22
ENG
“heaterSteam” +0300080EN - rel. 1.0 - 27.04.2016
Screen ind.
Screen desc.
Parameter
Ea01
Control type
prop. to external signal with limit probe
Ea03
Proportional band Set:
Hysteresis (0-100%)
Minimum production (0-100%)
Maximum production (0-100%)
Ea06
Limit probe
Set:
Set point (0-100 %rH)
Diff erential (0-100%)
Ec01
Main probe type
Select from: 0-1V, 0-10V, 2-10V, 0-20mA,
4-20mA
Ec02
Limit probe type
Select from: 0-1V, 0-10V, 2-10V, 0-20mA,
4-20mA
OUT
REF
M2
M9
M8
1
1
2
3
4
5
6
7
8
2
1
2
OUT H / T
M
+ (G)
Fig. 4.s
Note:
in industrial environments (IEC EN61000-6-2) the signal cables
leaving the unit must not exceed 30 m (98’) in length: steam production
signal cable (terminals M2.1, M2.2), digital remote on/off input (terminals
M2.7, M2.8) and shielded cable for RS485 communication.
4.6 Control with humidity probes
The main control board, connected to a room humidity probe, manages
steam production based on the humidity measured. A second outlet
humidity limit probe can also be connected: with this confi guration,
typical of air handling units, the main control board continues managing
steam production according to the humidity requirement, however
production is limited according to the relative humidity measured in the
outlet duct.
HP
HLP
Remote
Contact
Fig. 4.t
Key:
HP
Humidity control probe (intake/room humidity probe)
HLP
Limit humidity probe (outlet humidity probe)
Remote Contact Remote contact
CONTROL WITH ONE HUMIDITY PROBE
•
short-circuit terminals M2.7 – M2.8 (jumper) to enable production;
alternatively connect terminals M2.7 – M2.8 to a remote contact (e.g.:
switch, timer,...);
•
connect the main active room probe to terminals M2.1, M2.2 (GND)
and M2.3 (+12Vdc);
•
to enable control, set:
Screen ind.
Screen desc.
Parameter
Ea01
Control type
one humidity probe
Ea05
Modulating control
Set:
humidity set point (0-100 %rH)
diff erential (2-20%rh)
Minimum production (0-100%)
Maximum production (0-100%)
Ec01
Main probe type
Select from: 0-1V, 0-10V, 2-10V,
0-20mA, 4-20mA
M2
M9
M8
1
1
2
3
4
5
6
7
8
2
1
2
OUT H / T
M
+ (G)
M
ain pr
obe
Fig. 4.u
_________________________________________________________
CONTROL WITH ONE HUMIDITY PROBE AND LIMIT PROBE
•
short-circuit terminals M2.7 – M2.8 (jumper) to enable production;
alternatively connect terminals M2.7 – M2.8 to a remote contact (e.g.:
switch, timer,...);
•
connect the main active room probe to terminals M2.1, M2.2 (GND)
and M2.3 (+12Vdc);
•
connect the active limit probe to terminals M2.5, M2.3 (+12Vdc), M2.6
(GND);
•
to enable control, set:
Screen ind. Screen desc.
Parameter
Ea01
Control type
humidity with limit probe
Ea05
Modulating
control
Set:
humidity set point (0-100 %rH)
diff erential (2-20%rh)
Minimum production (0-100%)
Maximum production (0-100%)
Ea06
Limit probe
Set point (0-100 %rH)
Diff erential (0-100%)
Ec01
Main probe type Select from: 0-1V, 0-10V, 2-10V, 0-20mA, 4-20mA
Ec02
Limit probe type Select from: 0-1V, 0-10V, 2-10V, 0-20mA, 4-20mA
M2
M9
M8
1
1
2
3
4
5
6
7
8
2
1
2
OUT H / T
M
+ (G)
M
ain pr
obe
OUT H / T
M
+ (G)
S
e
cond pr
obe
Fig. 4.v
The following probes can be connected:
CAREL probes for rooms
DPWC111000
for air ducts
DPDC110000, DPDC210000
for technical applications
DPPC210000, DPPC210000
Note
: non-CAREL active probes can be connected to the controller.