G38xx14 Configuration Software
Common siren
Operation:
The common siren gives out a signal depending on the alarm to which it is connected. If all
alarms use common siren, the priority is as follows:
1.
Smoke alarm: Pulsating 1/1 sec.
2.
Intruder
alarm:
Continuously.
3.
ISA
alarm.
3.
Water alarm: Pulsating 4/60 sec.
The common siren is active during the set siren time (0..30 min).
Does not react on a transmit pulse.
Logic functions will activate the output.
Parameters:
Any combination of Smoke alarm, Intruder alarm, ISA alarm and Water alarm
Smoke alarm - Siren time
Intruder aalrm - Siren time
ISA alarm - Siren time
Water alarm - Siren time
Other configurable channel operations
Display of time
Operation:
The internal Real time clock “Hours and minutes” is output on selected channels in a 4-digit
BCD format. Transmission on these channels will not change the receiver output, but can be
used as input for Logic functions.
The Display-of-time function can be used in any application requiring a central master clock.
Displaying of time requires external display receiver modules.
Parameters:
Selection of which channel group pair (16 channels) to be used.
Configured under Basic Set-up, since the used 16 channels cannot be changed, but may influence other
settings made.
.
Multiplexer
Operation:
Outputs a Multiplexing address on channels A1 to A4. Used to enable multiplexed Analog
transfer.
Parameters:
Multiplexer Count (Off, 2,3 ..16), Multiplexer Delay (1,2,4..128).
Configured under Basic set-up, as this function is fixed on channels A1..A4.