BROADway - Release 4.00
Configuration
Setting System Node Parameters
To view the power input redundancy status of the system, use the
RTRV-EQPT
TL1 command:
RTRV-EQPT::NSP-x.PWR-1:1234;
To enable or disable power input redundancy, use the
ED-EQPT
TL1 command:
ED-EQPT::NSP:1234::<setting>;
<setting>
—
ENA
,
ENABLE
,
ENABLED
,
DIS
,
DISABLE
, or
DISABLED
.
Examples:
Enable power supply input redundancy (assuming NSP-1 is the active NSP):
ED-EQPT::NSP:1234::ENA;
Disable power supply input redundancy (assuming NSP-1 is the active NSP):
ED-EQPT::NSP:1234::DIS;
If you have installed two separate power sources to the
BROAD
way chassis (both
FEED A
and
FEED B
on the back of the chassis), you should enable power input supply redundancy. (For
information about connecting these power feeds, see
Cabling Power and Ground
on page 2-6.) If you
do not have two separate power sources connected to the chassis, you should disable power supply
redundancy; otherwise, the
NSP PWR
alarm LED will lamp red (as described in the online help).