CARLO GAVAZZI UWP 3.0 Скачать руководство пользователя страница 6

 

 

How to install an UWP 3.0 system 

6

 

1.1 The master unit: UWP 3.0 

The  system  is  based  on  UWP  3.0,  a  Linux  based  embedded  PC  that  embeds  datalogger,  gateway, 
controller and web-server functions in a small 2DIN unit. The Ethernet port allows both local and remote 
communication via a wide range of protocols; the data logger can record any value/event coming from 
the field buses. Meters, sensors and actuators can be connected and configured for putting in place the 
necessary mix of monitoring and control functions.

 

 
Here below a diagram of the system is shown. 

 
 

System 

 

Modbus RTU connection. COM 1 slave, COM 2 master 

 
 
 

 

Modbus RTU connection. COM 1 master, COM 2 master

 

 

Содержание UWP 3.0

Страница 1: ...UWP 3 0 HW manual rev 0 7 06 09 2018...

Страница 2: ...it contains important information regarding safety The smart building system must be used only for the usage it has been designed for Every other kind of usage is potentially unsafe The manufacturer i...

Страница 3: ...1 3 1 4 Placing the SB2REP230 in a project 21 1 3 2 Dupline cable and installation tips 24 1 3 2 1 New Installation Planning 24 1 3 2 2 Retrofit Installation using existing cables 25 1 3 2 3 Cable Rou...

Страница 4: ...UWP 3 0 system 4 3 1 2 RS 485 cable 42 3 1 3 RS 485 grounding 42 3 1 4 RS 485 shielding 42 3 1 5 RS 485 termination 42 3 1 6 RS 485 wiring procedure 42 3 1 7 RS 485 topology 43 4 APPENDIX B SAFETY RE...

Страница 5: ...nitors and controls connected devices via its local bus management functions it includes a web server with a powerful and intuitive user interface to display custom dashboards and interact with local...

Страница 6: ...allows both local and remote communication via a wide range of protocols the data logger can record any value event coming from the field buses Meters sensors and actuators can be connected and config...

Страница 7: ...How to install an UWP 3 0 system 7 Example of Smart Dupline modules connection using master channel generators Hardware...

Страница 8: ...ired from the UWP 3 0 side see Appendix A for the other termination 1 1 1 UWP 3 0 bus description Local bus 1 This is placed in the connector on the right side and it is called the High Speed bus This...

Страница 9: ...How to install an UWP 3 0 system 9 The available connections can be summarized as shown below N B All the connections described in the following paragraphs must be carried out without power supply...

Страница 10: ...a detailed explanation 1 1 2 4 How to connect energy meters UWP 3 0 works as a Modbus master for any Modbus device Very often it is necessary to connect Modbus energy meters so to log their data and m...

Страница 11: ...e UWP 3 0 tool manual for further details 1 1 4 Modbus TCP 1 1 4 1 Abstract UWP 3 0 has an Ethernet port by which it is possible to connect both Modbus TCP slaves and Modbus TCP masters at the same ti...

Страница 12: ...ation from them They are connected to the UWP 3 0 via the high speed bus that is present both on the local bus and on the terminals at the bottom of the bus generators This means that the connection i...

Страница 13: ...How to install an UWP 3 0 system 13 Example 1 The bus generators are all connected in the same Din rail...

Страница 14: ...How to install an UWP 3 0 system 14 Example 2 The bus generators are mounted in different cabinets...

Страница 15: ...ble stars multiple cable segments brought back to a single point or loops must not be used Cable length The maximum length of the cable is 600 metres Connection of the cable shield The shield of the R...

Страница 16: ...powered by 15 to 30Vdc The Dupline modules in the building automation system can be divided into two groups Decentralized modules these are all the modules such as light switches PIR sensors lux sens...

Страница 17: ...eered around the Dupline bus because it can be matched to the application The routing of the cable may be in a line star ring or any combination Straight through the best place for the SH2MCG24 would...

Страница 18: ...dules result in an excess voltage drop and might cause the modules placed far from the Dupline generator not to work properly The SB2REP230 module is a 115 to 230 VAC powered Dupline repeater and isol...

Страница 19: ...the SB2REP230 provides the bus power supply to the modules connected to it Example 1 UWP 3 0 SH2MCG24 MODULE A MODULE B SB2REP230 MODULE C MODULE D Note the local bus on both sides is connected to th...

Страница 20: ...ater is connected to Example 2 The example below shows the network topology UWP 3 0 SH2MCG24 SH2MCG24 SH2RE16A4 SH2RE16A4 SH2SSTRI424 SB2REP230 Modules D and E are part of the Dupline network 1 Module...

Страница 21: ...the short circuit is removed see above neither of the Dupline sides will operate 1 3 1 4 Placing the SB2REP230 in a project To wire a Dupline repeater into a network the Dupline transparent module SH1...

