USER INTERFACE 

 

 

The front panel contains the display and keyboard, made up from 4 keys, which, pressed individually 
or together, allow to perform all of the controller programming operations.  
 

 
 

3.1 

Display 

The display features 3 digits, with the display of the decimal point between -99.9 and 99.9. Outside of this range of measurement, the value is 
automatically displayed without the decimal (even if internally the unit still operates considering the decimal part). In normal operation, the value 
displayed corresponds to the temperature read by probe B1, that is, the evaporator water inlet temperature*. During the programming it shows the 
codes of the parameters and their value. 
 
(*) Viewing of the standard display can be changed via parameter b00. 

 

 

Icon 

Colour 

Meaning 

With LED on 

With LED flashing 

1, 2 

Amber 

Compressor 1 and/or 2 on 

Start up request 

3 ,4 

Amber 

Not used 

Not used 

 

Amber 

At least 1 compressor on 

 

Amber 

Condenser pump/fan on 

Start up request 

 

Amber 

Condenser fan active 

 

Amber 

Not used 

Not used 

 

Amber 

Heater on 

 

Red 

Alarm on 

 

Amber 

Not used 

Not used 

 

Amber 

Chiller mode 

Chiller mode request 

 
 

3.2 

Keypad 

 

Key 

Machine state 

Pressure mode 

Loading default values 

Controller power supply with key pressed 

Return to upper level up to exit (with saving in EPROM) 

Single press 

 

Access to parameters type “Direct” 
Selection and display of type“Direct” parameter value 
Confirm parameter value variation 

Single press 

 

 

 

 

Parameters programming via introduction of password 

Press for 5 s 

 

 

 

 

(UP)

 

Value increase 

Single of continuous press 

Selection of successive parameter 

Single of continuous press 

Immediate access to values read by the probes (parameters b01, b02,…) 

Single press 

Passage from stand-by to chiller mode and vice versa 

Press for 5 s 

 

 

 

 

(DOWN)

 

Value decrease 

Single or continuous press 

Select previous parameter 

Immediate access to values read by the probes (parameters b01, b02,…) 

Single press 

 

 

 

 

Alarms manual reset 
Immediate timer reset 

Press for 5 s 
 
 

 
 

3.3 

Example: timer reset 

 

 

Pressing 

 e 

 simultaneously, in the timer value display phase (e.g. parameter c10), resets the same at 

zero and consequently cancels the maintenance request. 
 

 
 

3.4 

Programming 

The parameters divide into 4 different levels according to their accessibility by the user via password and their function. Entering a certain level it is possible: 
1. to access all parameters of the same level and the lower levels (S-P menu); 
2. set the desired level for each parameter (L-P menu). 

 

 

Содержание MuC2SE

Страница 1: ...C2 SE for process chiller Electronic controller ENG User manual I n t e g r a t e d C o n t r o l S o l u t i o n s E n e r g y S a v i n g s...

Страница 2: ......

Страница 3: ...ms could suffer irreparable damage Not to use corrosive chemical products aggressive solvents or detergents to clean the device Not to use the product in application environments different than those...

Страница 4: ...4 C2 SE process chiller 030220416 rel 2 3 17 05 2018...

Страница 5: ...n 16 4 2 Configuration 16 4 3 Minimum and maximum fan speed calculation 17 5 FUNCTIONS 18 5 1 Set point 18 5 2 Probes analogue inputs 18 5 3 Probe reading 19 5 4 Digital inputs 19 5 5 Digital outputs...

Страница 6: ...6 C2 SE process chiller 030220416 rel 2 3 17 05 2018...

Страница 7: ...2 display of further warnings alarms on the controller display 3 selection of the digital outputs to switch over 1 2 Codes Description Cod C 2 SE 1 circuit 2 compressors panel assembly MCH2000050 C 2...

Страница 8: ...250 Vac into AC1 1 3 HP inductive Analogue output module code CONV0 10A0 Converts a PWM signal for relay in solid state into an output 0 10 Vdc or 4 20 mA The three phase regulators of the FCS range...

Страница 9: ...the structure of the tLAN network with the C 2 SE controller for process chiller which can operate alone or with the I O expansion board The EVD 4 driver is an optional NETWORK STRUCTURE Key T Evapor...

Страница 10: ...ference ID11 ID15 Digital inputs 11 15 B8 Analogue input 8 C11 C15 Common digital outputs 11 15 NO11 NO15 Digital outputs 11 15 normally open contact V Ratiometric pressure probe power supply Y2 Analo...

Страница 11: ...e power cables and probe cables including those of electric control board into the same cable conduits do not install the probe cables in the immediate vicinity of power devices switches magnet circui...

Страница 12: ...ve or not according to that indicated in the user notes of the specific controller There are two main functions envisioned and they are selected via two dip switches situated under the battery lid The...

Страница 13: ...tly but at the end of the operation the battery voltage is low Flashing simultaneously red green LED signal orange Instrument not compatible The parameters set up cannot be copied because the controll...

Страница 14: ...mode request 3 2 Keypad Key Machine state Pressure mode Loading default values Controller power supply with key pressed Return to upper level up to exit with saving in EPROM Single press Access to par...

Страница 15: ...Set the password via and and confirm with 4 Select the parameters menu S P via and Confirm with 5 Select the parameters category A b c d via and Confirm with 6 Select the parameter via and Confirm wit...

Страница 16: ...replaced by the electronic expansion valve the EVD 4 driver must be connected If connected the I O expansion board allows to configure the digital inputs with 5 new warnings or alarms Moreover it allo...

Страница 17: ...d parameter F04 to the maximum value Given the different types of motors existing on the market it must be possible to set the voltages supplied by the circuit board corresponding to the temperatures...

Страница 18: ...ndenser NT 2 External NTC 3 Differential control 0 0 3 04 Probe B4 0 Absent 1 Digital input 2 External NTC 3 Ratiometric Condenser 4 Differential control 0 0 4 09 Minimum voltage input value 50 0 10 V...

Страница 19: ...ure b11 driver superheating superheated gas temperature evaporation saturate temperature b12 saturation temperature value calculated of the evaporation saturate temperature b13 valve position as b19 c...

Страница 20: ...l input 14 See P37 0 0 10 P41 Digital input 15 See P37 0 0 10 H11 0 1 2 3 4 5 6 NO1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1 NO2 heater 1 heater 1 hea...

Страница 21: ...ited to an acceptable number The storage tank can be eliminated in low load conditions Low load condition 1 only one compressor is active 2 the compressor is switched off after an operating period les...

Страница 22: ...evaporation temperature probe t time 6 4 Compressors management Digital outputs at relay par c01 c02 c03 c04 c05 The parameters in question regard the minimum operating times or switch off times of t...

Страница 23: ...p below this limit Compressors rotation par r05 The rotation of the compressors allows the operating hours to be balanced either statistically using FIFO logic or absolutely by counting the effective...

Страница 24: ...the deactivation of compressors in this mode selected via parameter r12 Below this value the deactivation time will be the same as the minimum set to the temperature value A04 beyond which all compre...

Страница 25: ...tion Def Min Max U M c17 Pump minimum switch off time 30 0 150 min c18 Pump minimum switch on time 3 0 15 min t c18 c07 c08 c17 c18 c17 c18 ON OFF ON OFF CMP P Key CMP Compressor P Pump t time 6 6 Com...

Страница 26: ...rature pressure differential for switch off If the speed controller is used it represents the differential with respect to F05 below which the fans switch off Switch on has a hysteresis of 1 C or 0 5...

Страница 27: ...rs activation threshold and relative set point i e electric heaters activation threshold referring to an operational set point For example if r43 7 the anti freeze support heater will activate below t...

Страница 28: ...0 22 229 R W I A04 Anti freeze heater s set point in stand by see r43 U A01 80 C F 5 AA 13 13 R W A A04 Anti freeze heater s relative set point in stand by see r43 U 0 20 C F 7 AR 77 77 R W A A05 Ant...

Страница 29: ...mp when starting 0 Disabled U 0 999 s 0 FN 91 298 R W I Par Description Level MIN MAX U M DERF Disp SVP Carel ModBus R W Var type Machine setting parameters H H01 Chiller type 2 Air water 4 Water wate...

Страница 30: ...ure alarm threshold 0 alarm disabled F 0 99 9 bar 20 P 39 39 R W A P19 Low temperature alarm threshold U 40 176 C F 10 AA 40 40 R W A P19 Relative low temperature alarm threshold U 0 100 C F 2 AR 83 8...

Страница 31: ...40 80 C F 40 65 65 R W A r27 Accumulation vessel suppression low load 0 Disabled 1 Enabled 2 3 Do not select F 0 3 0 88 295 R W I r28 Min compressor running time for low load F 0 999 s 60 89 296 R W I...

Страница 32: ...l E4 Probe B4 alarm Automatic OFF OFF OFF OFF ON 46 R Probes alarm Digital Hc1 2 Comp 1 2 pumps hour warning Automatic 47 R Compress warning Digital EPr EEPROM error during operation Automatic 50 R Ge...

Страница 33: ...arm is detected after time P03 with compressors off or active depending on P15 The hysteresis for this alarm is 1 bar tP General overload The alarm is detected irrespective of the status of the pump a...

Страница 34: ...y the condenser fan is activated along with the alarm relay and flashing display Whenever C 2 SE is in stand by the alarm condition is not detected but just the heaters are managed Reset depends on pa...

Страница 35: ...s no driver status EU1 Valve open error EVD 1 start I in system start up the driver detects the valve is still open the alarm has passed to C 2 SE which switches the compressors and fans off Eb1 EVD b...

Страница 36: ...fications stated in figure Minimum interval between the communications every relay 12 s it is the task of the machine manufacturer in which the device is incorporated to guarantee the correct configur...

Страница 37: ...shock and maintenance warnings The system made up of the control board MCH200005 and the other optional boards MCH200006 MCH200485 MCHRTF CONVONOFF CONV0 10A EVD000040 constitute a control device to b...

Страница 38: ......

Страница 39: ......

Страница 40: ...REL INDUSTRIES HeadQuarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com C2SE chiller processo 030220416 rel 2 3 17 05 20...

Отзывы: