pre-warning
the RG..N will issue an alarm
Default (0dC)
Output substitute mode
Set the output mode to be used in
case of a communication timeout
0
→
Clear Output
1
→
Hold Output (default)
2
→
Set Value
Output substitute value
Set the % control level to be used in
case of a communication timeout.
(Only applicable for ‘Set Value
option’ for Output substitute mode
0 (default)
–
100%
Switching mode
Set the switching mode that the
RG..N shall use at the output
0
→
External
1
→
ON/OFF (default)
2
→
Burst
3
→
Advanced full cycle
4
→
Distributed full cycle
Timebase
Set the desired timebase. (only
applicable for burst firing mode)
This parameter is in steps of 0.1,
therefore a value of 11 = 1.1s
0.1 (default) - 10s
RG..N commands
Insert value to indicate the
command that shall be executed by
the RG..N
1 -> start a TEACH operation
4 -> store parameters
permanently in RG..N
8 -> clear Latched Alarms in
case latching of alarms is
activated
99 -> factory reset of RG..N
TEACH voltage reference
Holds the reference voltage to be
used for the load deviation alarm.
Value be updated automatically with
a TEACH command or manually.
If TEACH is not successful value will
reset to 0
0 (default)
–
660VAC
TEACH current reference
Holds the reference current to be
used for the load deviation alarm.
Can be updated automatically with
a TEACH command or manually
If TEACH is not successful value will
reset to 0
This parameter is in steps of 0.01,
therefore a value of 1745 = 17.45A
0
–
Max. current limit (RG..N
model dependent)
TEACH % load deviation
Holds the percentage load deviation
used for the load deviation alarm.
4
–
100%
10% (default)
Load running hours reset
Use this index to reset the load
running hours reading in case of load
or SSR replacement in hours
0 hrs (default) -
Energy Reading (low)
(read only)
The energy reading is split into 2
indexes. This index holds the lower
value
0 (default) -
Energy Reading (high)
(read only)
This index holds the upper value of
the energy reading
0 (default) -
SSR ON time
(read only)
Holds the accumulated time in hours
that the output of the RG..N was
switched ON
0 (default) -