Страница 22: ...A even if this value increases when a relay is switched on off in the purple cabinet the installer has placed another 6 SH2RE16A4 modules the green cabinet is 700 metres away from the violet cabinet a...

Страница 23: ...How to install an UWP 3 0 system 23...

Страница 24: ...this is not recommended the table is not valid in this case The values shown in the table are also suitable for installations where the majority of the modules are placed at the beginning of the netwo...

Страница 25: ...t must not be grounded at the splicing points Splices need to be water tight to prevent the entry of water into the cable which could result in increased capacitance Note Bad splices and or splices le...

Страница 26: ...e the cable resistance and the load from bus powered modules result in an excess of voltage drop Cabinet 2 Dupline modules e g 6 SH2RE16A4 Cabinet 3 Dupline modules e g 6 SH2RE16A4 Main Cabinet UWP 3...

Страница 27: ...line modules e g 6 SH2RE16A4 Main Cabinet UWP 3 0 SH2MCG24 150 m Cabinet 4 SH2MCG24 Dupline modules e g 4 SH2RE16A4 150 m 170 m Cabinet 5 Dupline modules e g 6 SH2RE16A4 RS485 HSBUS from first SH2MCG2...

Страница 28: ...to manage double word information 5 A CRC control is implemented in request and reply frames Should an error occur the bus generator resends the request until it receives a correct frame Analogue data...

Страница 29: ...ne module is given in the relevant datasheet Current consumption in the datasheet instruction manual this is always given in the Dupline Specifications of each module Dupline channel consumption in th...

Страница 30: ...the terminals at the top If more bus generators are connected in a DIN rail they do not need to be plugged next to one other and they can also be mixed with the Dupline I O modules The only rule that...

Страница 31: ...etween different rails in a cabinet the Dupline transparent module SH1DUPFT has to be used The SH1DUPFT simplifies the wiring of a building automation installation it has to be connected at the beginn...

Страница 32: ...How to install an UWP 3 0 system 32 Example 3...

Страница 33: ...stall the smart building wireless system 1 5 How to connect the Mobile modem The USB Dongle Connection Module SH2DSP24 has to be connected to the UWP 3 0 through the auxiliary bus on the left side of...

Страница 34: ...onnect the SH2DSP24 to the left of the UWP 3 0 controller 2 Insert the SIM into the dongle USB modem through the SIM slot Make sure the SIM is not protected by a PIN code should that be the case disab...

Страница 35: ...dation Place the modem where there is good signal strength this can be checked by connecting to the UWP 3 0 Tool at the bottom of the user interface there are 5 bars that indicate the field strength a...

Страница 36: ...e Ethernet port LEDS will also light up To configure the IP address please refer to the UWP 3 0 Tool software manual The LAN connection can be used to connect the UWP 3 0 to an Ethernet network when i...

Страница 37: ...for the insertion of the Micro SD memory card 2 Insert the Micro SD card making sure it is not write protected and it is correctly formatted FAT32 3 Close the flap Warning if the flap is not properly...

Страница 38: ...insertion of the Pen drive memory 2 Insert the Pen drive making sure it is not write protected and it is correctly formatted FAT32 3 As soon as you have inserted the Pen drive UWP 3 0 will install th...

Страница 39: ...nd module for AC motor 3 0 W SH2INDI424 Digital input module 0 4 W SH2SSTRI424 Solid state relay output module 0 4W SH2D10V424 1 to 10V dimmer 0 4 W SH2UMMF124 Universal mobile modem 5 0 W The suggest...

Страница 40: ...eed up commissioning Recommendations 1 Use a battery back up system to avoid switching off the installation if a power down should occur 2 Be careful to have a total current not greater than 3A on the...

Страница 41: ...y blue USB LED indicating the presence of a USB device and red Status LED at the first start up it will be ON indicating that no configuration is present or when it is connected to a PC via the UWP 3...

Страница 42: ...common so a three wire connection is needed The shield must be connected directly to earth ground preferably at one point only for the entire RS 485 Bus Generally this point should be chosen on the ma...

Страница 43: ...RS 485 topology Due to signal reflection issues topology is not free but only certain configurations are allowed The only configuration which guarantees sufficient reliability is the daisy chain The...

Страница 44: ...ipment UNAUTHORIZED PEOPLE MUST NOT TOUCH The product contains electrical components constantly under voltage Only skilled personnel correctly trained to operate on circuits constantly under voltage a...

Страница 45: ...amage to the equipment and injury to operators Use cable lugs for any wiring cables DANGER RISK OF DAMAGE AND INJURY AS A RESULT OF INCORRECT GROUNDING Carefully check grounding The user must provide...