48
ENG
“heaterSteam” +0300080EN - rel. 1.0 - 27.04.2016
Variable
Variable name
R/W
Description
Category
47
Year
RW
Year
Clock
48
Month
RW
Month
49
Day
RW
Day
50
Hour
RW
Hour
51
Minute
RW
Minutes
52
SetTimezone
RW
Time zone
53
NetStatus[1]
R
Unit 1 status
Network
feedback
54
NetStatus[2]
R
Unit 2 status
55
NetStatus[3]
R
Unit 3 status
56
NetStatus[4]
R
Unit 4 status
57
NetStatus[5]
R
Unit 5 status
58
NetStatus[6]
R
Unit 6 status
59
NetStatus[7]
R
Unit 7 status
60
NetStatus[8]
R
Unit 8 status
61
NetStatus[9]
R
Unit 9 status
62
NetStatus[10]
R
Unit 10 status
63
NetStatus[11]
R
Unit 11 status
64
NetStatus[12]
R
Unit 12 status
65
NetStatus[13]
R
Unit 13 status
66
NetStatus[14]
R
Unit 14 status
67
NetStatus[15]
R
Unit 15 status
68
NetStatus[16]
R
Unit 16 status
69
NetStatus[17]
R
Unit 17 status
70
NetStatus[18]
R
Unit 18 status
71
NetStatus[19]
R
Unit 19 status
72
NetStatus[20]
R
Unit 20 status
93
SV_Command
RW
1: reset alarms, 2: reset hour counter
Comm
94
SV_CommandResult
R
1: successful, 2: failed, 3: invalid command
Tab. 11.b
Analogue variables
Variable
Variable name
R/W
Description
Category
1
MainPrb
R
Main probe value (REAL)
I/O
2
LimitPrb
R
Limit probe/second probe value (REAL)
3
PreheatPrb
R
NTC preheating probe value (REAL)
4
WirelessPrbVal_1.Hum
R
Wireless probe 1: Humidity
Wireless probes
5
WirelessPrbVal_1.Temp
R
Wireless probe 1: Temperature
6
WirelessPrbVal_2.Hum
R
Wireless probe 2: Humidity
7
WirelessPrbVal_2.Temp
R
Wireless probe 2: Temperature
8
WirelessPrbVal_3.Hum
R
Wireless probe 3: Humidity
9
WirelessPrbVal_3.Temp
R
Wireless probe 3: Temperature
10
WirelessPrbVal_4.Hum
R
Wireless probe 4: Humidity
11
WirelessPrbVal_4.Temp
R
Wireless probe 4: Temperature
12
SV_PwrReq
RW
Production request percentage from supervisor
Unit Status
13
CurrProdPh
R
Current production in kg/h (lbs/h)
15
GlbSetP_Hum
RW
Humidity control set point
Regulation
16
GlbSetP_Temp
RW
Temperature control set point
17
RegulationCfg.Hyst
RW
Control hysteresis
18
RegulationCfg.Diff RW
Control
diff erential
19
GlbSetPLim_Hum
RW
Set point limit for humidity control
20
GlbSetPLim_Temp
RW
Set point limit for temperature control
21
RegulationCfg.Diff Lim
RW
Limit diff erential
22
RegulationCfg.MinReq
RW
Minimum production
23
AlrmThrshHumLo
RW
Low humidity alarm threshold
Alarms Thresholds
24
AlrmThrshHumHi
RW
High humidity alarm threshold
25
AlrmThrshHumHiLim
RW
High humidity limit alarm threshold
26
AlrmThrshTempLo
RW
Low temperature alarm threshold
27
AlrmThrshTempHi
RW
High temperature alarm threshold
28
AlrmThrshTempHiLim
RW
High temperature limit alarm threshold
29
MainPrbCfg.Mi_Hum
RW
Main probe minimum humidity value
Probes cfg
30
MainPrbCfg.Ma_Hum
RW
Main probe maximum humidity value
31
MainPrbCfg.Mi_Temp
RW
Main probe minimum temperature value
32
MainPrbCfg.Ma_Temp
RW
Main probe maximum temperature value
33
LimitPrbCfg.Mi_Hum
RW
Limit probe minimum humidity value
34
LimitPrbCfg.Ma_Hum
RW
Limit probe maximum humidity value
35
LimitPrbCfg.Mi_Temp
RW
Limit probe minimum temperature value
36
LimitPrbCfg.Ma_Temp
RW
Limit probe maximum temperature value
37
RegulationCfg.PwrCorrectionFactor
RW
Power correction for thermal dissipation
Unit Cfg
38
SchedDayCfg[0].SetP
RW
Band 1 set point
Scheduler
39
SchedDayCfg[1].SetP
RW
Band 2 set point
40
SchedDayCfg[2].SetP
RW
Band 3 set point
41
SchedDayCfg[3].SetP
RW
Band 4 set point
42
SchedDayCfg[4].SetP
RW
Band 5 set point
43
SchedDayCfg[5].SetP
RW
Band 6 set point
44
NetReq
R
Current system request
Network feedback
45
NetProd
R
Current system production
Tab. 11.c