• Before commencing with the installation of this appliance make sure that you
have read the following instructions carefully.
In particular familiarise yourself with the safety devices required by the system,
only then will you be able to use them to great effect.
• Not all of the safety devices required by the local safety standards have been
taken into consideration in this manual.
The installer must therefore make sure that any eventual safety devices required
by the local standards and regulations have been installed both ahead of and
after the products described in this manual.
• These instructions are aimed at professionally qualified "installers of electrical
equipment" and must respect the local standards and regulations in force .
• This appliance must be used exclusively for the purpose for which it has been
made. "i.e. for the automation of gates and doors" Any non authorised modi-
fications are to be considered improper and therefore dangerous.
Attention! This electronic programmer can only be used
with the low voltage Cardin Elettronica motors of the series
"BL", "HL" and "GL".
Electronic programmer for a DC motor with an incorporated radio receiver card,
which allows the memorisation of
300 user codes
(see "remote control" page
10). The 'rolling code' type decoder uses
433.92 MHz.
series transmitters.
The travel speed is electronically controlled based on indications given by the
travel limits, starting slowly and increasing in speed; the speed is reduced
as it nears the completely closed/open position so as to enable a controlled
smooth stop.
Programming is carried out using two buttons and allows you to configure the
system and set the pause time.
The intervention of the anticrush/antidrag sensor during the closing and open-
ing stages causes travel direction inversion (if automatic reclosing has been
enabled).
If activated towards the end of the movement (almost closed) it will act as a
travel limit.
ELECTRICAL CONNECTION
Open the "
Wiring diagram
". To make it easier to follow the instructions the
diagram has been placed on the inside of the last page of this manual.
Legend
B
Signal buzzer "via radio" mode
D
Seven segment display
F
,6A
delayed fuse (
230Vac 50-60 Hz
power supply)
F2
A
rapid action fuse (
24V
circuit )
F3
0A
rapid action fuse (motor power supply)
J2
Enable transmitter memorisation via radio
(without opening the container)
L
LED
power on
L2
LED
transmitter code management
L3
LED
manual operation
L4
LED
inverting photocells activated
L5
LED
opening travel limit activated
L6
LED
closing travel limit activated
L7
LED
stop button activated
L8
LED
stop photocell activated
M
Memory module (300 codes)
P
Programming button
P2
Selection button
P3
Transmitter code memorization button
P4
Transmitter code cancellation button
R
433 MHz radio frequency module
CN
Secondary Faston connection
24Vac
CN2
Secondary Faston connection
20Vac
(
V0:0Vac, V:5Vac, V2:20Vac
)
CN3
Motor Faston connection
IMPORTANT REMARKS
IMPORTANT REMARKS
IMPORTANT REMARKS
TO REDUCE THE RISK OF SEVERE INJURY OR DEATH READ THE FOLLOWING REMARKS
CAREFULLY BEFORE PROCEEDING WITH THE INSTALLATION. PAY PARTICULAR ATTENTION
TO ALL THE PARAGRAPHS MARKED WITH THE SYMBOL
. NOT READING THESE IMPORTANT
INSTRUCTIONS COULD COMPROMISE THE CORRECT WORKING ORDER OF THE SYSTEM.
ELECTRONIC PROGRAMMER
Before connecting the appliance make sure that the voltage and frequency
rated on the data plate conform to those of the mains supply. An all pole
trip switch with at least
3 mm
between the contacts must be installed
between the unit and the mains supply.
• Connect the control and security device wires.
• Connect the power supply cable to the device.
• Do not use cables with aluminium conductors; do not solder the ends of
cables which are to be inserted into the binding posts; use cables which are
marked
T min 85°C
and are resistant to atmospheric agents.
• The terminal wires must be positioned in such a way that both the wire and the
insulating sheath are tightly fastened (a plastic jubilee clip may be used).
Terminal board connection (pag. 28)
1-2-4-5 Common for all inputs and outputs
3
24Vac 7W
in output, powering external devices
6
24Vac 0W
in output warning lights
(intermittent or continuous activation)
7
TD
(contact N.O.) dynamic button input "Open-Close"
8
TB
(contact N.C.) stop button input (The opening of this contact inter-
rupts the cycle until a new movement command is given)
9-17
Common for all inputs and outputs
10
FCC
(contact N.C.) closing travel limit switch
11
FCA
(contact N.C.) opening travel limit switch
12
FTCI
(contact N.C.) safety and control devices in input (photocells
invert the travel direction when an obstruction is detected) The opening
of this contact will provoke a travel direction inversion during closure
due to the cutting in of the safety device
13
FTCS
(contact N.C.) safety and control devices in input (stop photo-
electric cells). The opening of this contact will block all movement, until
the obstruction has been removed, due to the safety device cutting in,
the door will then continue moving until it reaches a travel limit (only
in the automatic mode)
14
TC
(contact N.O.) closing button input
15
TA
(contact N.O.) opening button input
16
TAL
(contact N.O.) limited opening button input
18
Indicator light
24Vac 3W
19-20
230Vac 50-60 Hz
output powering the toroidal transformer
21-22 Power supply
230Vac 50-60 Hz
23-24
230Vac 40W + 40W
courtesy light output
25
Programmer earthing wire
26
Motor earth outputs
27
Mass for radio receiver antenna
28
Pole for radio receiver antenna (if an external antenna is fitted use a
coaxial type cable
RG58
with an impedance of
50
Ω
)
NOTE: ALL UNUSED NC CONTACTS MUST BE BRIDGED
Switch on the power and make sure that the red indicator
LEDS
are in the
following condition:
- L
Power on
LED
on
- L2
Transmitter programming
LED
off
- L3
Manual mode
LED
off
- L4
Safety
LED
for the inverting photoelectric cells
"FTCI"
on
- L5
Opening direction travel limit
LED
"FCA" on
*
- L6
Closing direction travel limit
LED
"FCC" on
*
- L7
Safety
LED
for the stop button
"TB"
on
- L8
Safety
LED
for the stop photoelectric cells
"FTCS"
on
*
The Leds are "ON" if the relative security device is inactive (depends on the
position of the gate/door.
Check that the activation of the safety devices switches the corresponding
LEDS
off.
If the
power on LED doesn't light up
check the condition of the fuses and the
power cable connection between binding posts
"2"
and
"22"
(
pag. 28
).
If one or more of the
safety LEDS do not light up
check the contacts of the
relative security devices and check that the unused safety device contacts
have been bridged.