37
7)
Press the reset button on the ignition control within the alotted time
Master Boiler
8)
Press
and
9)
Press
[Lead Lag Master Configuration]
10)
Press
[Advanced Settings >]
11)
Press the to arrive at
Outdoor Reset
12)
Select
Enable: Enabled
13)
Select
Maximum outdoor temperature
(WWSD)
14)
Select
Minimum outdoor temperature
(Outdoor Design)
15)
Select
Low Water Temperature
(Min. Water Temp)
16)
Select
Outdoor boost maximum off point
(Design Max.)
17)
Press
[Show Line]
to confirm reset curve
18)
Press the to arrive at
Warm Weather Shutdown
19)
Select
Enable = Shutdown after demand ends
Содержание DRH300