Installation notes
g0300122EN rel. 1.0 - 01.12.2021
ga
S
team layout with
DP
series steam distributor
12
15
9
6
14 13
11 10
2
1
5
4
3
8
7
Limit set point 90%
A
D
min 3xA
D
(min 3m/9.8 ft)
ARIA ESTERNA
ARIA DI MANDATA
ARIA IN USCITA
ARIA DI RIPRESA
ARIA DI
RICIRCOLO
Fig. 6.b
Key:
Ref.
Description
Ref.
Description
1
Air intake probe
9
Air fl ow switch
2
Limit probe
10
Water inlet shut-off valve
3
Steam distributor
11
Filter (not supplied as standard)
4
Condensate drain trap
12
Water fi ll pipe
5
Condensate drain pipe
13
Water drain pipe
6
Steam hose
14
Elbow
7
Signal / power input
15
Drain trap
8
Gas inlet line
Tab. 6.b
Notice:
• A
D
: Steam absorption distance (also see paragraph 8.1 Steam distribution).
– For a length equal to at least A
D
, there must be no obstacles of any type downstream of the steam distributor. This ensures
best absorption of the steam into the air, thus avoiding the formation of condensate or wetting of parts and components
of the AHU/duct.
– The limit probe must be placed three times further than the estimated absorption distance (A
D
).
– If the estimated absorption distance is not known, the limit probe must be placed at least 3 m from the distributor.
The suggested set point for the limit probe is 90% rH.
OUTLET AIR
EXTERNAL AIR
RETURN AIR
OUTLET AIR
RECIRCULATION
AIR