55
ENG
“heaterSteam” +0300080EN - rel. 1.0 - 27.04.2016
The address to be used by the Access Point is set using the dipswitches
on the device, and is the following:
DIP:
1 2 3 4
+
+ G
-
-
Rx- Rx+ GND
L1 L2 L3
T1
DIP
1-2-3
selezione indirizzo di rete
DIP
4
selezione baud di rete
Dipswitch
Access
Point add.
Serial port baud rate
(Bit/S) N82
1
2
3
4
2
19200
OFF ON OFF ON
Fig. 12.c
This assigns the address 2 to the Access Point, with a baud rate (Bit/sec)
of 19200 (N82). The addresses of the four serial probes, on the other hand,
must be set as shown in the table below:
Address
Dipswitch
1
2
3
4
5
6
7
8
Probe 1
16
0
0
0
0
1
0
0
0
Probe 2
17
1
0
0
0
1
0
0
0
Probe 3
18
0
1
0
0
1
0
0
0
Probe 4
19
1
1
0
0
1
0
0
0
Tab. 12.l
Remember to verify the quality of the wireless signal between the Access
Point and each wireless probe.
For a complete description of the installation procedure, see the Carel
manual on the corresponding probes and Access Point.
To confi gure the probes, go the screens: Ec03, Ec04, Ec05, Ec06 and Ec07,
described in paragraph 7.4.3 “Wireless probes”.
In particular, screen Ec03 is used to enable the wireless probes connected
to the Access Point, knowing that addresses 16, 17, 18 and 19 are Probe 1,
Probe 2, Probe 3 and Probe 4 respectively.
Address: 16
Address: 17
Address: 18
Address: 19
Note:
the wireless probes are managed on the heaterSteam
titanium version.
12. WIRELESS PROBES, INSTALLATION AND CONFIGURATION
Recommended Carel wireless probes are the room (WS01G01M00) or
industrial versions (WS01F01M00), both of which measure humidity
and temperature. The type of installation is shown in the fi gure below
(referring to four wireless room probes):
2
1
4
3
Key:
1.
HeaterSteam humidifi er;
2.
humidifi er/Access Point connection;
3.
Access Point (WS01AB2M20);
4.
Wireless probes for measuring
temperature and humidity (WS01G01M00
or WS01F01M00).
Fig. 12.b
HeaterSteam/Access point connection:
To connect the humidifi er to the access point, use the Fieldbus
connection on terminal M3 (M3.1: Tx/Rx-, M3.2: Tx/Rx+, M3.3: GND):
Note:
the devices have a range of around a hundred metres in a free
space, i.e. without any obstacles. In a closed space, the range varies
considerably depending on the type of environment and the surrounding
objects (shelves, metal partition walls etc.).
If installing multiple wireless probes, the controller will calculate the
weighted average between the various probe readings, depending on
the settings made by the user and the defi ned probe groups. Also see
paragraph 7.4.3 Wireless probes. The controller also displays (locally only)
the battery and signal level for each probe (screen index D05-D08).
The table below shows the part numbers and descriptions of the Carel
devices that can be used:
P/N
Model
Features
Power supply
WS01F01M00
SI Probe
Temperature/
humidity for
industrial use
Battery
WS01G01M00
SA probe
Room
temperature/
humidity
Battery
WS01AB2M20
Access
Point
Wireless gate-
way ZigBee™ –
RS485 ModBus
12/24 Vac/dc ±10%
100 mA; 50/60 Hz;
Use a Class II safety
transformer with
minimum power
rating of 2 VA. A 12
Vac transformer is
recommended
Tab. 12.k
12.2 Wireless probe installation
The main steps for installing the wireless devices are:
•
power up the Access Point (12/24 Vac/dc ±10%m, 100mA) and
complete the initialisation procedure, creating the network and
selecting the channel;
•
after having opened the domain on the Access Point, complete the
binding procedure so as to uniquely identify each probe.
12.1 Type of installation and wireless probe
electrical connections
Wireless probes are available for systems where standard wired probes
cannot be used, for example modifi cations to existing installations. An
Access Point (CAREL P/N: WS01AB2M20) is used to connect up to four
wireless probes.
Содержание heaterSteam
Страница 2: ......
Страница 4: ......
Страница 86: ...86 ENG heaterSteam 0300080EN rel 1 0 27 04 2016...
Страница 87: ......