“EVD mini” +0300036EN - rel. 1.2 - 23.04.2018
9.5 Network
alarm
The digital input configuration parameter can only be set to control
backup from the supervisor. If there is a communication error between
the pCO controller and driver, the digital input status determines whether
to continue control (input closed = the valve remains in the current
position) or stop (input open).
9.6 Alarm
table
Alarm code on
the display
Red LED
Cause of the alarm
Reset
Effects on control
Checks / Solutions
A1
flashes
Probe S1 faulty or set alarm range
exceeded
automatic
Valve closed
Check the probe connections.
A2
flashes
Probe S2 faulty or set alarm range
exceeded
automatic
Valve closed
Check the probe connections.
E1
flashes
MOP protection activated
automatic
Protection action already
in progress
Check parameter “MOP protection:
threshold”
E2
flashes
LOP protection activated
automatic
Protection action already
in progress
Check parameter “LOP protection:
threshold”
E3
flashes
LowSH protection activated
automatic
Protection action already
in progress
Check parameter “LowSH protection:
threshold”
E4
flashes
Low suction temperature
automatic
No effect
Check the threshold parameter.
E5
flashes
Chiusura di emergenza: LowSH,
LOP, MOP, bassa T/P di aspirazione,
mancanza di alimentazione
automatic
Valve closed
Reset power supply
E6
flashes
Network error
automatic
Control based on DI
Check the wiring and that the pCO is
on and operating
E7
flashes
Ultracap module powered at low volta-
ge or low charge
automatic
No effect
Check the wiring, the power supply
and that the minimum recharge time
has elapsed
E8
flashes
Emergency closing not completed
Manual
Valve closed
Press PRG/Set or set the corresponding
supervisor variable to 0
EE
on steady
EEPROM operating and/or unit parame-
ters damaged
Replace the
driver/ Contact
service
Total shutdown
Replace the driver/Contact service
Tab. 9.d