How to install an UWP 3.0 system
21
1.3.1.3 Isolator feature
In addition, the isolator feature contributes to the separation of the sides of the bus for maximum safety.
The primary and secondary Dupline® signals are isolated, which means the primary side, made up of the
modules connected to the Dupline® generator, will continue to operate in the case of a short circuit on
the secondary side, made up of the modules connected to the Dupline® repeater.
As shown in the example below, the modules connected to the Dupline generator (shown in the green
box) will continue to operate in the case of a short circuit on the secondary side (shown in the red box)
Example 3
:
UWP 3.0
SB2REP230
As soon as the short circuit is removed, the secondary side will automatically become operational again.
N.B.
In the case of a short circuit on the primary Dupline® side, the secondary Dupline® also goes down:
until the short circuit is removed (see above), neither of the Dupline sides will operate.
1.3.1.4 Placing the SB2REP230 in a project
To wire a Dupline repeater into a network, the Dupline transparent module SH1DUPFT has to be used:
the terminals on the top of the
SH2MCG24
are connected to the Transparent module and the Dupline
repeater just has to be plugged into the local bus connector. The Dupline® repeater is typically mounted
in a different cabinet some distance from the
SH2MCG24
.
The secondary side has to be connected to the terminals REP+ and REP- (see pictures on pages 18 and
19).
The Dupline repeater is able to regenerate the bus voltage starting from a minimum value of 5.5V: care
must be taken to connect it before the voltage drops to below this minimum voltage.
Recommendation:
On each bus branch it is not possible to connect more than one repeater in series: the connection shown
in the picture below must be avoided
.
SH2MCG24
SB2REP230
SB2REP230
Dupline® modules
PRIMARY DUPLINE® SIDE
SECONDARY DUPLINE® SIDE
PRIMARY DUPLINE® SIDE
SECONDARY DUPLINE® SIDE
Dupline®
modules
Dupline®
modules
Содержание UWP 3.0
Страница 1: ...UWP 3 0 HW manual rev 0 7 06 09 2018...
Страница 13: ...How to install an UWP 3 0 system 13 Example 1 The bus generators are all connected in the same Din rail...
Страница 14: ...How to install an UWP 3 0 system 14 Example 2 The bus generators are mounted in different cabinets...
Страница 23: ...How to install an UWP 3 0 system 23...
Страница 32: ...How to install an UWP 3 0 system 32 Example 3...