EN

 

5.

 

Communication 

5.1

 

Exclusive Owner Connection 

 Implicit Messaging 

 

The implicit data associated with the Exclusive owner connection includes parameters measured by each NRG 
solid state relay as well as the control value from the PLC to control each solid state relay. Start-up parameters are 

delivered on connection established for each end device. Refer to the below tables for the list of information 
provided via implicit messaging. 
 
Connection path: 20 04 24 66 2C 64 2C 65 

 
Request Packet Rate (RPI) range: 8ms 

 512ms 

Time out Multiplier Range: 4 - 512 
 

 

Input Data 

 

Data 

Data type 

Hold Current Reading 

uint16 

Voltage RMS Reading 

uint16 

Frequency Reading 

uint16 

Current RMS Reading 

uint16 

Apparent Power Reading 

uint16 

Real Power Reading 

uint16 

 
 

The  current  measurement  is  returned  as  scaled  integers.  Therefore,  a  current  value  of  16.81A  will  be  received  as 
1681. The PLC program has to convert the numbers into floating point values. For further information regarding the 
scaling of each measurement, refer to the Measurements section in this User Manual. 

 

 

 

Note

: ‘Ref’ terminal connection is required for Voltage, Apparent Power and Real Power readings. Otherwise the 

readings of these parameters will be 0. 
 

Output Data 

 

 

Data

 

Data type 

Control level (0 -100%)

 

uint8 

 

 

 

 
In case of 

ON/OFF

 control mode, a control level 

< 100%

 shall indicate SSR output 

OFF

 and a control level of 

100%

 

shall indicate SSR output 

ON

 

 
For the 

Power control

 firing modes (Burst, Distributed full cycle and Advanced full cycle) the 

% control value

 shall be 

translate to 

% power

 of the SSR output. Refer to Section 6.2 for more information on Switching Modes. 

 
 

5.2

 

Input Only Connection 

 Implicit Messaging 

 

Implicit data from the Input only connection includes the alarming data from each end device connected on the 
bus  chain  as  well  as  the  NRG  controller.  Additionally,  configuration  and  communication  status  data  for  each  end 

device is also transferred. With this connection there are no configuration parameters. 
 
Connection path: 20 04 23 6B 2C 69 2C 6A 

 
Request Packet Rate (RPI) range: 8ms 

 512ms 

Time out Multiplier Range: 4 - 512 

 

Fixed data irrespective of active devices: 

 

 

Name 

Data type 

Description 

Unused Data  

2 bytes, WORD,  
big-endian encoding 

reserved for future use

 

NRG Controller Status  

2 bytes, WORD,  
big-endian encoding 

Bit 0 

 NRG Controller reset Flag 

Bit 1 

 

Not used

 

Bit 2 

 Internal error alarm Flag 

Bit 3 

 

Not used

 

Bit 4 

 Bus error Flag 

Bit 5 

 Device limit error Flag 

Содержание NRGC

Страница 1: ...NRG EtherNet IP User Manual Operating instructions Manuale d istruzioni Betriebsanleitung Manuel d instructions Manual de instrucciones Brugervejledning...

Страница 2: ...0 4 2 Adding the NRGC EIP to a project in Studio 5000 Logix Designer V31 12 4 3 Start up Parameters 14 4 4 EtherNet IP factory reset 15 5 Communication 16 5 1 Exclusive Owner Connection Implicit Messa...

Страница 3: ...equipment Nor can Carlo Gavazzi assume liability for recommendations that appear or are implied in the following description The information in this document is not considered binding on any product w...

Страница 4: ...gislation please note that WEEE cannot be disposed of as municipal waste and such waste must be collected and disposed of separately the public or private waste collection systems defined by local leg...

Страница 5: ...are required for an NRG bus chain Description Part number Notes NRG controller NRGC NRGC NRG Controller with Modbus RTU NRGC PN NRG controller with PROFINET NRGC EIP NRG controller with EtherNet IP 1...

Страница 6: ...It is not required to physically set the ID for each RG N This can be done through an auto addressing function which occurs automatically on the first start up whereby each RG N on the bus chain will...

Страница 7: ...p to 32 NRG solid state relays The NRG controller is the interface to the main controller via the 2xRJ45 shielded communication ports The connection between the NRG controller and the solid state rela...

Страница 8: ...elays are required in an application multiple bus chains can be utilised These can be configured in a line or star topology as deemed fit for the application Wiring between EtherNet IP devices should...

Страница 9: ...d based on their position on the bus In case of an RG N replacement or any changes to the NRG bus chain the RG Ns have to be readdressed Follow the procedure below Figure 6 to readdress the RG Ns on t...

Страница 10: ...onductive and grounded Shielded Cat 5e cables fitted with an outer metallic shell should be used The shell should be connected to the wire screen of the cable Figure 7 Metal din clip on NRG controller...

Страница 11: ...Logix Designer V31 1 Open the EDS Hardware Installation Tool from Tools EDS Hardware Installation Tool Press Next 2 Select Register an EDS file s from the Options dialog window and press Next 3 On th...

Страница 12: ...e to the below should show up in the next dialog box Press Next 5 Press Next for the following 2 dialog boxes Note an image icon is currently not defined in the eDS file 6 Press the Finish button to c...

Страница 13: ...Designer V31 1 Right click on any of the PLC ethernet interfaces and select New Module 2 Select the NRGC EIP device from the Select Module Type dialog window and click the Create button 3 The New Modu...

Страница 14: ...each of the two connections Exclusive Owner and Input Only 5 Select the Disable Keying from the Electronic Keying drop down and then click OK 6 Click Yes when the following message window pops up 7 Cl...

Страница 15: ...M42GEN RGC1A60CM62GEN RGS1A60CM50KEN RGS1A60CM92KEN RGS1A60CM92GEN for future use RGC1P60CM25KEN RGC1P60CM32KEN RGC1P60CM32GEN RGC1P60CM42GEN RGC1P60CM62GEN RGS1P60CM50KEN RGS1P60CM92KEN RGS1P60CM92GE...

Страница 16: ...s reset mode will return as closely as possible to the factory default configuration and then emulate power cycle as closely as possible of the device Apart from the standard reset functionality as sp...

Страница 17: ...Ref terminal connection is required for Voltage Apparent Power and Real Power readings Otherwise the readings of these parameters will be 0 Output Data Data Data type Control level 0 100 uint8 In cas...

Страница 18: ...3 Voltage out of range alarm Flag Bit 4 Current out of range alarm Flag Bit 5 Frequency out of range alarm Flag Bit 6 Over temperature pre warning alarm Flag Bit 7 Temperature out of range alarm Flag...

Страница 19: ...on mode of the device Common services Service code Service Name Class Level Instance Level Description 0x01 Get Attribute All Retrieve all attribute values 0x05 Reset Reset the device 0x4B Flash LEDs...

Страница 20: ...4 Size n a Process data size in number of bytes Common services Service code Service Name Class Level Instance Level Description 0x0E Get Attribute Single Retrieve attribute value 0x10 Set Attribute S...

Страница 21: ...stance Level Description 0x01 Get Attribute All Retrieve all attribute values 0x0E Get Attribute Single Retrieve attribute value Quality of Service Object Object Class No Object Instance Description 0...

Страница 22: ...ess subnet mask gateway address etc 6 Host Name The Host Name attribute contains the device s host name which can be used for informational purposes 8 TTL Value 1 TTL value for EtherNet IP multicast p...

Страница 23: ...ommon Services Service code Service Name Class Level Instance Level Description 0x01 Get Attribute All Retrieve all attribute values 0x0E Get Attribute Single Retrieve attribute value 0x10 Set Attribu...

Страница 24: ...gy Reading low Energy Reading high SSR ON time A description of each parameter with an indication of the possible values is listed in the table below Parameters Description Values Hold current period...

Страница 25: ...tching of alarms is activated 99 factory reset of RG N TEACH voltage reference Holds the reference voltage to be used for the load deviation alarm Value be updated automatically with a TEACH command o...

Страница 26: ...erable fault In this case the module status LED flashes red 5 Major unrecoverable fault In this specific scenario the module status LED is steady red Network Status Returned Value Description 0 Not po...

Страница 27: ...vely a direct replacement of the A1 A2 i e for existing systems the control algorithm within the PLC can be left relatively untouched and the output is redirected via the communication interface All R...

Страница 28: ...firing mode 33 control level Output with Distributed firing mode 50 control level Output with Distributed firing mode 66 control level The advantage of Distributed over Burst is the reduction in ther...

Страница 29: ...s that visual flicker is less noticeable than Distributed thus making it suitable for shortwave infrared heater applications AFC has the disadvantage of worse harmonics emissions than Burst and also s...

Страница 30: ...onstantly 0 Real Power The real power reading is recorded in W This reading is in steps of 1W and hence a value of 567 would mean 567W This value is updated every half cycle and is a multiplication of...

Страница 31: ...forming its power up testing Red NRG Controller has detected a major unrecoverable fault Red Flickering NRG Controller has detected a major recoverable fault OFF NRG Controller is powered off NS Red G...

Страница 32: ...hain Diagnose Confirm that the number of RG Ns connected to one NRG Controller is 32 Termination Error Description This alarm is issued at power up if the NRG controller detects that the BUS between t...

Страница 33: ...ng and surrounding temperature Load deviation alarm Description This alarm works in conjunction with the TEACH Voltage Reference TEACH Current Reference and TEACH load deviation settings If the values...

Страница 34: ...function on the RG N and it is up to the user to decide what to do when this alarm is activated Diagnose Check line frequency and ensure that the over and under frequency limits are set properly Thoug...

Страница 35: ...igger the BUS error alarm via the communication system Diagnose Not applicable Internal error Description This alarm is issued when a problem arises within the internal circuit of the RG N In the pres...

Страница 36: ...th the communications check it is important to turn it off by pressing again the blue button 2 5 secs otherwise PLC cannot communicate with the NRG bus chain 8 2 Replacing an RG N When an RG N has to...

Страница 37: ...REF terminal however this will constitute some limitations as listed below 1 The following readings are not available RMS Voltage Real Power and Apparent Power 2 The TEACH operation cannot be execute...

Отзывы: