![Carel MuC2SE Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/carel/muc2se/muc2se_user-manual_2557435010.webp)
10
µC
2
SE process c030220416
- rel. 2.3 - 17.05.2018
2.3
μC
2
SE Wiring diagram
Key
G
24 Vac power supply
G0
Power supply reference
B1…B4
Analogue inputs 1…4
ID1…ID5
Digital inputs 1…5
C1…C5
Common digital outputs 1…5
NO1…NO5
Digital outputs 1…5 normally open contact
Y1
Analogue output 1
Key/SPV
Connector for key/supervisor
V+
Ratiometric pressure probe power supply
Tx/Rx
tLAN port
Ground
Note:
l’uscita digitale 1 non è programmabile ed è destinata al compressore;
gli ingressi analogici B1 e B2 sono riservati rispettivamente alle sonde
ingresso e uscita evaporatore.
2.4
I/O board Wiring diagram
Key
G
24 Vac power supply
G0
Power supply reference
ID11…ID15
Digital inputs 11…15
B8
Analogue input 8
C11…C15
Common digital outputs 11…15
NO11…NO15
Digital outputs 11…15 normally open contact
V+
Ratiometric pressure probe power supply
Y2
Analogue output 2
Tx/Rx
tLAN port
Ground
2.5
Optional connection
The programming key input can be used successively for the connection to the supervision network via RS485 converter.
2.6 Inputs/outputs labelling
μC
2
SE
I/O expansion board
Analogue inputs
B1…B4
B8
Digital inputs
ID1…ID5
ID11…ID15
Analogue outputs
Y1
Y2
Digital outputs
NO1…NO5
NO11…NO15
Notes:
only probe B8 can be connected to the I/O expansion board;
the numbering of the digital inputs/outputs of the expansion board goes from 11 to 15.
!
If the serial line is connected in supervision mode, do not connect to earth the secondary terminal of the supply transformer of the control.