SmartLock
®
Pro
Page 24 of 29
Installation Manual
April 2009 • Rev. 1.7
SET ADDRESS FOR SMARTLOCK CONNECT (STAND-ALONE)
To enable stand-alone operation and programming using the
Stand-Alone
Programming Module
, set the controller switch settings as follows:
1.
Locate DIP switch position 8 using the diagram above.
2.
Set switch positions 1 through 6 to the
ON
position (address 0).
3.
Set switch position 8 to enable/disable door contact input.
NOTE
: Switch setting changes do not take effect until the power is
disconnected, then reconnected.