easy/easy compact  +030220791 - rel. 2.0 - 30.05.2007

Parameters for setting the AUX output activation time band

AOd 

AUX output activation time band day setting

 

AOd= 0 no event set 

 

AOd= 1…7 Monday to Sunday 

 

AOd= 8 from Monday to Friday 

 

AOd= 9 from Monday to Saturday 

 

AOd= 10 Saturday & Sunday 

 

AOd= 11 every day

 

AOh 

AUX output activation time band start hours

 

AOm 

AUX output activation time band start minutes

 

AFh 

AUX output activation time band end hours

 

AFm 

AUX output activation time band end minutes

Example:

 To program the activation of the AUX output every day from 

12.31 at 13.29, set: AOd=11 (days), AOh=12 (start hours), AOm=31 (start 
minutes), AFh=13 (end hours) and AFm=29 (end minutes).

Important

Important

: the activation the AUX output activation time band is 

linked to parameters H1=3 and A4≠6/7/8.

4.11 Rapid parameter set selection (EZY)

The easy and easy compact controllers feature the EZY parameter (on 
the compact models, this is called EY), which is used to quickly choose 
a list of parameters, with corresponding values, for the control of the 
refrigeration system. 
By setting parameter EZY=1, 2, 3, 4, one of the 4 lists made up of a 
maximum of 25 parameters (for the lists see par. “5.8 Table of EZY 
parameter sets” page 27). The values in the chosen list overwrite the 
corresponding operating parameters.

Note

to restore the selected rapid parameter set at any time, turn the 
controller off  and on again, while holding SET. The display shows 
“CE” to indicate that the selected rapid set (EZY= 1, 2, 3, 4) has again 
overwritten the operating parameters, thus restoring the original set 
of parameters;
to restore all the parameters and return to the original default values 
(factory settings), turn the controller off  and on again while holding 
DOWN and SET, until the display shows “CF”. Use this procedure with 
extreme care, as it may compromise the fundamental control settings;
EZY=0 brings no change;
on the thermometer models (PJEZM*), the EZY parameter (EY for the 
easy compact models) is not featured. 

4.12  Other settings   

The operation of the device is completed by a series of additional 
functions, such as the assignment of a supervisor serial network address, 
the confi guration of the AUX relay, the enabling of the keypad and the 
buzzer.

H0: serial address

Assigns the instrument an identifi cation address for connecting to a 
supervisory or telemaintenance system (def. H0=1). 

H1: AUX output confi guration

Establishes the operating logic of the auxiliary relay; in particular defi nes 
whether it is used as an alarm output or as an auxiliary output linked to 
the digital input.
H1= 0 

no function associated with the output

H1=1 

alarm output: norm. energised (relay de-energised with  

 alarm)
H1=2 

alarm output: norm. de-energised (relay energised with  

 alarm)
H1=3 

AUX output linked to Dig. in [A4=6/7/8]

 

Dig. in OPEN = AUX de-energised

 

Dig in CLOSED = AUX ene “AUX” LED on display


Note

in mode H1= 1/2, the alarms that act on the AUX output are: “LO”,  “HI”, 
“E0”, “IA”, “CHT”;
mode H1= 1 is useful for signalling an alarm when a power failure 
occurs

H2: enable keypad

Used to prevent the set point and the other operating parameters 
from being changed when the instrument is located in a place that is 
accessible to the public.

H2= 0 

keypad disabled:

 

- F parameters read-only

 

- C parameters modifi able (with password)

 

- no set point modifi cation

 

- no manual defrost

 

- no continuous cycle

 

- no ON/OFF

H2=1 keypad 

enabled

H2=2 

keypad enabled except for ON/OFF

H4: disable buzzer

Setting H4= 1 disables the operation of the audible buzzer.

H5: ID code

Display-only value: this can only be modifi ed via serial connection (key 
or supervisor). When set to a positive value (values from 0 to 31 are used 
by CAREL for the basic models), if a parameter, including the set point, is 
modifi ed from the keypad, the value becomes negative. This allows any 
modifi cations made the parameters compared to the initial settings to 
be monitored.

PS: password

Protection code for modifying the confi guration parameters (default= 
22). The value of the password can be customised from the supervisor.

Содержание easy

Страница 1: ...easy easy compact digital electronic thermostats with defrost control User manual...

Страница 2: ......

Страница 3: ...oduct should be used or stored in environments that comply with the temperature and humidity limits specified in the manual do not attempt to open the device in any way other than described in the man...

Страница 4: ......

Страница 5: ...erature control 13 4 4 Duty Setting 14 4 5 Continuous cycle 14 4 6 Compressor protection 15 4 7 Defrost 15 4 8 Alarm parameters 17 4 9 Evaporator fan management parameters 20 4 10 Clock and time band...

Страница 6: ......

Страница 7: ...es Models easy easy compact Ergonomic polycarbonate keypad with three buttons P P Keypad protection to prevent tampering P P Access to the configuration parameters by password P P Digit display 199 to...

Страница 8: ...d 4 12 P P P P P P P P P enable disable buzzer 4 12 P P P P P P modified parameter detection 4 12 P P P P P P P P P rapid parameter set selection 4 11 P P P P P P P clock and time band management 4 10...

Страница 9: ...the head of the screw must not be raised from the surface of the front panel phase 2 repeat the same operation for the top screw phase 2 apply the front frame phase 3 max 2 5 1 2 3 Fig 2 c do not over...

Страница 10: ...TC PTC PROBES or or SERIAL CONV PROG KEY 10T50 AUX or AUX PJEZ M 1 2 3 4 5 6 7 9 10 11 8 L N L N 230Vac or 115 Vac or 12 Vac Vdc DEF T DI PROBE AMB T NTC PTC PROBES or SERIAL CONV PROG KEY 10T50 AUX F...

Страница 11: ...digit values can be set from the supervisor In this case the display will show 3 2 Keypads Keypad functions for easy and easy compact models C S X Y 2 1 3 Fig 3 c but no normal operation start up pres...

Страница 12: ...or fan alarm hysteresis and management A0 temperature control hysteresis rd cht pre alarm hysteresis AE In addition the delays are set to zero for the display of the temperature alarms Ad d8 c6 drippi...

Страница 13: ...ultifunction input analogue or digital Parameter 4 selects the probe shown on the display all the other display and control modes remain unchanged Important the easy compact models can display up to 2...

Страница 14: ...emain always on and the 15 minute off time is not considered 0 c4 100 0 c4 99 for easy compact at the moment a probe error E0 is detected the duty setting cycle starts from the current status of the c...

Страница 15: ...ater or hot gas In addition it can be managed by temperature using the defrost probe located on the evaporator In any case the defrost will end after a maximum settable safety duration The end defrost...

Страница 16: ...t performed In the event of defrost probe failure the controller performs a timed defrost with a duration equal to the value set for dP The same is true if the end defrost set point can not be reached...

Страница 17: ...compressor has just stopped and there is a minimum time between two starts Remember however that in this case the maximum number of activations per hour of the compressor may not be respected d defros...

Страница 18: ...door closed 9 Direct reverse operating mode SE r3 0 input open direct defrost input closed reverse SE r3 1 2 input open direct input closed reverse 10 Probe for dirty condenser alarm 11 Product probe...

Страница 19: ...r will start counting the pre alarm time and subsequently the dor alarm time After the pre alarm the controller will continuously signal the door open alarm the display will show the message dor alter...

Страница 20: ...UX FAN COMP A4 1 IA A4 6 P A4 7 dor P P A4 8 dor P P P Table 4 k 1 2 3 4 5 A7 digital input alarm delay Sets the delay in minutes for detecting the external alarm when A4 1 7 or 8 A8 enable alarm Ed e...

Страница 21: ...day of the week hr hours Min minutes at the end of the operations press the SET button for more than 3 seconds to permanently save the selected values and exit 1 2 3 4 5 6 7 8 9 Setting the time bands...

Страница 22: ...er models PJEZM the EZY parameter EY for the easy compact models is not featured 4 12 Other settings The operation of the device is completed by a series of additional functions such as the assignment...

Страница 23: ...n reset ENABLE ALARM parameters involved easy easy compact E0 active ON probe 1 error control automatic E1 not active ON probe 2 error defrost automatic d0 0 1 4 F0 1 E2 not active ON probe 3 error co...

Страница 24: ...SET button for more than 3 s if there are active alarms mute the buzzer the display shows the parameter code PS password press the SET button to access the password setting use the UP and DOWN buttons...

Страница 25: ...defrost priority over compressor protectors C 0 1 0 S with 1 2 probes X Y C d defrost probe reading 2 F C F S with 2 probes X Y C dC time base C 0 1 0 S with 1 2 probes X Y C A0 alarm and fan temperat...

Страница 26: ...2 probes c4 compressor on time with duty setting C 0 100 min 0 S with 1 2 probes cc continuous cycle duration C 0 15 h 4 S with 1 2 probes c6 temperature alarm bypass after continuous cycle C 0 15 h...

Страница 27: ...ndenser alarm differential temperature 10 0 8 0 10 0 10 0 10 0 10 0 10 0 10 0 Acd dirty condenser alarm delay 60 40 200 60 60 60 60 60 F0 enable evaporator fan control 1 0 1 0 F1 evaporator fan contro...

Страница 28: ...o low or the evaporator temperature is too high parameters dt and d defrost probe the manual defrost is not activated and the defrost LED flashes compressor protection times set parameter d9 select d9...

Страница 29: ...the power cable less than 3 cm from the bottom of the device or the probes for the connections only use copper wires 71x29 10 3 33 74 81 36 58 65 29 28 5 6 2 easy compact technical specifications pow...

Страница 30: ...Note...

Страница 31: ......

Страница 32: ...rugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency easy easy compact 030220791 rel 2 0 30 05 2007 CAREL reserves the right to modify the feat...

Отзывы: