31
ENG
MC DUCT +03U400025 - rel. 4 - 20201201
13
Allows the user to configure the time before Stage
1 (Comp/Water On) and the Purge time for the
Compressor (Comp Off Del).
14
This sets the clean-out cycle for the atomizing heads.
When enabled, whenever the system runs for more
than the Time ON, it will shut down for Time OFF to
allow the heads to automatically clean themselves.
This feature is not needed with demineralized water
and may be disabled.
3.8 Factory Settings
(Initial password is 9999)
1
If a sensor is wired into the system, enable it by
setting it to YES.
2
If a sensor is wired into the system, enable it by
setting it to YES.
3
Enter the number of humidification stages.
4
Enter the type of signal from the sensor. (0-10Vdc,
0-1Vdc, 4-20mA)
Enter the sensor’s scale over the input range.
5
Enter the type of signal from the sensor. (0-10Vdc,
0-1Vdc, 4-20mA)
Enter the sensor’s scale over the input range.
6
Enter the type of signal from the sensor. (0-10Vdc,
0-1Vdc, 4-20mA)
Enter the sensor’s scale over the input range.