2.  ASSEMBLY AND INSTALLATION

2.1  Assembly

Warnings:

Avoid installing the boards in environments with the following 
characteristics:

relative humidity greater than 90% or where there is condensation;
strong vibrations or knocks;
exposure to continuous water sprays;
exposure to aggressive and polluting atmospheres(e.g.: sulphur and 
ammonia fumes, saline mist, smoke) so as to avoid corrosion and/or 
oxidation;
strong magnetic and/or radio frequency interference (there avoid 
installing the units near transmitting antennae);
near transmitting antennae and to the elements in general;
large and rapid fl uctuations in the ambient temperature;
environments where explosives or mixes of fl ammable gases are 
present;
exposure to dust (formation of corrosive patina with possible oxidation 
and reduction of insulation.

To install easy and easy compact: make an opening in the panel based on 
the drilling template, 71x29 mm.

Panel installation using 2 rear brackets (Figs. 2.a and 
2.b)

insert the instrument in the opening (phase 1);
secure the instrument by sliding the brackets in the guides on the 
instrument until compressing them against the panel (phase 2);

easy

1

2

PUSH

Fig. 2.a

easy compact

1

2

PUSH

Fig. 2.b

Removing from the panel with brackets

release the instrument by pressing both brackets where marked “push” 
and sliding it back on the guides.

Panel installation from the front using screws (Fig. 2.c)

the thickness of the fastening panel must not exceed 3 mm;
remove the front frame and make sure that the two catches are in place 
(these must not protrude from the outline of the drilling template). If 
necessary, unscrew the two screws. Do not unscrew excessively, the 
screws must not be detached from the front panel (phase 1);
insert the instrument in the opening in the panel and hold it in position 
by the centre of the front panel (phase 1);
using the screwdriver, tighten the bottom screw 90°, the catch must 
come out of its slot and click onto the panel, then tighten until the front 
panel is secure; Do not over-tighten, when the front panel is secured 
blocks simply make another ½ turn to compress the gasket; If the catch 
does not click onto the panel, unscrew the screw, applying pressure at 








the same time with the screwdriver so that the catch moves back. Do 
not unscrew too much, the head of the screw must not be raised from 
the surface of the front panel (phase 2);
repeat the same operation for the top screw (phase 2);
apply the front frame (phase 3).

max 2,5

1

(

*

)

2

3

Fig. 2.c

(*) do not over-tighten the screws.

Dismantling using the screws from the front

unclip the front frame;
unscrew the bottom screw, at the moment the front panel detaches 
from the panel keep pressure on the screw and unscrew a further 90° 
to make the catch go back into its slot;
repeat for the top screw;
remove the instrument from panel, keeping it horizontal

 2.2  Electrical  connections

Warnings:

the electrical connections must only be completed by a qualifi ed 
electrician;
a power supply other than the type specifi ed may seriously damage 
the system;
separate as much as possible the probes and digital input signal 
cables from the cables carrying inductive loads and power cables to 
avoid possible electromagnetic disturbance. Never lay power cables 
(including the electrical cables) and probe signal cables in the same 
conduits. Do not install the probe cables in the immediate vicinity of 
power devices (contactors, circuit breakers or similar);
reduce the path of the probe and sensor cables as much as possible, 
and avoid spiral paths that enclose power devices. The probes must 
be connected using shielded cables (minimum cross-section of each 
wire: 0.5 mm

2

);

avoid direct contact with internal electronic components;
connection errors (and connections other than those indicated in this 
manual) may involve danger to the safety of the users and cause faults 
on the instruments and the components connected; 
fi t the unit with all the electromechanical safety devices required to 
guarantee correct operation and the complete safety of the user.

Information:

the probes can be installed up to a maximum distance of 30 m from 
the controller. To extend the distance of the probes, use cables with a 
minimum cross-section of 1 mm2, shielded where possible. In this case, 
the shield must be connected to the common of the probe. Do not 
earth the other end of the shield (the sensor end);
only use IP67 probes as end defrost probes; place the probes with the 
vertical bulb upwards, so as to assist the drainage of any condensate. 
The thermistor temperature probes (NTC or PTC) have no polarity, so 
the order of connection of the ends is not important;
use cable ends suitable for the corresponding terminals. Loosen each 
screw and insert the cable ends, then tighten the screws. When the 
operation is completed, slightly tug the cables to check they are 





Содержание easy

Страница 1: ...easy easy compact digital electronic thermostats with defrost control User manual...

Страница 2: ......

Страница 3: ...oduct should be used or stored in environments that comply with the temperature and humidity limits specified in the manual do not attempt to open the device in any way other than described in the man...

Страница 4: ......

Страница 5: ...erature control 13 4 4 Duty Setting 14 4 5 Continuous cycle 14 4 6 Compressor protection 15 4 7 Defrost 15 4 8 Alarm parameters 17 4 9 Evaporator fan management parameters 20 4 10 Clock and time band...

Страница 6: ......

Страница 7: ...es Models easy easy compact Ergonomic polycarbonate keypad with three buttons P P Keypad protection to prevent tampering P P Access to the configuration parameters by password P P Digit display 199 to...

Страница 8: ...d 4 12 P P P P P P P P P enable disable buzzer 4 12 P P P P P P modified parameter detection 4 12 P P P P P P P P P rapid parameter set selection 4 11 P P P P P P P clock and time band management 4 10...

Страница 9: ...the head of the screw must not be raised from the surface of the front panel phase 2 repeat the same operation for the top screw phase 2 apply the front frame phase 3 max 2 5 1 2 3 Fig 2 c do not over...

Страница 10: ...TC PTC PROBES or or SERIAL CONV PROG KEY 10T50 AUX or AUX PJEZ M 1 2 3 4 5 6 7 9 10 11 8 L N L N 230Vac or 115 Vac or 12 Vac Vdc DEF T DI PROBE AMB T NTC PTC PROBES or SERIAL CONV PROG KEY 10T50 AUX F...

Страница 11: ...digit values can be set from the supervisor In this case the display will show 3 2 Keypads Keypad functions for easy and easy compact models C S X Y 2 1 3 Fig 3 c but no normal operation start up pres...

Страница 12: ...or fan alarm hysteresis and management A0 temperature control hysteresis rd cht pre alarm hysteresis AE In addition the delays are set to zero for the display of the temperature alarms Ad d8 c6 drippi...

Страница 13: ...ultifunction input analogue or digital Parameter 4 selects the probe shown on the display all the other display and control modes remain unchanged Important the easy compact models can display up to 2...

Страница 14: ...emain always on and the 15 minute off time is not considered 0 c4 100 0 c4 99 for easy compact at the moment a probe error E0 is detected the duty setting cycle starts from the current status of the c...

Страница 15: ...ater or hot gas In addition it can be managed by temperature using the defrost probe located on the evaporator In any case the defrost will end after a maximum settable safety duration The end defrost...

Страница 16: ...t performed In the event of defrost probe failure the controller performs a timed defrost with a duration equal to the value set for dP The same is true if the end defrost set point can not be reached...

Страница 17: ...compressor has just stopped and there is a minimum time between two starts Remember however that in this case the maximum number of activations per hour of the compressor may not be respected d defros...

Страница 18: ...door closed 9 Direct reverse operating mode SE r3 0 input open direct defrost input closed reverse SE r3 1 2 input open direct input closed reverse 10 Probe for dirty condenser alarm 11 Product probe...

Страница 19: ...r will start counting the pre alarm time and subsequently the dor alarm time After the pre alarm the controller will continuously signal the door open alarm the display will show the message dor alter...

Страница 20: ...UX FAN COMP A4 1 IA A4 6 P A4 7 dor P P A4 8 dor P P P Table 4 k 1 2 3 4 5 A7 digital input alarm delay Sets the delay in minutes for detecting the external alarm when A4 1 7 or 8 A8 enable alarm Ed e...

Страница 21: ...day of the week hr hours Min minutes at the end of the operations press the SET button for more than 3 seconds to permanently save the selected values and exit 1 2 3 4 5 6 7 8 9 Setting the time bands...

Страница 22: ...er models PJEZM the EZY parameter EY for the easy compact models is not featured 4 12 Other settings The operation of the device is completed by a series of additional functions such as the assignment...

Страница 23: ...n reset ENABLE ALARM parameters involved easy easy compact E0 active ON probe 1 error control automatic E1 not active ON probe 2 error defrost automatic d0 0 1 4 F0 1 E2 not active ON probe 3 error co...

Страница 24: ...SET button for more than 3 s if there are active alarms mute the buzzer the display shows the parameter code PS password press the SET button to access the password setting use the UP and DOWN buttons...

Страница 25: ...defrost priority over compressor protectors C 0 1 0 S with 1 2 probes X Y C d defrost probe reading 2 F C F S with 2 probes X Y C dC time base C 0 1 0 S with 1 2 probes X Y C A0 alarm and fan temperat...

Страница 26: ...2 probes c4 compressor on time with duty setting C 0 100 min 0 S with 1 2 probes cc continuous cycle duration C 0 15 h 4 S with 1 2 probes c6 temperature alarm bypass after continuous cycle C 0 15 h...

Страница 27: ...ndenser alarm differential temperature 10 0 8 0 10 0 10 0 10 0 10 0 10 0 10 0 Acd dirty condenser alarm delay 60 40 200 60 60 60 60 60 F0 enable evaporator fan control 1 0 1 0 F1 evaporator fan contro...

Страница 28: ...o low or the evaporator temperature is too high parameters dt and d defrost probe the manual defrost is not activated and the defrost LED flashes compressor protection times set parameter d9 select d9...

Страница 29: ...the power cable less than 3 cm from the bottom of the device or the probes for the connections only use copper wires 71x29 10 3 33 74 81 36 58 65 29 28 5 6 2 easy compact technical specifications pow...

Страница 30: ...Note...

Страница 31: ......

Страница 32: ...rugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency easy easy compact 030220791 rel 2 0 30 05 2007 CAREL reserves the right to modify the feat...

Отзывы: