6. OPERATION OPTIONS
6.1 Main menu and overview of functions
Access the main menu by pressing PRG. This menu lists a number of
submenus, where all the unit parameters can be read and set if necessary.
Each submenu is divided into a number of screens identified by the
index shown at the top right on the display. The table below provides a
complete overview of the screens.
Menu
Index
Description
A. Clock
Change time and data A01
Set date, time and date format
B. Scheduler
Scheduler
B01
Enable time bands
B02
(visible if time bands are enabled
Time band setting: day, ON time, OFF time
C. Inputs/Outputs
Analogue inputs
C01
Read water probes: feedwater pressure, outlet pressure, bypass temperature
C02
Read control probes: main zone 1, limit zone 1, main zone 2, limit zone 2
Digital inputs
C03
Read digital inputs
Analogue outputs
C04
Read production request [%] for zone 1 and for zone 2
Unit digital outputs
C05
Read status of contactor, fill valve (feedwater), drain valve (cabinet), bypass drain valve
Digital outputs, zone 1 C06
Read status of fill (outlet) and drain valve (return) for zone 1, fan status in zone 1
Digital outputs, zone 2 C07
Read status of fill (outlet) and drain valve (return) for zone 2, fan status in zone 2
Unit digital outputs
C08
Read unit status contact, alarm relay, cabinet fan enabling contact, external water treatment system
enabling contact
D. Settings
(password_ _ _ _)
a. Control
Da01
Set type of control in zone 1 and maximum production
Da02
Set type of control in zone 2 and maximum production
Da03
(visible if control using two main probes is enabled)
Weight of control probes in zone 1
Da04
Set point and band for the main probe in zone 1
Da05
Set point and band for the limit probe in zone 1
Da06
(visible if control using two main probes is enabled)
Weight of control probes in zone 2
Da07
Set point and band for the main probe in zone 2
Da08
Set point and band for the limit probe in zone 2
Da09
Maintenance hour counter, reset hour counter and set maintenance warning
Da10
Displayed after 40 hours of operation
Possibility to reset the oil change hour counter
(warning activated after 50 h)
Da11
Unit hour counter, not resettable
Da12
Unit hour settings (e.g. after replacing c.pHC controller) and maintenance warning
b. Functions
Db01
Enable filling and set fil duration
Db02
Set wash duration and frequency
Db03
Enable management of external water treatment system
Db04
Manage blower fan delay at unit start-up and shutdown
Db05
Export event log
Db06
Export alarm log
c. Configuration
Dc01
Set type of signal from the main humidity probe in zone 1, minimum/maximum probe reading, probe
offset, enable probe disconnected alarm and delay associated with the alarm
Dc02
Set type of signal from the main temperature probe in zone 1, minimum/maximum probe reading,
probe offset, enable probe disconnected alarm and delay associated with the alarm
Dc03
Set type of external signal for zone 1, minimum/maximum signal, signal offset
Dc04
Set N.O./N.C. logic for the control on/off external contact (humidistat)
Dc05
Set type of signal from the limit humidity probe in zone 1, minimum/maximum probe reading, probe
offset, enable probe disconnected alarm and delay associated with the alarm
Dc06
Set type of signal from the limit temperature probe in zone 1, minimum/maximum probe reading,
probe offset, enable probe disconnected alarm and delay associated with the alarm
Dc07
Set type of signal from the main humidity probe in zone 2, minimum/maximum probe reading, probe
offset, enable probe disconnected alarm and delay associated with the alarm
Dc08
Set type of signal from the main temperature probe in zone 2, minimum/maximum probe reading,
probe offset, enable probe disconnected alarm and delay associated with the alarm
Dc09
Set type of external signal for zone 2, minimum/maximum signal, signal offset
Dc10
Set N.O./N.C. logic for the control on/off external contact (thermostat)
Dc11
Set type of signal from the limit humidity probe in zone 2, minimum/maximum probe reading, probe
offset, enable probe disconnected alarm and delay associated with the alarm
Dc12
Set type of signal from the limit temperature probe in zone 2, minimum/maximum probe reading,
probe offset, enable probe disconnected alarm and delay associated with the alarm
Dc13
Set wireless probes 1-4: main, limit or absent
Dc14
Set wireless probes 5-8: main, limit or absent
Dc15
Enable wireless probes 1-4 for the main control/limit function in zone 1/2
Dc16
Enable wireless probes 5-8 for the main control/limit function in zone 1/2
Dc17
Weight [%] of the wireless probes
Dc18
Humidification load in zone 1/2
Dc19
Set delay in opening and closing the drain valve in zone 1
Dc20
Set delay in opening and closing the drain valve in zone 2
d. Network
Dd01
Enable network of humidifiers by Prg button
(if enabled, the network symbol is displayed at the top right of
the main screen)
Dd02
IP address setting of cabinet 1/2/3/4 in the network and check online/offline status
Dd03
Set maximum load and set grouped/balanced distribution
Dd04
Set rotation time (0 h = rotation disabled)
Dd05
Unit offline alarm timeout
Содержание humiFog direct
Страница 2: ......
Страница 4: ...4 ENG humiFog direct 0300073EN rel 1 0 31 03 2017...
Страница 6: ...6 ENG humiFog direct 0300073EN rel 1 0 31 03 2017...
Страница 38: ...38 ENG humiFog direct 0300073EN rel 1 0 31 03 2017 12 APPENDIX 12 1 Single zone cabinet wiring diagram Fig 12 a...
Страница 39: ...39 ENG humiFog direct 0300073EN rel 1 0 31 03 2017 12 2 Two zone cabinet wiring diagram Fig 12 b...
Страница 43: ......