19
ENG
MC DUCT +03U400025 - rel. 4 - 20201201
DPWC/DPWT- DPDC Wall – Duct Temperature/Humidity Sensors
Model
Description
Humidity:
Thin film capacitor
Linear 0-1 Vdc or 4-20 mAdc from 10 to 90%RH
Accuracy: +- 3%RH from 20 to 90%RH
calibrated at 55%RH and 25°C (77°F)
+- 5%RH above 90%RH and below 20%RH
Response time:
60 seconds
Power:
12 to 24 Vac/dc or +12 to –12 Vdc
Housing:
Wall: ABS with glass fiber fill
Certifications
: Calibrated to NIST traceable humidity/
temperature standard, CE Approved
Humidity (0-1 VDC or 4-20 mADC)
DPWC111000 Wall Humidity sensor (replaces ASWH100000 and SHWOOP)
DPDC110000 Duct Humidity sensor (replaces ASDH100000 and SSDOMH00/1)
Temperature & Humidity (NTC temp, 0-1 VDC or 4-20 mADC humidity)
DPWC111000
Wall Temp/hum sensor (replaces SWNTCTH0/1, STHONTC0/1 and
ASWC111000)
DPWC110000 Wall Temp/hum sensor (replaces STHOAP AND ASWC110000)
Temperature & Humidity (0-1 VDC or 4-20 mADC temp & humidity)
DPDC111000 Duct temp/hum sensor (replaces SDNTCTH0/1 AND ASDC111000)
DPDC110000
Duct temp/hum sensor (replaces SSDOMHT0/1 AND ASDC110000)
IMPORTANT:
If you are going to control the MC system from a DDC
system (and therefore Carel is not supplying any sensors, it is vitally
important that the preheat, cooling, and reheat systems are all integrated
to compensate for and take advantage of the evaporative cooling
effect of the atomizing system. If the following control sequence is not
followed, CAREL cannot be held responsible for improper evaporation
of the mist generated.