      Part Number 3E1086 R2

September 2002

Connecting to the URI

The Prox Plus 125 reader can connect to either a Cardax IV or CardaxFT URI.

Use the cable terminating tool to connect the cables to the socket as described in the
following sections.

Pin number 4 of the Prox Plus 125 connector feeds into the cable terminating tool first.

The pin numbers are marked on the connector.

Connecting to the CardaxFT URI

Connect the cables to the socket as shown.

     Prox Plus 125 Connector

4

3

2

1

GND

OUTPUTS

OUTPUTS

DET

COMMS

COMMS

5/12V

Plug P1 or P2

CardaxFT Universal Reader Interface

Red

White

Blue

Black

Connect the Prox Plus 125 connector to either the P1 or P2 plug on the CardaxFT URI.
Refer to the CardaxFT URI component layout diagram, below, for the location of the
plugs.

                             

1

Q31

D18

U19

T1

R7

R50

R55

R52

R51

R53

R54

JP2

D13

C30

D23

D24

D1

D2

D3

D4

D6

D5

D11

D10

D25

D20

D19

D17

D15

Q7

Q2

P3

D12

D16

D14

Q30

Q29

9

2

10

1

P8

JP1

0

SW1

E

Q26

1

P7

1

Q27

1

P6

COMM

NC NO

COIL

RLY2

COMM

NC NO

COIL

RLY1

D28

D27

D26

R80

R79

R95

R96

R81

R94

D21

Q28

D22

1

P4

Q41

1

P5

(c)1999 PEC(New Zealand) Ltd

REV[A][B][C]

22825V2 Assy 22826

5V

12V

+

+

GND

GND

IN6

IN5

IN4

OUTPUTS

OUTPUTS

5/12V

5/12V

DET

DET

COMMS

COMMS

GND

GND

COM

COM

NO

NO

NC

NC

GND

GND

IN3

IN2

IN1

COMMS

P4

Balanced Inputs

pin 1 = Input1
pin 2 = Input 2
pin 3 = Input 3
pin 4 = Input 4
pin 5 = Input 5
pin 6 = Input 6
pin 7 = Ground

P7

Relay Outputs

pin 1 = R1 Normally closed
pin 2 = R1 Normally open
pin 3 = R1 Common
pin 4 = R2 Normally closed
pin 5 = R2 Normally open
pin 6 = R2 Common
pin 7 = Ground

P5

Power & Comms

pins 1 & 2 = RS485
pin 3 = 13.6 V ± 15%
pin 4 = 0V

SW1

Unit address

Set unit number

P8

Diagnostic port

P6

13.6 V ± 15%out

pin 1 = 13.6 V ± 15%
pin 2 = Ground 3A fused

P3

Keypad

pin 1 = Row1
pin 2 = Row 2
pin 3 = Row 3
pin 4 = Row 4
pin 5 = Column1
pin 6 = Column2
pin 7 = Column3
pin 8 = Ground

P2

Non-CardaxFT
Reader 2

pin 1 = 5/12 V power
pin 2 = DataA
pin 3 = DataB
pin 4 = Card detect
pin 5 = LED output
pin 6 = Beeper output
pin 7 = Ground

P1

Non-CardaxFT
Reader 1

pin 1 = 5/12 V power
pin 2 = DataA
pin 3 = DataB
pin 4 = Card detect
pin 5 = LED output
pin 6 = Beeper output
pin 7 = Ground

F1

13.6 V Input Fuse

Rating = 500mA

F2

13.6 V Output Fuse

Rating = 3A

D17 

and

 D21

Relay state indicators

LED on = Energised
LED off = De-energised

D18

Run LED

D10

Comms LED

flashing = communicating with

FT Controller

JP1

Reader Voltage select

= 5V      (200mA total)
= 12V    (1A total)

P1

P2

Содержание Prox Plus 125

Страница 1: ...arthed before beginning anyservicing Before you Begin Unpack the Cardax Prox Plus 125 reader and check the shipment contains the following items 1 x Cardax Prox Plus 125 base with cable and Processor...

Страница 2: ...uce the read range of the Prox Plus 125 reader Cabling Use 4 core 0 2 mm2 AWG 24 cabling with a maximum nominal capacitance of 120 pf m The maximum external diameter of the cable must not exceed 5mm 1...

Страница 3: ...etween Proximity Readers The distance between any 2 proximity readers must be greater than 200mm in all directions Please note that 200mm in all directions includes the distance through walls Wall Pro...

Страница 4: ...o keep the unit waterproof Drill a 20mm 3 4 inch diameter hole for the base extrusion through or into the mounting surface to a minimum depth of 40mm 11 2 inch Run the building cabling through the bas...

Страница 5: ...towards the top of the reader with your thumb Lift the facia away from the base If the base is not flush to the wall or the screws have become loose you may need to pack the space between the de latch...

Страница 6: ...New Zealand Ltd REV A B C 22825V2 Assy 22826 5V 12V GND GND IN6 IN5 IN4 OUTPUTS OUTPUTS 5 12V 5 12V DET DET COMMS COMMS GND GND COM COM NO NO NC NC GND GND IN3 IN2 IN1 COMMS P4 Balanced Inputs pin 1 I...

Страница 7: ...his Installation Note for the location of the Cardax IV URI components Replacing the Facia Push the socket back into the grommet Push the connector into the socket and grommet combination Push the con...

Страница 8: ...itialise the URI with the door closed it sets the door to unlock and resets to lock as soon as the door is opened Push Button Exit If the door has a push button exit ensure the URI Exit terminal has t...

Страница 9: ...ow 3 4 Bottom Row 5 Left Column 6 Middle Column 7 Right Column 8 Not Used 1 Normally Open 2 Relay Common 3 Normally Closed Cardax Prox 125 Mifare or TIRIS Cardax Swipe 12 V ON OFF ON OFF Switch On Off...

Страница 10: ...ader Pins 1 2 4 and 5 reader type Exit Entry Connector J2 controls the Confirmed Entry function If you initialise the URI with no jumper fitted on J2 the Confirmed Entry function will be ON To switch...

Страница 11: ...For further details on software versions refer to Check Software Version in the InitialisationsectionearlierinthisInstallationNote CAUTION Do not fit the lithium battery jumper J1 before powering up t...

Страница 12: ...armfulinterferenceinaresidentialinstallation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful in...

Страница 13: ...Part Number 3E1086 R2 13 September 2002 Icons The Prox Plus 125 reader displays the following icons on the liquid crystal display LCD to indicate the access status of the zone controlled by the reader...

Отзывы: