background image

Cannon Fitzroy Inbuilt Power Flue | 13

setting tHe gas PressUre

1.  gas valve layout is as indicated in 

FIG 29

Pressures for ‘burner high flame’ and ‘burner low 
flame’ are factory set, however if pressures need to be 
checked or adjusted follow the procedures described 
below. to check outlet pressure at burner ‘high flame’ 
and ‘low flame’ positions remove the plastic cap from 
the regulatior adjustment location as indicated  
in 

FIG 30

.

2.  the pressure point is closed with a captive screw. turn 

screw 6 revolutions anticlockwise to open the pressure 
point as indicated on 

FIG 31 (a)

 and place manometer 

tube over the test point as per 

FIG 31 (b)

.

3.  Switch the control buttons to ‘High flame’ position. 

Wait for heater to switch to ‘High’ setting (time delay 
on start up). retain screwdriver in position and using 
a spanner adjust the outer nut on the control to give a 
pressure reading of 0.75 kPa for natural gas and 2.65 
kPa for lPg. 

(Turn clockwise to increase pressure 

and anticlockwise to decrease pressure)

refer 

FIG 32

.

4.  Switch the control buttons to ‘low flame’ position. 

retain spanner in position and using a screwdriver 
adjust the central screw control to give a pressure 
reading of 0.4 kPa for natural gas and 1.1 kPa for 
lPg. 

(Turn clockwise to increase pressure and 

anticlockwise to decrease pressure)

refer 

FIG 33

.

5. remove spanner and screwdriver. Switch from high to       
    low to ensure settings are correct.
6.  Switch heater off and remove the manometer  

tube. tighten pressure test point by  
turning the captive screw fully clockwise.

7.  replace plastic cap. ensure the little lug is positioned 

towards lower right hand side to clear the controls.

8.  refit the fascia, making sure not to damage the power 

cord or switch cable.

9.  Operate the heater on HIgH, MeDIuM and lOW 

settings. the flame should be stable, no lifting from the 
burner and the logs should glow after approximately 
15 minutes of operation on HIgH setting.

If the flame is unstable:

• Check that the burner is located correctly.
•  Check that the glass front is located correctly and is 

against the sealing rope.

• Check that the gas pressure is correctly adjusted
• Check that flue is operating correctly

If the heater still does not operate to specification refer  
to the troubleshooting chart on page 19, or contact  
Sampford IXl in your state.

fig 30

fig 31

(a)

(b)

fig 29

burner adjustment 
(burner ‘low flame’)

Plastic Cap

Pressure adjustment 
(burner ‘Full on’)

Pressure test 
point with captive 
screw

fig 32

adjust

Hold

fig 33

Hold

adjust

Содержание Fitzroy Inbuilt Power Flue

Страница 1: ...Flue Instruction Manual Please read this manual before installing and using this heater Please leave instruction manual with the owner Distributor This appliance is designed manufactured and distribut...

Страница 2: ...of this warranty repair or replace free of charge this Cannon appliance or any component part which upon examination by us or our repair agent is found to be defective in materials workmanship or man...

Страница 3: ...S 3100 AS 5601 AS 4553 2008 Safety Warnings Please read this manual before installing and using the heater Safety Warnings 1 Improper installation adjustment alteration service or maintenance can caus...

Страница 4: ...OFF button once to restart the heater during this time Wait at least 20 seconds before attempting to turn the heater on OperatiON ON OFF LOW HIGH MEDIUM FIG 2 FIG 1 If there is an interruption to the...

Страница 5: ...FLUEWFX Versatility and flexibility are key components of our instal lation options Install in a shallow recess or an existing fireplace elegant spacers will eliminate any size discrep ancies To enhan...

Страница 6: ...lectronic direct spark Power requirement 240 VAC 10 Amp Power consumption 90 VA maximum Minimum cavity Height Dimensions 605 mm Width 700 mm Depth 485 mm Optional accessories Glass front Remote thermo...

Страница 7: ...TER IS FAN ASSISTED SEE COLUMN HIGHLIGHTED a Below eaves balconies and other projections Appliances up to 50 MJ hr input 300 200 Appliances over 50 MJ hr input 500 300 b From the ground above a balcon...

Страница 8: ...Ensure that the combustion air opening under the heater is not obstructed Ensure the minimum clearances to combustible materials are maintained during installation including adequate space for the pr...

Страница 9: ...level Using your template as a guide mark the flue cutout on the rear wall of the cavity and cut through from either the inside or the outside to produce a neat round hole in the external wall To mak...

Страница 10: ...8 Fitment Of Flexible Pipes To Flue Terminal The flexible tubing is now fully extended out of the hole in the wall 1 Cut the tubing so that 20mm is extending past the wall opening 2 Fit the stainless...

Страница 11: ...liance is designed to operate on 240V AC power supply Failure to operate unit at correct supply voltage may create unsafe conditions The heater is supplied with a flexible power cord with a plug fitte...

Страница 12: ...er glass making sure not to over tighten the screws 4 Reconnect switch loom to the fascia switch set 5 Replace the fascia GAS CONNECTION FIG 24 FIG 25 FIG 27 FIG 26 1 Push the gas inlet access plate i...

Страница 13: ...w control to give a pressure reading of 0 4 kPa for Natural Gas and 1 1 kPa for LPG Turn clockwise to increase pressure and anticlockwise to decrease pressure Refer FIG 33 5 Remove spanner and screwdr...

Страница 14: ...r to fault codes on page 17 General 1 Service work to be carried out by an authorised service person only 2 Unplug from wall socket or turn off power at main switchboard if heater is hard wired 3 Alwa...

Страница 15: ...m Check for gas tightness For log placement refer page 12 of this manual To Replace The Combustion Fan Fig 36 The Combustion Fan is accessed from the rear of the heater Therefore to replace the combus...

Страница 16: ...HIGH FAN SHEATHED HIGH TEMP DATA CABLE SWITCH BLUE 4 WAY 2 WAY 6 WAY 3 WAY EARTH RED 1 WAY C ROOM FAN F3594 240 V MAINS PLUG BROWN BLUE MODULATING VALVE F3691 COILS FLAME SENSOR SPARK ELECTRODE IGNITI...

Страница 17: ...r has attempted to light however it did not sense flame within the allowed time Check the gas supply to the unit is not switched off Check the gas pressures Check the flame and spark electrode connect...

Страница 18: ...fan for dust build up and lint Check that the room air fan is spinning Check that the pressure tubes are connected correctly and not pinched or kinked The black tube should run from the black side of...

Страница 19: ...Cannon Fitzroy Inbuilt Power Flue 19 Notes...

Страница 20: ...mpliance Certificate No Installed by COPY RATING LABEL HERE Don t Risk Your Appliance Warranty Only a licensed person will give you a compliance certificate showing that the work complies with all the...

Отзывы: