆
H-08
Cooling water high temperature
Cooling water temperature is high.
H-10
Power failure
There was power failure in time
that the Chiller is operating.
★
mark : When this appears, the Chiller needs an immediate action.
☆
mark : When this appears, the Chiller does not need an immediate action.
However, as this might lead to
★
mark code, attention should be paid.
Consult Carrier service personnel at the next periodic maintenance.
NOTE : These indications disappear when the failure is corrected.
29
Содержание 16LJ-01
Страница 1: ...Absorption Chiller OPERATION MANUAL 16LJ 01 02 03 Original instructions ...
Страница 13: ...9 2 2 CONTROL PANEL Fig 2 3 CONTROL PANEL Fig 2 4 CONTROL PANEL inside ...
Страница 14: ...10 Fig 2 5 POWER BOX Fig 2 6 POWER BOX inside TERMINAL BASE CIRCUIT BREAKER MAGNET SWITCH OVERCURRENT RELAY ...
Страница 15: ...11 Fig 2 7 OPERATION BOARD ...
Страница 18: ...14 Fig 2 8 FLOW DIAGRAM ...
Страница 24: ...Fig 3 3 SW3 backup switch and backup battery SW3 Backup switch UP ON DOWN OFF Backup switch 20 ...
Страница 51: ...47 ...