10

GB

easy/easy compact  +030220791 - rel. 2.0 - 30.05.2007

suffi

  ciently tight.

The connections of the inputs and outputs, depending on the models, 
may be made: 

using traditional screw terminals;
using plug-in terminals with screw cable connection blocks;
using plug-in terminals with crimped cable connection blocks.
using plug-in terminals, which signifi cantly simplify the connection 
of the instrument both during installation and maintenance. This also 
avoids connection errors, as there are three connection blocks with a 
diff erent number of pins.

Connect the inputs and the outputs following the diagram shown on the 
instrument label.

For the 12 Vac versions:

if the power supply available is mains, a safety transformer is required 
to ensure double insulation between the power supply and the very 
low voltage electronics. If required, a fuse must be installed in series 
with the primary (32 mAT for code TRA12VDE00). The transformer-
instrument connection must be as short as possible;
if the power supply available is already low voltage, but not 12 Vac, 
a suitable adapting transformer must be used: double insulation 
between the primary and secondary and defi nition for surge on the 
primary to the appropriate level (2000 V for applications in industrial 
environments.

The voltage supplied to these terminals (see the wiring diagrams)  must 
correspond, within the specifi ed tolerances, to the value shown on 
the instrument connection label. The insulation of the instrument, for 
versions with mains power supply (230 Vac and 115 Vac), is reinforced. 
The versions with 12 Vac/Vdc power supply, on the other hand, do not 
feature such insulation.

easy wiring diagrams

PJEZ(S, X)*

PJEZ(C, Y)*

1   2   3   4   5

6   7

9 10 11

8

L
N

L

N

DEF

. T

.

DI / PR

OBE

AMB.

 T

.

NTC/PTC
PROBES

or

SERIAL

CONV

PROG.

KEY

-10T50

1   2   3   4   5

6   7

9 10 11

8

L
N

L

N

230Vac or

115 Vac or

12 Vac/Vdc

230Vac or

115 Vac or

12 Vac/Vdc

DEF

. T

.

DI / PR

OBE

AMB.

 T

.

NTC/PTC
PROBES

or

or

SERIAL

CONV

PROG.

KEY

-10T50

AUX

or

AUX

PJEZ(M)*

1   2   3   4   5

6   7

9 10 11

8

L
N

L

N

230Vac or

115 Vac or

12 Vac/Vdc

DEF

. T

.

DI / PR

OBE

AMB.

 T

.

NTC/PTC
PROBES

or

SERIAL

CONV

PROG.

KEY

-10T50

AUX

Fig. 2.d




easy compact wiring diagrams

1

2

3

4

5

6

L

N

NTC PROBES

SERIAL

CONV

PROG.

KEY

PJEZS***0**
PJEZS***1**

1

2

3

4

5

NTC PROBES

PJEZS***E**

1

2

3

4

5

L

N

12V~

NTC PROBES

SERIAL

CONV

PROG.

KEY

PJEZM*N*0**
PJEZM*N*1**

1

2

3

4

L

N

12V~

NTC PROBES

PJEZM*N*E**

1

2

3

4

5

6

NTC PROBES

SERIAL

CONV

PROG.

KEY

PJEZM*P*0**
PJEZM*P*1**

3

4

NTC PROBES

AUX

1

2

3

PJEZM*P*E**

L

N

L

N

AUX

L

N

Fig. 2.e

2.3  Wiring diagram for multiple units 

Warnings:

the RS485 converter (IROPZ485S0)  is sensitive to electrostatic 
discharges, and therefore must be handled with extreme care;
check the technical documents on the CAREL IROPZ485S0 option for 
the description of the connection methods so as to avoid damaging 
the instrument;
suitably fasten the converter so as to avoid disconnections;
perform the wiring with the power supply disconnected;
keep the IROPZ485S0 serial option cables separate from the original 
wires (relay outputs and power supply).

The RS485 converter (IROPZ485S0) is used to connect the easy and easy 
compact instruments to the supervisor network, allowing complete 
control and monitoring of the easy units connected.
The system allows up to 207 units to be connected together, with a 
maximum length of 1000 m. For the connection, the standard accessories 
are required (RS485-USB converter CAREL code CVSTDUMOR0) and two 
120 Ω, terminal resistors, to be fi tted on the terminal block on the fi rst and 
last instrument connected.
Connect the RS485 converter to the easy or easy compact unit using 
a 4-wire cable and make the connections as shown in the fi gure. The 
line should be started and ended with a 120 Ω 1/4 W resistor. For the 
allocation of the serial address see parameter H0. The recommended 
connection cable is a twisted pair with shield and cross-section from 0.5 
to 1.5 mm

2

 (AW6 22-24).

easy

easy

max. 207

units

easy

. . .

RS485

RS485

+

+

GND

GND

USB

-

-

+

GND

-

+

GND

120 ohm

-

120 ohm

IROPZ485S0

IROPZ485S0

CVSTDUMOR0

IROPZ485S0

Fig. 2.f



Содержание easy

Страница 1: ...easy easy compact digital electronic thermostats with defrost control User manual...

Страница 2: ......

Страница 3: ...oduct should be used or stored in environments that comply with the temperature and humidity limits specified in the manual do not attempt to open the device in any way other than described in the man...

Страница 4: ......

Страница 5: ...erature control 13 4 4 Duty Setting 14 4 5 Continuous cycle 14 4 6 Compressor protection 15 4 7 Defrost 15 4 8 Alarm parameters 17 4 9 Evaporator fan management parameters 20 4 10 Clock and time band...

Страница 6: ......

Страница 7: ...es Models easy easy compact Ergonomic polycarbonate keypad with three buttons P P Keypad protection to prevent tampering P P Access to the configuration parameters by password P P Digit display 199 to...

Страница 8: ...d 4 12 P P P P P P P P P enable disable buzzer 4 12 P P P P P P modified parameter detection 4 12 P P P P P P P P P rapid parameter set selection 4 11 P P P P P P P clock and time band management 4 10...

Страница 9: ...the head of the screw must not be raised from the surface of the front panel phase 2 repeat the same operation for the top screw phase 2 apply the front frame phase 3 max 2 5 1 2 3 Fig 2 c do not over...

Страница 10: ...TC PTC PROBES or or SERIAL CONV PROG KEY 10T50 AUX or AUX PJEZ M 1 2 3 4 5 6 7 9 10 11 8 L N L N 230Vac or 115 Vac or 12 Vac Vdc DEF T DI PROBE AMB T NTC PTC PROBES or SERIAL CONV PROG KEY 10T50 AUX F...

Страница 11: ...digit values can be set from the supervisor In this case the display will show 3 2 Keypads Keypad functions for easy and easy compact models C S X Y 2 1 3 Fig 3 c but no normal operation start up pres...

Страница 12: ...or fan alarm hysteresis and management A0 temperature control hysteresis rd cht pre alarm hysteresis AE In addition the delays are set to zero for the display of the temperature alarms Ad d8 c6 drippi...

Страница 13: ...ultifunction input analogue or digital Parameter 4 selects the probe shown on the display all the other display and control modes remain unchanged Important the easy compact models can display up to 2...

Страница 14: ...emain always on and the 15 minute off time is not considered 0 c4 100 0 c4 99 for easy compact at the moment a probe error E0 is detected the duty setting cycle starts from the current status of the c...

Страница 15: ...ater or hot gas In addition it can be managed by temperature using the defrost probe located on the evaporator In any case the defrost will end after a maximum settable safety duration The end defrost...

Страница 16: ...t performed In the event of defrost probe failure the controller performs a timed defrost with a duration equal to the value set for dP The same is true if the end defrost set point can not be reached...

Страница 17: ...compressor has just stopped and there is a minimum time between two starts Remember however that in this case the maximum number of activations per hour of the compressor may not be respected d defros...

Страница 18: ...door closed 9 Direct reverse operating mode SE r3 0 input open direct defrost input closed reverse SE r3 1 2 input open direct input closed reverse 10 Probe for dirty condenser alarm 11 Product probe...

Страница 19: ...r will start counting the pre alarm time and subsequently the dor alarm time After the pre alarm the controller will continuously signal the door open alarm the display will show the message dor alter...

Страница 20: ...UX FAN COMP A4 1 IA A4 6 P A4 7 dor P P A4 8 dor P P P Table 4 k 1 2 3 4 5 A7 digital input alarm delay Sets the delay in minutes for detecting the external alarm when A4 1 7 or 8 A8 enable alarm Ed e...

Страница 21: ...day of the week hr hours Min minutes at the end of the operations press the SET button for more than 3 seconds to permanently save the selected values and exit 1 2 3 4 5 6 7 8 9 Setting the time bands...

Страница 22: ...er models PJEZM the EZY parameter EY for the easy compact models is not featured 4 12 Other settings The operation of the device is completed by a series of additional functions such as the assignment...

Страница 23: ...n reset ENABLE ALARM parameters involved easy easy compact E0 active ON probe 1 error control automatic E1 not active ON probe 2 error defrost automatic d0 0 1 4 F0 1 E2 not active ON probe 3 error co...

Страница 24: ...SET button for more than 3 s if there are active alarms mute the buzzer the display shows the parameter code PS password press the SET button to access the password setting use the UP and DOWN buttons...

Страница 25: ...defrost priority over compressor protectors C 0 1 0 S with 1 2 probes X Y C d defrost probe reading 2 F C F S with 2 probes X Y C dC time base C 0 1 0 S with 1 2 probes X Y C A0 alarm and fan temperat...

Страница 26: ...2 probes c4 compressor on time with duty setting C 0 100 min 0 S with 1 2 probes cc continuous cycle duration C 0 15 h 4 S with 1 2 probes c6 temperature alarm bypass after continuous cycle C 0 15 h...

Страница 27: ...ndenser alarm differential temperature 10 0 8 0 10 0 10 0 10 0 10 0 10 0 10 0 Acd dirty condenser alarm delay 60 40 200 60 60 60 60 60 F0 enable evaporator fan control 1 0 1 0 F1 evaporator fan contro...

Страница 28: ...o low or the evaporator temperature is too high parameters dt and d defrost probe the manual defrost is not activated and the defrost LED flashes compressor protection times set parameter d9 select d9...

Страница 29: ...the power cable less than 3 cm from the bottom of the device or the probes for the connections only use copper wires 71x29 10 3 33 74 81 36 58 65 29 28 5 6 2 easy compact technical specifications pow...

Страница 30: ...Note...

Страница 31: ......

Страница 32: ...rugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency easy easy compact 030220791 rel 2 0 30 05 2007 CAREL reserves the right to modify the feat...

Отзывы: