Part number 3C4480 R10
5
May 2005
When mounting a proximity reader on an internal wall, check that
any reader fixed to the other side of the wall is not less than
200 mm away.
Attaching the base plate
Note:
The Prox Plus Mifare reader has been designed to metric
specifications. Any imperial measurements shown in this document
are approximate.
The Prox Plus Mifare reader is designed to be mounted on any solid
flat surface including metal surfaces.
The recommended mounting height for the Prox Plus Mifare reader
is 1100 mm from floor level to the centre of the reader device.
However this may vary in some countries and you should check
local regulations for variations to this height.
Drill a 20 mm (3/4 inch) diameter hole for the base extrusion
through or into the mounting surface to a minimum depth of 40 mm
(1½ inches).
Run the building cabling through the base.