1. Introduction

.7.

.6.

2.1 Safety symbols

Improper use may result in electric shock hazards or burns. This product manual contains 

important instructions that are required to be followed during installation and maintenance. 

Please read these instructions carefully before use and keep them in an easily locatable place 

for future reference.

Safety symbols used in this manual, which highlight potential safety risks and important safety 

information, are listed below:

WARNING

 

Symbol indicates important safety instructions, which if not correctly 

followed, could result in serious injury or death.

NOTE

 

Symbol indicates important safety instructions, which if not correctly 
followed, could result in damage to or the destruction of the inverter.

CAUTION, RISK OF ELECTRIC SHOCK

 

Symbol indicates important safety instructions, which if not correctly 
followed, could result in electric shock

CAUTION, HOT SURFACE 

Symbol indicates safety instructions, which if not correctly 
followed, could result in burns.

2.2 General safety instructions

WARNING

 

Do not connect PV array positive (+) or negative (-) to ground – doing 

so could cause serious damage to the inverter.

WARNING

 

Electrical installations must be done in accordance with local and 

national electrical safety standards. 

●  Use the original box to repackage the inverter, seal with adhesive tape with the desiccant inside the 

    box. 

●  Store the inverter in a clean and dry place, free of dust and dirt. The storage temperature must be

between -40 - 70

 and humidity should be between 0 to 95%, non-condensing. 

●  Do not stack more than two (2) inverters high on a single pallet. Do not stack more than 2 pallets

high.

●  Keep the box(es) away from corrosive materials to avoid damage to the inverter enclosure.

●  Inspect the packaging regularly. If packing is damaged (wet, pest damages, etc.), repackage the 

    inverter immediately.

●  Store inverters on a flat, hard surface -- not inclined or upside down.

●  After 100 days of storage, the inverter and carton must be inspected for physical damage before

installing. If stored for more than 1 year, the inverter needs to be fully examined and tested by

qualified service or electrical personnel before using.

●  Restarting after a long period of non-use requires the equipment be inspected and, in some cases,

the removal of oxidation and dust that has settled inside the equipment will be required.

1.2.1 Storage

If the inverter is not installed immediately, storage instructions and environmental conditions are below:

DO

NOT

STACK

MORE

THAN

HIGH

Figure 1.3

2

2. Safety Instructions

WARNING

 

To reduce the risk of fire, branch circuit over-current protective 

devices (OCPD) are required for circuits connected to the Inverter.

CAUTION 

The PV array (solar panels) supplies a DC voltage when exposed to light.

Содержание CSI-50K-T400GL03-E

Страница 1: ...Sales Inquiries Email sales au csisolar com Customer Support Email service au csisolar com South East Asia 101 Thompson Road 15 03 United Square Singapore 307591 P 65 6572 905 F 65 6559 4690 Sales In...

Страница 2: ...1 Start up procedure 6 2 Shutdown procedure 39 39 39 7 1 Main Menu 40 40 7 2 Information 4 1 Inverter monitoring connection 28 7 Normal operation 40 4 2 DRM Connection Logic Interface Connection 31 7...

Страница 3: ...ontact your local Canadian Solar distributor Cross screws M4 14 x4 Cross Recessed Hexagon Bolt M6 12 x2 User manual x1 Manual AC terminal cover x1 4pin COM Port 16pin COM Port 16pin COM Connector x1 U...

Страница 4: ...nal box to repackage the inverter seal with adhesive tape with the desiccant inside the box Store the inverter in a clean and dry place free of dust and dirt The storage temperature must be between 40...

Страница 5: ...following The temperature of the inverter heat sink can reach 75 The inverter is designed to work in an ambient temperature range between 25 to 60 If multiple inverters are installed on site a minimu...

Страница 6: ...electricity supply the sound level from the inverter can be quite high 3 2 Product handling Figure 3 3 Handles used to move the inverter shown circled in red 3 1 2 4 Air circulation Do not install in...

Страница 7: ...ally The steps to mount the inverter are listed below 1 Refer to Figure 3 6 drill holes for expansion bolt M10 90 based on the hole diameter of bracket using a precision drill keeping the drill perpen...

Страница 8: ...from vertical Figure 3 10 Wrong installation Angle The steps to mounted to the rack are listed below 3 Install mounting plate 1 Remove the bracket and fasteners from the packaging Mark the position f...

Страница 9: ...he Grid Supply Main Switch AC OFF 2 Switch the DC Isolator OFF 3 Connect the inverter to the grid 4 Assemble PV connector and connect to the Inverter Inverter design uses PV style quick connect termin...

Страница 10: ...nding 2 Prepare OT terminals M10 To effectively protect the inverter two grounding methods must be performed Connect the AC grounding cable Please refer to section 3 4 3 Connect the external grounding...

Страница 11: ...MAKE SURE the polarity of the PV array output conductors matches the DC and DC terminal labels before connecting these conductors to the terminals of the inverter 5 Measure PV voltage of DC input wit...

Страница 12: ...urrent protection device must be used between the inverter and the grid 3 4 3 1 Connecting the inverter to the utility grid All electrical installations must be carried out in accordance with the loca...

Страница 13: ...of the OT terminal then use a hydraulic crimp tool to crimp the terminal The crimped portion of the terminal must be insulated with heat shrinkable tube or insulating tape 1 Strip the end of AC cable...

Страница 14: ...12 5 13 6 14 7 15 8 16 Meter RS485 B DRM 2 6 COM1 485 A DRM 3 7 COM1 485 B DRM 4 8 RefGen COM2 485 A Com DRM0 COM2 485 B V 12V V GND Figure 4 1 16pin COM Connector The following is the assembly diagra...

Страница 15: ...or one to multiple datalogging boxes including WiFi box and GPRS Box for the monitoring of multiple inverters Please refer to corresponding manuals for details 4 1 1 Monitoring for a single inverter E...

Страница 16: ...between Pin13 and Pin14 the inverter will reduce its output power to zero within 5s Figure 4 10 Pin Definition 13 14 RefGen Com DRM0 After wiring connection of DRM or Logic interface please refer to s...

Страница 17: ...n Connector 4 3 Meter Connection The inverter can work with a three phase smart meter to achieve Export Power Management function and or 24hour consumption monitoring function The Pin 1 and Pin 2 of t...

Страница 18: ...service technicians only The inverter is customized according to the local grid standard before shipping There should be no requirement to set the standard NOTE The User Def function can only be used...

Страница 19: ...the inverter see Specifications in section 10 may damage the inverter Although Canadian Solar inverters feature reverse polarity protection prolonged connection in reverse polarity may damage these p...

Страница 20: ...s start up voltage the inverter will turn on The red DC POWER LED and LCD will be continuously lit 4 Canadian Solar inverters are powered from the DC side When the inverter detects DC power that is w...

Страница 21: ...1 Information list Status Generating Power 0000W Grid Frequency F_Grid 00 00Hz Total Energy 0000000 kwh This Month 0000kwh Last Month 0000kwh Today 00 0kwh Yesterday 00 0kwh 10 sec 10 sec 10 sec 10 s...

Страница 22: ...arm Message 2 Running message 3 Version 4 Daily Energy 5 Monthly Energy 6 Yearly Energy 7 Daily Records 8 Communication Data 9 Warning Message The following submenus are displayed when the Settings me...

Страница 23: ...history of changing settings Only for maintance personel 7 Normal operation 7 Normal operation 7 4 3 Version The screen shows the model version of the inverter And the screen will show the software v...

Страница 24: ...ea is for fully qualified and accredited technicians only Please follow 7 4 to enter password to access this menu Select Advanced Settings from the Main Menu to access the following options 1 Select S...

Страница 25: ...ed to set the new password for menu Advanced info and Advanced information Figure 7 20 Set new password YES ENT NO ESC Password 0000 Enter the right password before set new password Press the DOWN key...

Страница 26: ...ystem Zero injection can be achieved Smart meter can be installed either on the grid side OR the load side 7 5 8 STD Mode Settings 1 Working Mode Set 2 Power Rate Limit 3 Freq Derate Set 4 10mins Volt...

Страница 27: ...ion For other regions customers can enable or disable the function as they desire NOTE When the failsafe function is ON and CT Meter is disconnected somehow the inverter will stop generation and give...

Страница 28: ...als to one of three phase load power that is the lowest load power of a certain phase Figure 7 30 Inverter Meter 7 5 13 Restart HMI The function is used for restart the HMI This function is applicable...

Страница 29: ...Test Figure 7 32 Selecting Fan Test displays the sub menu shown below Are you sure YES ENT NO ESC Fan Test is a factory test function Press the ENTER key to start the test Press the ESC key to return...

Страница 30: ...r damages caused by unauthorized modifications NOTE The setting corresponds to the current status as well which can be used to inspect the ON OFF state of the AFCI function 7 6 2 Arc Fault During the...

Страница 31: ...xed 2 Check if the DSP connector to power board are fixed 1 Check inverter surrounding ventilation 2 Check if there s sunshine direct on inverter in hot weather 1 Use user define function to adjust th...

Страница 32: ...ing current down below 0 5A Turn off the two DC switchs and fix the polarity issue Screen OFF with DC applied Inverter internally damaged 1 Do not turn off the DC switches as it will damage the invert...

Страница 33: ...umber Max input strings number Rated grid voltage Volts Power Factor at rated output power Max efficiency EU efficiency Topology Self consumption night Operating ambient temperature range Relative hum...

Страница 34: ...70 71 11 Declarations 11 1 REACH Declaration 11 Declarations...

Страница 35: ...72 11 Declarations 11 Declarations 73 11 2 CE and RoHS Declaration...

Страница 36: ...11 Declarations 74...

Страница 37: ...ances and are properly ventilated Completed 5 Serial number Record the product serial numbers located on the side label Serial Numbers attached list 6 Solar modules Confirm PV module installation comp...

Страница 38: ...he grid supply main Switch AC ON first 2 Switch the DC switch ON If the voltages of PV arrays are higher than start up voltage the inverter will turn on The red LED power will be continuously lit 3 Wh...

Страница 39: ...face Completed Record current date time in Notes 6 Communication setting if avail Set communication with a unique address for each inverter Completed Record address in Notes 7 Machine version For main...

Страница 40: ...Output power Input DC voltage Insulation limit K PV start up voltage Grid V Max V Min Frequency Max Min Reactive compensation PF Configuration MPPT Individual MPPT Parallel Monitoring RS485 Ethernet...

Страница 41: ...r to inverter site selection and installation 3 PHASE STRING INVERTERS CSIF ST 016 A 0 INSTALLER S NAME INSTALLER S SIGNATURE COMPANY DATE Inverter serial numbers 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1...

Отзывы: