18
ENG
MC DUCT +03U400025 - rel. 4 - 20201201
PC-301 Air Proving Switch
Mounting the PC-301 air flow switch:
Mount the airflow switch in the supply or return duct using the
screws supplied. Mount the device so that the diaphragm is in a
vertical position as shown at right.
If the airflow switch is to be mounted on the return duct
(vacuum), then mount it in a vertical position by the small plate.
Drill a 7/16” hole in the side of the duct and connect the supplied
tubing to the low pressure tap on the airflow switch and then
run it through the drilled hole in the duct. Put no more than 2” of
tubing into the duct. Caulk around the tubing where it enters the
duct. The high pressure tap is left open to atmosphere.
If the airflow switch is to be mounted to the supply duct
(pressure), then drill a 7/16 hole in the side of the duct, apply
caulking to the large plate, and mount the device with the large
plate to the duct and the high pressure tap/tubing mated to the
hole. The low pressure tap is left open to atmosphere.
Mounting Diagram
Maximum Electrical Switch Ratings
Vac
Full Load
Amps
Locked Rotor
Amps
Pilot Duty
(VA)
Non-Inductive
Amps
24V
-
-
60
10
120V
6.25
37.5
300
10
240V
3.1
18.6
300
10
277V
2.7
16.2
300
10
Wiring Diagram
NOTE:
There is an adjustment screw located under the metal
cover. This must be adjusted to insure that the air flow switch
turns on during air flow and off when air flow ceases.