Cannon Fitzroy Inbuilt Power Flue | 15

serViCe instrUCtions (Do not MoDify tHis aPPlianCe)

fig 35

To Replace The Burner And Spark/Sense Electrodes

1. remove the logs from the burner chamber.
2.  remove the burner chamber front inspection panel,  

4 screws.

3.  Disconnect the 16mm nut at the inlet of the  

injector.

4.  Disconnect the spark and sense electrodes from the 

ignition module.

5.  remove the burner fixing brackets (2) from the  

left and right hand side of the burner. lift the burner 
assembly upward and carefully remove from the  
burner chamber.

6.  replace in reverse order, checking correct location of 

spark/sense electrodes. Spark gap between electrode 
and spark plate is 6 - 8 mm. Check for gas tightness. 
For log placement refer page 12 of this manual.

To Replace The Combustion Fan (Fig 36)

the Combustion Fan is accessed from the rear of the 
heater. therefore to replace the combustion fan the 
heater must be removed from the fireplace. the flue 
terminal may need to be removed from the flue hoses  
to allow the heater to be moved.
1. remove the rear cover
2. Disconnect combustion fan wiring from loom.
3. remove the rear cover.
4.  remove the four (4) screws securing the fan to  

fan duct.

5. remove fan assembly from fan duct.
6. replace in reverse order.

To Replace The Gas And Fan Controller

1.   remove the fascia. refer to page 11 of the  

installation booklet

2.  Disconnect the plugs on box.
3.  remove the screw retaining the bracket
4.   replace the control box
5.  Check and re-set gas pressures.

To Replace Type “X”Cord

Contact Sampford IXl service department.

fig 36

Содержание Fitzroy Inbuilt Power Flue

Страница 1: ...Flue Instruction Manual Please read this manual before installing and using this heater Please leave instruction manual with the owner Distributor This appliance is designed manufactured and distribut...

Страница 2: ...of this warranty repair or replace free of charge this Cannon appliance or any component part which upon examination by us or our repair agent is found to be defective in materials workmanship or man...

Страница 3: ...S 3100 AS 5601 AS 4553 2008 Safety Warnings Please read this manual before installing and using the heater Safety Warnings 1 Improper installation adjustment alteration service or maintenance can caus...

Страница 4: ...OFF button once to restart the heater during this time Wait at least 20 seconds before attempting to turn the heater on OperatiON ON OFF LOW HIGH MEDIUM FIG 2 FIG 1 If there is an interruption to the...

Страница 5: ...FLUEWFX Versatility and flexibility are key components of our instal lation options Install in a shallow recess or an existing fireplace elegant spacers will eliminate any size discrep ancies To enhan...

Страница 6: ...lectronic direct spark Power requirement 240 VAC 10 Amp Power consumption 90 VA maximum Minimum cavity Height Dimensions 605 mm Width 700 mm Depth 485 mm Optional accessories Glass front Remote thermo...

Страница 7: ...TER IS FAN ASSISTED SEE COLUMN HIGHLIGHTED a Below eaves balconies and other projections Appliances up to 50 MJ hr input 300 200 Appliances over 50 MJ hr input 500 300 b From the ground above a balcon...

Страница 8: ...Ensure that the combustion air opening under the heater is not obstructed Ensure the minimum clearances to combustible materials are maintained during installation including adequate space for the pr...

Страница 9: ...level Using your template as a guide mark the flue cutout on the rear wall of the cavity and cut through from either the inside or the outside to produce a neat round hole in the external wall To mak...

Страница 10: ...8 Fitment Of Flexible Pipes To Flue Terminal The flexible tubing is now fully extended out of the hole in the wall 1 Cut the tubing so that 20mm is extending past the wall opening 2 Fit the stainless...

Страница 11: ...liance is designed to operate on 240V AC power supply Failure to operate unit at correct supply voltage may create unsafe conditions The heater is supplied with a flexible power cord with a plug fitte...

Страница 12: ...er glass making sure not to over tighten the screws 4 Reconnect switch loom to the fascia switch set 5 Replace the fascia GAS CONNECTION FIG 24 FIG 25 FIG 27 FIG 26 1 Push the gas inlet access plate i...

Страница 13: ...w control to give a pressure reading of 0 4 kPa for Natural Gas and 1 1 kPa for LPG Turn clockwise to increase pressure and anticlockwise to decrease pressure Refer FIG 33 5 Remove spanner and screwdr...

Страница 14: ...r to fault codes on page 17 General 1 Service work to be carried out by an authorised service person only 2 Unplug from wall socket or turn off power at main switchboard if heater is hard wired 3 Alwa...

Страница 15: ...m Check for gas tightness For log placement refer page 12 of this manual To Replace The Combustion Fan Fig 36 The Combustion Fan is accessed from the rear of the heater Therefore to replace the combus...

Страница 16: ...HIGH FAN SHEATHED HIGH TEMP DATA CABLE SWITCH BLUE 4 WAY 2 WAY 6 WAY 3 WAY EARTH RED 1 WAY C ROOM FAN F3594 240 V MAINS PLUG BROWN BLUE MODULATING VALVE F3691 COILS FLAME SENSOR SPARK ELECTRODE IGNITI...

Страница 17: ...r has attempted to light however it did not sense flame within the allowed time Check the gas supply to the unit is not switched off Check the gas pressures Check the flame and spark electrode connect...

Страница 18: ...fan for dust build up and lint Check that the room air fan is spinning Check that the pressure tubes are connected correctly and not pinched or kinked The black tube should run from the black side of...

Страница 19: ...Cannon Fitzroy Inbuilt Power Flue 19 Notes...

Страница 20: ...mpliance Certificate No Installed by COPY RATING LABEL HERE Don t Risk Your Appliance Warranty Only a licensed person will give you a compliance certificate showing that the work complies with all the...

Отзывы: