4
Part number 3C4480 R10
May 2005
Cabling
The Prox Plus Mifare reader uses the Cardax IV communications
system. It can be connected to the following equipment:
Cardax FT Controller 3000
Cardax FT Reader I/O Interface
Cardax FT URI
Use 4 core, 0.2 mm² (AWG 24) cabling with a maximum nominal
capacitance of 120 pF/m.
With this type of cable, the maximum distance between the Prox
Plus Mifare reader and the device to which it connects is 200 m
(650 ft).
Distance between proximity readers
The distance separating any two proximity readers must not be less
than 200 mm in all directions.
200 mm