39
rate (80%).
Adjust staging of boilers
Description
Electrical Connection(s)
Programming Instructions
•
Upon a call for heat the lead
boiler will fire up to the
specified base load rate
(80%). If the temperature is
not within Error threshold
(5
o
F) of setpoint after
Interstage delay (2 minutes) a
lag boiler will be brought
online and will also fire up to
the base load rate specified.
•
This method will then be
repeated for the next lag
boiler, if available.
1)
Press
and
2)
Press
[Lead Lag Master Configuration]
3)
Press
[Advanced Settings >]
4)
Press the to arrive at
Add Stage
5)
Select
Error threshold
6)
Select
Interstage delay