Removing the Reader Cover 

 

1.

 

Insert a slotted screwdriver into the slot located at the bottom of the reader cover. 

2.

 

Gently pry the reader cover off. 

 
 
 
 
 
 
 

 

 
Troubleshooting 

 

PROBLEM 

POSSIBLE CAUSE 

CORRECTIVE ACTION 

The reader does not recognize 

a card/tag (no beep, no LED 
flash). 

1.  One or more of the readers’ 

wiring connections are incorrect. 

Power down the reader/access panel and check that 

your wiring is correct. 

 

2.  The reader is not receiving proper 
power from the access panel. 

Measure the voltage at the reader. It should be 
b5 VDC and +14 VDC. 

 

3.  The reader is mounted too close 
to a device that radiates 
electromagnetic interference. 

If possible, install the reader in a different location or 
move any other electronic devices away from the 
reader. 

 

4.  You are using an incorrect type of 
card. 

Make sure you are using an access card that is 
compatible with the reader. 

The reader has a short read 
range. 

1.  The connection of the readers 
shield wire has opened somewhere. 

Check the shield line for open connections. Make 
sure it is properly connected to the access panel. 

 

2.  The reader is mounted too close 
to a device that radiates electro-
magnetic interference. 

If possible, install the reader in a different location or 
move any other electronic devices away from the 
reader. 

 

3.  The power supply is generating 

electromagnetic interference. 

The power supply on the access panel must be a 

regulated, linear supply. Switching supplies are often 
sources of electromagnetic interference. 

 

CanProx One is compliant with the following organizations: 

 

 

 

 

 

 

 
FCC compliance statement: This device complies with part 15 of the FCC rules. Operation is subject to the following two 
conditions:   
(1) This device may not cause harmful interference; and  
(2) This device must accept any interference received, including interference that may cause undesired operation. 

 

 Page: 

6/6 

 

CanProx One Installation Instructions 

August 2010 Rev 2.6 

 

Содержание CanProx One

Страница 1: ...CanProx One INSTALLATION INSTRUCTIONS Reader August 2010 ...

Страница 2: ...on 3 Specifications 3 Reader Wiring 4 Wall Mounting 4 Mullion Mounting 5 Removing the Reader Cover 6 Troubleshooting 6 Cansec Systems Ltd 2007 All rights reserved Page 2 2 CanProx One Installation Instructions August 2010 Rev 2 6 ...

Страница 3: ...es between credentials and with input voltage Specifications Description CanProx One multi mount proximity reader Available in AWID and HID compatible versions Warranty Limited lifetime warranty against defects in material and workmanship Operating Voltage 5 to 14 VDC Current Draw 5 mA min 45 mA typical 80 mA max Output Format 26 bit 37 bit Wiegand Frequency 125 KHz Range up to 5 varies with reade...

Страница 4: ...e adapter plate to a standard single gang electrical box 2 Wire the reader module to the access control panel Screw the reader module to the adapter plate 3 Snap the reader cover on ADAPTER PLATE READER MODULE READER COVER Page 4 4 CanProx One Installation Instructions August 2010 Rev 2 6 ...

Страница 5: ...holes drill an appropriate pilot hole for the screws you intend to use CABLE FEED HOLE 7 8 22 mm SCREW HOLE SCREW HOLE 1 13 16 46 mm 13 16 21 mm 39 64 16 mm 35 64 14 mm 2 Wire the reader module to the access control panel Screw the reader module to the mullion 3 Snap the reader cover on MULLION READER MODULE READER COVER Page 5 5 CanProx One Installation Instructions August 2010 Rev 2 6 ...

Страница 6: ...ble with the reader The reader has a short read range 1 The connection of the readers shield wire has opened somewhere Check the shield line for open connections Make sure it is properly connected to the access panel 2 The reader is mounted too close to a device that radiates electro magnetic interference If possible install the reader in a different location or move any other electronic devices a...

Отзывы: