The defrost may be called, but not activated, in the following 
cases:

continuous cycle;
dripping (dd>0);
post-dripping ( Fd>0);
compressor protectors;
off  status;
disabling from digital input(A4=2);
setting the time delay (d5>0) for the defrost function when the 
instrument is switched on (d4=1);
direct control mode only without defrost (r3=1) or reverse (r3=2)  (in 
this case the defrost is not called);
defrost by temperature (d0=0, 1, 4) and temperature measured by the 
defrost probe above the end defrost set point (dt).

The defrost ends correctly:

at the end of the pre-set time (see parameter “dP”);
when reaching the set temperature (dt).

When the defrost ends correctly, the dripping (equal to the time set for 
parameter dd) and post-dripping (parameter Fd) phases start.

The defrost ends early:

from the keypad, pressing the DOWN button for 3 s (manual end 
defrost); 
due to an immediate external alarm “IA” ;
due to a dirty condenser alarm “CHt”;
by setting direct mode only without defrost (r3=1) or reverse (r3=2);
switching off ;
when requested from the supervisor;
from digital input (see parameter A4=2) (the defrost call remains 
pending).

In these cases, the early end of the defrost is not followed by dripping 
and post-dripping.

Important:

the defrost is only available in direct mode, that is, when parameters 
r3=0 or A4=9 (the latter has priority over r3);
using parameter d0, and according to the model available, type of 
defrost to be activated can be selected;
the defrost has priority over normal temperature control; it may also 
have priority over the compressor protectors (see parameter d9);
during the defrost, the temperature display can be frozen (see 
parameter d6);
the continuous cycle has priority over the defrost  

Parameters for confi guring the defrost

dI: interval between defrosts

The defrost is performed periodically at a frequency of every “dI” (in hours 
or minutes, see parameter dC). 
The interval starts counting from the previous end defrost. If the time is 
equal to 0 (dI=0), the defrost is not performed, except when activated 
from the keypad, by digital input, from the supervisor or by time band.
During defrosts the temperature alarms are inhibited.

dt: end defrost temperature set point/defrost temperature threshold 
with temp. control

For the models fi tted with end defrost probe, this parameter allows an 
evaporator temperature to be set at which the defrost is stopped (the 
evaporator temperature is measured by the defrost probe). The end 
defrost temperature diff erential is fi xed at 1° C (defrost thermostat, d0= 
4).
If, at the start of a defrost cycle, the temperature measured by the defrost 
probe is greater than “dt”, the cycle is not performed.













In the event of defrost probe failure, the controller performs a timed 
defrost with a duration equal to the value set for “dP”. The same is true if 
the end defrost set point can not be reached, the defrost is stopped after 
a maximum time equal to the value of dP, and the error Ed is displayed (if 
enabled by A8) and stays on until a correct defrost cycle is performed.

dP: maximum defrost duration

Determines the maximum duration of the defrost (in minutes or seconds, 
see parameter dC). When defrost by time is set (d0= 2/3/4) dP represents 
the eff ective duration of the defrost.

d4: defrost when switching the instrument on

Starts a defrost when switching the instrument on (d4= 1). This has 
priority over the activation of the compressor and the continuous cycle.

Running a defrost when switching the instrument on may be useful in 
special situations (e.g. frequent power failures).

Case 1: the system is subject to frequent power failures

In the event of power failures the instrument’s internal clock, which 
calculates the interval between two defrosts, starting from zero, is reset. 
If the frequency of the power failure were, in an extreme case, greater 
than the defrost frequency (e.g. a power failure every 8 hours against a 
defrost every 10 hours), the controller would never perform a defrost. In 
this type of situation it is better to activate the defrost when the unit is 
turned on, above all if the defrost is controlled by temperature (probe on 
the evaporator), so unnecessary defrosts are avoided or at least reduced 
in duration.

Case 2: Systems with many refrigeration units

In this situation, if the defrost on power-up is activated (d4= 1) after a 
power failure all the units will start a defrost. This may cause overloads. 
To avoid this, parameter “d5” can be exploited, which allows a delay to be 
set before the defrost starts, a delay which obviously must be diff erent 
for each unit.

2

d5 (3)

dP (3)

d5 (2)

dP (2)

dP (1)

unit 1
[d4(1)= 1]

ON

OFF

ON

OFF

ON

OFF

ON

OFF

unit 2
[d4(2)= 1]

unit 3
[d4(3)= 1]

1

Fig. 4.h

Key:

1  

power-up;

2  

voltage.

d5: defrost delay on power-up or when enabled by digital input

Represents the time which must elapse between when the controller is 
turned on and the start of the defrost.

The digital input can be used to start a defrost from external contact (see 
parameter A4=3); d5 represents the delay between when the defrost is 
enabled, or called, and when it eff ectively starts. 
The defrost from digital input can be exploited to perform defrosts in real 
time when is the RTC option is not fi tted. Simply connect a timer to the 
multifunction digital input. The defrost will be activated when the timer 
contact is closed. In the case where more than unit is connected to the 
same timer, it is recommended to set parameter d5 to delay the defrosts 
to a diff erent time for each unit.
Furthermore, to avoid unnecessary defrosts controlled by the instrument’s 

Содержание easy

Страница 1: ...easy easy compact digital electronic thermostats with defrost control User manual...

Страница 2: ......

Страница 3: ...oduct should be used or stored in environments that comply with the temperature and humidity limits specified in the manual do not attempt to open the device in any way other than described in the man...

Страница 4: ......

Страница 5: ...erature control 13 4 4 Duty Setting 14 4 5 Continuous cycle 14 4 6 Compressor protection 15 4 7 Defrost 15 4 8 Alarm parameters 17 4 9 Evaporator fan management parameters 20 4 10 Clock and time band...

Страница 6: ......

Страница 7: ...es Models easy easy compact Ergonomic polycarbonate keypad with three buttons P P Keypad protection to prevent tampering P P Access to the configuration parameters by password P P Digit display 199 to...

Страница 8: ...d 4 12 P P P P P P P P P enable disable buzzer 4 12 P P P P P P modified parameter detection 4 12 P P P P P P P P P rapid parameter set selection 4 11 P P P P P P P clock and time band management 4 10...

Страница 9: ...the head of the screw must not be raised from the surface of the front panel phase 2 repeat the same operation for the top screw phase 2 apply the front frame phase 3 max 2 5 1 2 3 Fig 2 c do not over...

Страница 10: ...TC PTC PROBES or or SERIAL CONV PROG KEY 10T50 AUX or AUX PJEZ M 1 2 3 4 5 6 7 9 10 11 8 L N L N 230Vac or 115 Vac or 12 Vac Vdc DEF T DI PROBE AMB T NTC PTC PROBES or SERIAL CONV PROG KEY 10T50 AUX F...

Страница 11: ...digit values can be set from the supervisor In this case the display will show 3 2 Keypads Keypad functions for easy and easy compact models C S X Y 2 1 3 Fig 3 c but no normal operation start up pres...

Страница 12: ...or fan alarm hysteresis and management A0 temperature control hysteresis rd cht pre alarm hysteresis AE In addition the delays are set to zero for the display of the temperature alarms Ad d8 c6 drippi...

Страница 13: ...ultifunction input analogue or digital Parameter 4 selects the probe shown on the display all the other display and control modes remain unchanged Important the easy compact models can display up to 2...

Страница 14: ...emain always on and the 15 minute off time is not considered 0 c4 100 0 c4 99 for easy compact at the moment a probe error E0 is detected the duty setting cycle starts from the current status of the c...

Страница 15: ...ater or hot gas In addition it can be managed by temperature using the defrost probe located on the evaporator In any case the defrost will end after a maximum settable safety duration The end defrost...

Страница 16: ...t performed In the event of defrost probe failure the controller performs a timed defrost with a duration equal to the value set for dP The same is true if the end defrost set point can not be reached...

Страница 17: ...compressor has just stopped and there is a minimum time between two starts Remember however that in this case the maximum number of activations per hour of the compressor may not be respected d defros...

Страница 18: ...door closed 9 Direct reverse operating mode SE r3 0 input open direct defrost input closed reverse SE r3 1 2 input open direct input closed reverse 10 Probe for dirty condenser alarm 11 Product probe...

Страница 19: ...r will start counting the pre alarm time and subsequently the dor alarm time After the pre alarm the controller will continuously signal the door open alarm the display will show the message dor alter...

Страница 20: ...UX FAN COMP A4 1 IA A4 6 P A4 7 dor P P A4 8 dor P P P Table 4 k 1 2 3 4 5 A7 digital input alarm delay Sets the delay in minutes for detecting the external alarm when A4 1 7 or 8 A8 enable alarm Ed e...

Страница 21: ...day of the week hr hours Min minutes at the end of the operations press the SET button for more than 3 seconds to permanently save the selected values and exit 1 2 3 4 5 6 7 8 9 Setting the time bands...

Страница 22: ...er models PJEZM the EZY parameter EY for the easy compact models is not featured 4 12 Other settings The operation of the device is completed by a series of additional functions such as the assignment...

Страница 23: ...n reset ENABLE ALARM parameters involved easy easy compact E0 active ON probe 1 error control automatic E1 not active ON probe 2 error defrost automatic d0 0 1 4 F0 1 E2 not active ON probe 3 error co...

Страница 24: ...SET button for more than 3 s if there are active alarms mute the buzzer the display shows the parameter code PS password press the SET button to access the password setting use the UP and DOWN buttons...

Страница 25: ...defrost priority over compressor protectors C 0 1 0 S with 1 2 probes X Y C d defrost probe reading 2 F C F S with 2 probes X Y C dC time base C 0 1 0 S with 1 2 probes X Y C A0 alarm and fan temperat...

Страница 26: ...2 probes c4 compressor on time with duty setting C 0 100 min 0 S with 1 2 probes cc continuous cycle duration C 0 15 h 4 S with 1 2 probes c6 temperature alarm bypass after continuous cycle C 0 15 h...

Страница 27: ...ndenser alarm differential temperature 10 0 8 0 10 0 10 0 10 0 10 0 10 0 10 0 Acd dirty condenser alarm delay 60 40 200 60 60 60 60 60 F0 enable evaporator fan control 1 0 1 0 F1 evaporator fan contro...

Страница 28: ...o low or the evaporator temperature is too high parameters dt and d defrost probe the manual defrost is not activated and the defrost LED flashes compressor protection times set parameter d9 select d9...

Страница 29: ...the power cable less than 3 cm from the bottom of the device or the probes for the connections only use copper wires 71x29 10 3 33 74 81 36 58 65 29 28 5 6 2 easy compact technical specifications pow...

Страница 30: ...Note...

Страница 31: ......

Страница 32: ...rugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency easy easy compact 030220791 rel 2 0 30 05 2007 CAREL reserves the right to modify the feat...

Отзывы: