Controller Calibration / Offset
The following procedure outlines the steps for setting a temperature or humidity offset.
A. Press the advance key until CAL1 is in the lower display
B. Press the up or down keys to obtain the desired temperature or humidity offset
C. Press the Infinity key to return to the home page
Controller Parameters
Controller parameters are factory set and should not be changed. Incorrect controller parameters
will result in poor performance and are not covered under warrantee. If parameter re-setting to
factory default values is needed, consult CARON service.
Diural Lighting & Contact Closure System
With the diural lighting and contact closure systems, different temperature and humidity set points
maybe selected for lights ‘on’ and ‘lights ‘off’. To set the second set point:
A. Press the up and down keys together for 3 seconds
B. Press the advance key until SP2 is in the lower display
C. Press the up or down keys to obtain the desired temperature or humidity set point
D. Press the Infinity key to return to the home page
The original setpoints “SP” are the NIGHT, when the lights are off, temperature and humidity
setpoint settings.
Communications
Optional Anafaze
®
Watview Run-Time computer communications software using RS-485
computer communications is available for use with the standard controls and is very user friendly
software. The software can be used for real time operation, set-up, and data logging. Please
consult the Watview help files in the software for operating instructions.