CanProx One Installation Instructions 

August 2010 Rev 2.6 

 

Introduction 

 

The CanProx One proximity reader is mullion mountable and includes an adapter plate for wall mounting. Readers 
have 26-bit and 37-bit Weigand output capability. Credentials for the Cansec/AWID-compatible reader (CA-CPIR) 
include a standard, clamshell-style proximity card, ISO-thin proximity card – standard and magnetic stripe, Cansec’s 
CanProx One proximity key fob, and the CanProx One dual-technology RF transmitter. (

NOTE

: the dual-

technology RF transmitter only works as a proximity credential with the CanProx One Reader.) Credentials for the 
HID-compatible reader (CA-CP1RHID) include HID clamshell and graphics cards and the HID proximity key fob. 
Read range varies between credentials and with input voltage. 
 

 
 

Specifications

*

 

 

Description: 

 ............................................................................................... CanProx One multi-mount proximity reader  

Available in AWID- and HID-compatible versions 

Warranty:

  ........................................................ Limited lifetime warranty against defects in material and workmanship 

 

Operating Voltage:

  ....................................................................................................................................... 5 to 14 VDC 

Current Draw:

  ................................................................................................... 5 mA min., 45 mA typical, 80 mA max. 

Output Format: 

 .......................................................................................................................... 26-bit & 37-bit Wiegand  

Frequency:

  ........................................................................................................................................................... 125 KHz 

Range:

   ............................................................................................ up to 5” (varies with reader voltage and credentials) 

Operating Temp: 

......................................................................................................... -40 °C to 65 °C (-40 °F to 149 °F) 

Dimensions:  

 

Wall Mount:

  ..................................... 70mm (w) x 115mm (h) x 23mm (d) [2.8 in (w) x 4.5 in (h) x 1.0 in (d)] 

 

Mullion Mount:

  ................................. 40mm (w) x 98 mm (h) x 17mm (d) [1.6 in (w) x 3.9 in (h) x 0.7 in (d)] 

Weight:

  ................................................................................................................................................ approx. 85 g (3 oz) 

Colour:

  ................................................................................................................................................................ Flat  black 

Housing:

 ................................................................................................................................................. High  impact  ABS 

Mounting:

  ................................................................................................................................................ Wall or mullion 

Environment: 

 .......................................................................................................................................... Indoor/outdoor   

Rated IP 67:

  ........................................................................... Sealed against dust; protection against powerful water jet 

LED:

    ......................................................................................................................... Four-state (red, green, amber, off) 

Beeper:

  ................................................................................................................................................................. Standard 

Cable:

    .......................................... up to 7 conductors, 22 AWG, stranded, overall shield; 150 m (500 ft) max length 

 

 
 
 
 
 
 
 
 

Содержание CanProx One

Страница 1: ...CanProx One INSTALLATION INSTRUCTIONS Reader August 2010 ...

Страница 2: ...on 3 Specifications 3 Reader Wiring 4 Wall Mounting 4 Mullion Mounting 5 Removing the Reader Cover 6 Troubleshooting 6 Cansec Systems Ltd 2007 All rights reserved Page 2 2 CanProx One Installation Instructions August 2010 Rev 2 6 ...

Страница 3: ...es between credentials and with input voltage Specifications Description CanProx One multi mount proximity reader Available in AWID and HID compatible versions Warranty Limited lifetime warranty against defects in material and workmanship Operating Voltage 5 to 14 VDC Current Draw 5 mA min 45 mA typical 80 mA max Output Format 26 bit 37 bit Wiegand Frequency 125 KHz Range up to 5 varies with reade...

Страница 4: ...e adapter plate to a standard single gang electrical box 2 Wire the reader module to the access control panel Screw the reader module to the adapter plate 3 Snap the reader cover on ADAPTER PLATE READER MODULE READER COVER Page 4 4 CanProx One Installation Instructions August 2010 Rev 2 6 ...

Страница 5: ...holes drill an appropriate pilot hole for the screws you intend to use CABLE FEED HOLE 7 8 22 mm SCREW HOLE SCREW HOLE 1 13 16 46 mm 13 16 21 mm 39 64 16 mm 35 64 14 mm 2 Wire the reader module to the access control panel Screw the reader module to the mullion 3 Snap the reader cover on MULLION READER MODULE READER COVER Page 5 5 CanProx One Installation Instructions August 2010 Rev 2 6 ...

Страница 6: ...ble with the reader The reader has a short read range 1 The connection of the readers shield wire has opened somewhere Check the shield line for open connections Make sure it is properly connected to the access panel 2 The reader is mounted too close to a device that radiates electro magnetic interference If possible install the reader in a different location or move any other electronic devices a...

Отзывы: