91
ENG
Web server
g0300122EN rel. 1.0 - 01.12.2021
Type
Add. Variable name
Description
Def.
Min
Max
UoM
Access
Boolean
83
Alrm_NetUnit_17.Active Alarm ALN17: Problems on network unit 17
RW
Boolean
84
Alrm_NetUnit_18.Active Alarm ALN18: Problems on network unit 18
RW
Boolean
85
Alrm_NetUnit_19.Active Alarm ALN19: Problems on network unit 19
RW
Boolean
86
Alrm_NetUnit_20.Active Alarm ALN20: Problems on network unit 20
RW
Boolean
87
Alrm_WirelessPrb_1_
LowBatt.Active
Alarm ALP05: Wireless probe 1 low battery
RW
Boolean
88
Alrm_WirelessPrb_2_
LowBatt.Active
Alarm ALP06: Wireless probe 2 low battery
RW
Boolean
89
Alrm_WirelessPrb_3_
LowBatt.Active
Alarm ALP07: Wireless probe 3 low battery
RW
Boolean
90
Alrm_WirelessPrb_4_
LowBatt.Active
Alarm ALP08: Wireless probe 4 low battery
RW
Boolean
91
Alrm_WirelessPrb_Main.
Active
Alarm ALA05: Wireless main probe not available
RW
Boolean
92
Alrm_WirelessPrb_Limit.
Active
Alarm ALA06: Wireless limit probe not available
RW
Boolean
101
Klixon_Fan_1
Flue gas Klixon safety thermostat status 1
RW
Boolean
102
Klixon_Fan_2
Flue gas Klixon safety thermostat status 2
RW
Boolean
103
Klixon_Fan_MB_3
Flue gas Klixon safety thermostat status 3
RW
Boolean
104
Flame_1_Present
Burner 1 fl ame presence status
RW
Boolean
105
Flame_2_Present
Burner 2 fl ame presence status
RW
Boolean
106
Flame_MB_3_Present
Burner 3 fl ame presence status
RW
Boolean
107
Burner1_GO
Burner 1 gas ignition command status
RW
Boolean
108
Burner2_GO
Burner 2 gas ignition command status
RW
Boolean
109
Burner3_GO
Burner 3 gas ignition command status
RW
Boolean
113
BackupHwReq
Hardware backup request
RW
Boolean
114
Alrm_Termic_Fan_1.
Active
Alarm ALA07: Thermal protector 1 active
RW
Boolean
115
Alrm_Termic_Fan_2.
Active
Alarm ALA08: Thermal protector 2 active
RW
Boolean
116
Alrm_Fumes_1_broke.
Active
Alarm ALP10: Flue gas probe 1 broken
RW
Boolean
117
Alrm_Fumes_2_broke.
Active
Alarm ALP11: Flue gas probe 2 broken
RW
Boolean
118
Alrm_warning_
fumes_1.Active
Warning ALP13: Flue gas 1
RW
Boolean
119
Alrm_warning_
fumes_2.Active
Warning ALP14: Flue gas 2
RW
Boolean
120
Alrm_fumes_1.Active
Alarm ALP16: Flue gas 1
RW
Boolean
121
Alrm_fumes_2.Active
Alarm ALP17: Flue gas 2
RW
Boolean
122
Alrm_Termic_Fan_3.
Active
Alarm ALA09: Thermal protector 3 active
RW
Boolean
123
Alrm_Fumes_3_broke.
Active
Alarm ALP12: Flue gas probe 3 broken
RW
Boolean
124
Alrm_fumes_3.Active
Alarm ALP18: Flue gas 3
RW
Boolean
125
Alrm_warning_
fumes_3.Active
Warning ALP15: Flue gas 3
RW
Boolean
126
Alrm_Fan_1.Active
Alarm ALA10: Fan 1
RW
Boolean
127
Alrm_Fan_2.Active
Alarm ALA11: Fan 2
RW
Boolean
128
Alrm_Fan_3.Active
Alarm ALA12: Fan 3
RW
Boolean
129
Al_AntiFreeze_1.Active
Alarm ALA13: Frost protection check components
RW
Boolean
130
Al_Secondary_450_Of-
fLine.Active
Alarm ALA14: Secondary 450 online
RW
Boolean
131
Al_Main_450_Off Line.
Active
Alarm ALA15: Main 450 offl
ine
RW
Boolean
132
Al_AntiFreeze_2_Sec-
ondary.Active
Alarm ALA17: Secondary frost protection
RW
Boolean
133
Al_Speed_Fault_Fan_1.
Active
Alarm ALA20: Fan 1 speed error
RW
Boolean
134
Al_Speed_Fault_Fan_2.
Active
Alarm ALA21: Fan 2 speed error
RW
Boolean
135
Al_Speed_Fault_Fan_3.
Active
Alarm ALA22: Fan 3 speed error
RW
Boolean
136
Alrm_SVOffl
ine.Active
Alarm ALP21: Supervisor offl
ine
RW
Boolean
137
Alrm_MissingModel_S.
Active
Alarm ALP24: No secondary model
RW
Boolean
138
Alrm_WMiss_S.Active
Alarm ALP25: Secondary no water
RW
Boolean
139
Alrm_Foam_S.Active
Alarm ALM21: Secondary foam warning
RW
Boolean
140
Alrm_LowProd_S.Active Alarm ALB03: Secondary low production
RW
Boolean
141
Alrm_LevSen_S.Active
Alarm ALC05: Secondary level sensor broken
RW
Boolean
142
Alrm_Autotest_S.Active Alarm ALC06: Secondary autotest failed
RW
Boolean
143
Alrm_CylFull_S.Active
Alarm ALW12: Secondary cylinder full alarm
RW
Boolean
144
Alrm_HighConductAl_S.
Active
Alarm ALC07: Secondary high conductivity
RW
Boolean
145
Alrm_PreHPrb_S.Active Alarm ALA18: Secondary preheating probe broken or
disconnected
RW
Boolean
146
Alrm_ConductPrb_S.
Active
Alarm ALA19: Secondary conductivity probe
RW
Boolean
147
Alrm_RetMem_S.Active Alarm ALR02: Secondary retain memory
RW
Boolean
148
Warn_Autotest_S.Active Warning ALW07: Secondary autotest
RW
Boolean
149
Warn_LevSen_S.Active
Warning ALW10: Secondary level sensor
RW
Boolean
150
Warn_LowProd_S.Active Warning ALW11: Secondary low production
RW
Boolean
151
Al_AntiFreeze_2.Active
Alarm ALA16: Frost protection force preheating
RW
Boolean
152
EnHiConductAlrm
Enable high conductivity alarm
TRUE
RW
Boolean
153
ManDrain
Manual total drain command (1=startup; value changes
from 1 to 0 when drain is complete)
RW
Boolean
154
ManDrain_Secondary
Secondary unit manual total drain command (1=startup;
value changes from 1 to 0 when drain is complete)
RW
Boolean
155
EnPreheatOff
Enable preheating function (0=disabled, 1=enabled)
FALSE
RW
Boolean
156
EnPartFills
Enable micro-fi lling function to restore water level (0=disa-
bled, 1=enabled)
FALSE
RW