1. Introduction

.7.

.6.

2.1 Safety symbols

Safety symbols used in this manual, which highlight potential safety risks and important safety 

information, are listed below:

WARNING

 

Symbol indicates important safety instructions, which if not correctly 

followed, could result in serious injury or death.

NOTE

 

Symbol indicates important safety instructions, which if not correctly 
followed, could result in damage to or the destruction of the inverter.

CAUTION, RISK OF ELECTRIC SHOCK

 

Symbol indicates important safety instructions, which if not correctly 
followed, could result in electric shock

CAUTION, HOT SURFACE 

Symbol indicates safety instructions, which if not correctly 
followed, could result in burns.

2.2 General safety instructions

WARNING

 

Do not connect PV array positive (+) or negative (-) to ground – doing 

so could cause serious damage to the inverter.

WARNING

 

Electrical installations must be done in accordance with local and 

national electrical safety standards. 

●  Use the original box to repackage the inverter, seal with adhesive tape with the desiccant inside the 

    box. 

●  Store the inverter in a clean and dry place, free of dust and dirt. The storage temperature must be

between -40 and 158 

°

F (-40 - 70

°

C) and humidity should be between 0 to 100%, non-condensing. 

●  Do not stack more than two (2) inverters high on a single pallet. Do not stack more than 2 pallets

high.

●  Keep the box(es) away from corrosive materials to avoid damage to the inverter enclosure.

●  Inspect the packaging regularly. If packing is damaged (wet, pest damages, etc.), repackage the 

    inverter immediately.

●  Store inverters on a flat, hard surface -- not inclined or upside down.

●  After 100 days of storage, the inverter and carton must be inspected for physical damage before

installing. If stored for more than 1 year, the inverter needs to be fully examined and tested by

qualified service or electrical personnel before using.

●  Restarting after a long period of non-use requires the equipment be inspected and, in some cases,

the removal of oxidation and dust that has settled inside the equipment will be required.

1.2.1 Storage

If the inverter is not installed immediately, storage instructions and environmental conditions are below:

DO

NOT

STACK

MORE

THAN

HIGH

Figure 1.3

2

2. Important Safety Instruction

WARNING

 

To reduce the risk of fire, branch circuit over-current protective 

devices (OCPD) are required for circuits connected to the Inverter.

CAUTION 

The PV array (solar panels) supplies a DC voltage when exposed to light.

SAVE THESE INSTRUCTIONS – This manual contains important instructions for Models 

CSI-125-T600GL02-U that shall be followed during installation and maintenance of the 

inverter.

Содержание CSI-125-T600GL02-U

Страница 1: ...gsu China 215129 P 1 519 837 1881 F 1 519 837 2550 Sales Inquiries Email info csisolar com Customer Support Email service ca csisolar com This manual is subject to change without prior noti cation Cop...

Страница 2: ...equipment has supplied The customer is fully liable for any modifications made to the system therefore any hardware or software modification manipulation or alteration not expressly approved by the ma...

Страница 3: ...reen 3 3 2 Rack mounting 3 4 Electrical Connections 17 18 3 4 1 Grounding 20 3 4 2 Connect PV side of inverter 23 3 4 3 Connect grid side of inverter 26 4 Communication Monitoring 6 5 1 Set Time 40 6...

Страница 4: ...emarks The inverter ships with all accessories in one carton When unpacking please verify all the parts listed below are included 3 4 Fastening screw 2 User manual 1 1 2 3 4 Manual Canadian Solar Thre...

Страница 5: ...en 0 to 100 non condensing Do not stack more than two 2 inverters high on a single pallet Do not stack more than 2 pallets high Keep the box es away from corrosive materials to avoid damage to the inv...

Страница 6: ...against the inverter 3 Installation To meet relevant codes and standards the Canadian Solar three phase inverter line is equipped with protective circuitry and controls Anti Islanding Protection Isla...

Страница 7: ...verter can be quite high 3 2 Product handling Figure 3 3 Handles used to move the inverter shown circled in red 3 1 2 4 Air circulation Do not install in small closed rooms where air cannot freely cir...

Страница 8: ...1 Refer to Figure 3 6 drill holes for mounting screws based on the hole diameter of bracket using a precision drill keeping the drill perpendicular to the wall Max depth is 90mm 2 Make sure the brack...

Страница 9: ...gle Please install the inverter vertically If the inverter cannot be mounted vertically it may be tilted backward to 15 degrees from vertical Vertical 15 Backward Figure 3 9 Correct installation Angle...

Страница 10: ...3 Connect the AC wires 4 Connect the DC wires The inverter is designed with a wiring box at the bottom Before the electrical connection it requires the cover for the bottom wiring box to be removed Ta...

Страница 11: ...ion 3 4 3 Connect the external grounding terminal 1 Prepare the grounding cable recommend to use the outdoor copper core cable The grounding wire should be at least half size of the hot wires To conne...

Страница 12: ...ol to crimp the terminal The crimped portion of the terminal must be insulated with heat shrinkable tube or insulating tape 4 Insert the cable through the nut sheath and DC terminal cover Connect the...

Страница 13: ...we recommend installing a device for protection against over current and leakage with the following characteristics noted in Table 3 2 3 4 2 1 DC connection high voltage danger notice CAUTION RISK OF...

Страница 14: ...erminal then use a hydraulic crimp tool to crimp the terminal The crimped portion of the terminal must be insulated with heat shrinkable tube or insulating tape 1 Strip the end of AC cable insulating...

Страница 15: ...net OUT Figure 4 3 Strip the insulation layer and connect to RJ45 plug Correspondence between the cables and the stitches of plug Pin 1 white and orange Pin 2 orange Pin 3 white and green Pin 4 blue P...

Страница 16: ...for onsite Ethernet communication commissioning If the router doesn t support automatic IP address use an Ethernet cable to connect the Ethernet module and your laptop Change the Laptop s IP address...

Страница 17: ...0 100 254 via web browser Enter username and password admin admin 3 Select Network from left menu 4 Select Use IP address below radio button Enter IP address subnet mask and default gateway Click Save...

Страница 18: ...inverter inverter damage or the inverter not operating at all 5 2 Changing the grid standard 5 2 1 Procedure to set the grid standard NOTE This operation is for service technicians only The inverter...

Страница 19: ...the strings if a leakage to ground has been detected Improper operation and damage to the inverter may result Once all DC tests have been completed close the fuse holders Measure leakage to ground to...

Страница 20: ...hat is within start up and operating ranges the inverter will turn on After turn on the inverter will check internal parameters sense and monitor AC voltage hertz rate and the stability of the supply...

Страница 21: ...he reactive power of the inverter App_Power Shows the apparent power of the inverter Work Mode Volt watt DRM NO 08 10 sec Work Mode Shows current working mode DRM NO Shows DRM Number VPV_Total 1000 0V...

Страница 22: ...3 NEXT ENT OK ESC 01 01 2019 16 37 Figure 6 3 Set Time Press the UP DOWN keys to set time and data Press the ENTER key to move from one digit to the next from left to right Press the ESC key to save t...

Страница 23: ...7 Daily Records The screen shows history of changing settings Only for maintance personel 6 6 3 Version The screen shows the model version of the inverter And the screen will show the software ver by...

Страница 24: ...V 415 1S V 415 0 16S 207 V 304 2S V 207 0 16S 60 5Hz F 62Hz 2S F 2Hz 6 0 16S 57Hz F 59 5Hz 2S 57Hz F 0 16S 600V Rated L L 6 7 Advanced Settings Technicians Only NOTE To access to this area is for full...

Страница 25: ...the previous menu 6 7 7 Special Settings This function is applicable by maintenance personnel only wrong operation will prevent the inverter from reaching maximum power 6 7 2 Grid ON OFF Grid ON Grid...

Страница 26: ...346 415V Default 381V Figure 6 22 Volt VAR Voltage1 303V Voltage2 340V 1 NULL Description Inverter is not under any working mode 6 Normal operation 6 Normal operation 6 7 8 STD Mode Settings 1 Working...

Страница 27: ...Fixed PF Description Inverter will output power with fixed power factor Setting Range 0 8 to 0 8 Default value is PF 1 5 Reac power Not Required Description Inverter will generate reactive power base...

Страница 28: ...nge 0 8 to 0 8 Default value is PF 1 6 Normal operation 6 Normal operation 6 7 8 1 2 With Rule21 Standard selected NOTE The other three working mode P1 V Watt P1 V Var and P1 V P V Q are NOT applicabl...

Страница 29: ...check the Volt watt and Volt var priority simply enter the working modes V Q V P indicates Volt Var First V P V Q indicates Volt Watt First 6 Normal operation 6 Normal operation 5 Reac power Not Requ...

Страница 30: ...scope 61 64Hz the default setting 62Hz Press the Enter key to select the mode or frequency Press Up Down to set Press ESC to save the settings Figure 6 36 Freq Watt characteristic f min f nom f start...

Страница 31: ...ximum power 6 7 8 5 Power Priority Figure 6 39 Power Priority This setting is used to set the priority between Active Power Control Watt and Reactive Power Control Var YES ENT NO ESC Select Var First...

Страница 32: ...not change this setting unless specifically instructed to This function is used to calibrate inverter output energy and voltage It will not impact the energy count for inverter with RGM Two sections...

Страница 33: ...ween PV and ground No need any control or settings The Anti PID module repairs the PID effect of the PV model at night When operating the inverter LCD screen displays PID repairing information and the...

Страница 34: ...age displayed on the screen and the status of the screen status indicator lights Other readings obtained from the Information sub menu refer to Section 6 4 will also be helpful 5 PV array configuratio...

Страница 35: ...Test DC switch OFF Check PV connections Check polarity Check voltage 860V Test DC Switch ON Check voltage 860V If DC voltage is 0 replace inverter Initializing Inverter stuck in this mode Inverter is...

Страница 36: ...itch ON Test AC line for THD Multiple inverters turn one off Impedance matching adjustment or box Internal damage Wire came loose in shipping INI PRO Initialization Protection Master and Slave DSP hav...

Страница 37: ...Ue 1500V DC In 315A Icu 20KA Type II In 20KA Imax 40KA Up 5 0KV Uc 1500V LM PVSZ CV G20 Manufactured by LONGMAX Monitor Bus voltage current of per string power status of SPD output DC MCCB status on...

Страница 38: ...ompleted Record V AC in Notes 10 Grounding cable Good Poor INSTALLATION Check inverter condition after unpacking Install inverter mounting bracket according to installation instructions in user manual...

Страница 39: ...cable to the communication port 1 Switch the grid supply main Switch AC ON rst 2 Switch the DC switch ON If the voltages of PV arrays are higher than start up voltage the inverter will turn on The re...

Страница 40: ...eted Record address in Notes 7 Machine version For maintenance and reference please record the irmware revisions if applicable Completed Record with serial numbers 8 Operating parameter Record operati...

Страница 41: ...ting tilt Output power Input DC voltage Insulation limit K PV start up voltage Grid V Max V Min Frequency Max Min Reactive compensation PF Coniguration MPPT Individual MPPT Parallel Monitoring RS485 E...

Страница 42: ...to inverter site selection and installation 3 PHASE STRING INVERTERS KTL SERIES CSIF ST 016 A 0 INSTALLER S NAME INSTALLER S SIGNATURE COMPANY DATE Inverter serial numbers 1 2 3 4 5 6 7 8 9 10 11 12 1...

Отзывы: