21
ENG
“EVD mini” +0300036EN - rel. 1.2 - 23.04.2018
7. PARAMETERS
TABLE
Par.
Description
Def.
Min.
Max.
UOM
Type
Carel Modbus® R/W
Note
BASIC (INITIAL CONFIGURATION)
GAS
Type
Refrigerant
1
R22
15
R422D
29
R455A (-1...12.8 barg)
2
R134a
16
R413A
30
R170 (0...17.3 barg)
3
R404A
17
R422A
31
R442A (-1...12.8 barg)
4
R407C
18
R423A
32
R447A (-1...12.8 barg)
5
R410A
19
R407A
33
R448A
6
R507A
20
R427A
34
R449A
7
R290
21
R245FA
35
R450A (-1...4.2 barg)
8
R600(-1...4.2 barg)
22
R407F
36
R452A (-1...12.8 barg)
9
R600a (-1...4.2 barg) 23
R32
(0...17.3
barg)
37
R508B (-1...4.2 barg)
10
R717
24
HTR01
38
R452B
11
R744 (0...45 barg)
25
HTR02
39
R513A (-1...4.2 barg)
12
R728
26
R23
40
R454B
13
R1270
27
R1234yf
41
R458A
14
R417A
28
R1234ze
(-1...4.2
barg)
3
1
41
-
I
12
139
R/W
Mode Operating mode
1
Multiplexed cabinet/cold room
2
Air-conditioner/chiller with plate heat exchanger
3
Air-conditioner/chiller with tube bundle heat exchanger
4
Air-conditioner/chiller with finned coil heat exchanger
5
Analogue positioner (0 to 10 V)
6
Superheat control with 2 temperature probes
7
Subcritical CO2 showcase/cold room
8
Hot gas bypass by pressure
9
Hot gas bypass by temperature
1
1
9
-
I
13
140
R/W
Super
Heat
Superheat set point
11
(20)
LowSH
protec-
tion: th-
reshold
55
(99)
K
(°F)
A
10
9
R/W
_P
Hot gas bypass pressure set point
3
-20(-
290)
200(2900)
barg
(psig)
A
23
22
R/W
_t
Hot gas bypass temperature set point
10
-85(-
121)
200(392)
°C(°F)
A
22
21
R/W
SERVICE
P1
Probe S1 reading
-
-85
(-290)
200
(2900)
barg
(psig)
A
6
5
R
P2
Probe S2 reading
-
-85
(-121)
200
(392)
°C(°F)/
V
A
7
6
R
tE
Evaporation temperature (converted)
-
-85
(-121)
200
(392)
°C
(°F)
A
4
3
R
tS
Suction temperature
-
-85
(-121)
200
(392)
°C
(°F)
A
3
2
R
Po
Valve opening
-
0
100
%
A
1
0
R
CP
PID: proportional gain
15
0
800
-
A
11
10
R/W
ti
PID: integral time
150
0
999
s
I
17
144
R/W
C1
LowSH protection: threshold
5(9)
-5
(-9)
Superh. set
point
K
(°F)
A
12
11
R/W
C2
LowSH protection: integral time
15
0
800
s
A
13
12
R/W
C3
LOP protection: threshold
-50(-58)
-85(-
121)
MOP
protection:
threshold
°C
(°F)
A
14
13
R/W
C4
LOP protection: integral time
0
0
800
s
A
15
14
R/W
C5
MOP protection: threshold
50
(122)
LOP
protec-
tion: th-
reshold
200
(392)
°C
(°F)
A
16
15
R/W
C6
MOP protection: integral time
20
0
800
s
A
17
16
R/W
C7
MOP protection: disabling threshold
30
(86)
-85
(-121)
200
(392)
°C
(°F)
A
19
18
R/W
C8
Low suction temperature alarm threshold
-50
(-58)
-85
(-121)
200
(392)
°C
(°F)
A
18
17
R/W
S1
Type of probe S1
Ratiometric (OUT=0…5V)
1 = -1…4.2 barg
8 = -1…12.8 barg
2 = 0.4…9.3 barg
9 = 0…20.7 barg
3 = -1…9.3 barg
10 = 1.86…43.0 barg
4 = 0…17.3 barg
11 = NTC (-50…105°C)
5 = 0.85…34.2 barg
12 = Ratiometric (OUT=0-5V) 0-60 barg
6 = 0…34.5 barg
13 = Ratiometric (OUT=0-5V) 0-90 barg
7 = 0…45 barg
14 = Remote pressure probe from RS485
3
1
11
-
I
14
141
R/W
n1
Network address
99
1
99
-
I
10
137
R/W