Camus Hydronics DFH1100 Скачать руководство пользователя страница 54

 

 

49 

 

10.6.1 

RE-INSTALLING THE IGNITER 

 

Confirm that the end of the replacement igniter has a 
bead of silicone sealing the gap between the metal 
mounting flange and the ceramic shaft of the igniter. 

 

Carefully insert the igniter into the mounting point on 
the burner flange and push into position on top of the 
fan’s flange. The word ‘OUTSIDE’ on igniter faces you 
when inserting igniter. 

 

Reinstall the two mounting head screws and tighten by 
hand only. 

 

Ensure that the igniter ceramic paper gaskets are 
properly installed and seal the point of contact between 
the igniter and fan mounting flange. 

 

Reconnect the power leads to the igniter.  

 

Turn on main gas supply.  

 

Turn on main power.  

 

Test fire the appliance to ensure proper operation. 

 

The igniter must generate 3A to reliably prove the 
ignition system. 

10.7 

PRIMARY HEAT EXCHANGER 
INSPECTION 

 

The primary heat exchanger should be inspected at the 
time of burner maintenance. 

 

Turn off all power to the appliance. 

 

Turn off main gas to the appliance. 

 

Remove top cover. 

 

Remove fan assembly and burner as detailed in the 
Burner and Cleaning section. 

 

Check the heat exchanger surface for soot. If soot is 
present, heat exchanger must be cleaned and problem 
corrected. 

 

Remove the front outer jacket door. 

 

Remove the front inner jacket door. 

 

Check “V” baffles on the exchanger. 

 

Use detergent water pressure wash to remove soot 
from heat exchanger and surfaces of the inner 
chamber. 

 

When necessary, the heat exchanger can be removed 
by disconnecting all water piping and removing the 
eight flange mounting bolts at the rear of the appliance. 
The heat exchanger can now be removed from the 
front of the appliance. 

 

Reinstall inner jacket door. Replace any damaged 
gaskets to ensure a proper air seal. 

 

Reinstall the burner and fan assembly. 

 

Reassemble all gas and water piping. Test for gas 
leaks.  

 

Reassemble outer jacket panels. Keep top cover off. 

 

Cycle unit and check for proper operation. 

 

Once proper operation is confirmed replace the top 
cover. 

10.8 

CONDENSING HEAT RECOVERY 
MODULE (CHRM) INSPECTION 

 

Inspect the CHRM annually. 

 

Turn off all power to the appliance.  

 

Turn off main gas to appliance.  

 

Remove the top cover, front and right side outer 
panels.  

 

Remove the CHRM access cover.  

 

Pressure wash the heat exchanger. Use a soft bristle 
brush to remove any remaining deposits. If necessary 

the heat exchanger can be removed by disconnecting 
all water piping and lifting it out from the side.  

10.9 

RE-INSTALL HEAT EXCHANGERS 

 

Carefully reinstall the heat exchanger if removed from 
the appliance. 

 

Check all gaskets and replace if damaged. 

 

Replace heat exchanger cover. 

 

Reassemble outer jacket panels. 

 

Cycle unit and check for proper operation. 

 

Replace the top cover 

10.10  COMBUSTION AIR FAN 

Combustion air fan should be checked every 6 months. 
Clean internal filter to fan as required when installed in a 
dust or dirt contaminated location. See Combustion Air Fan 
in the component section for cleaning procedure. The motor 
and bearings on the combustion air fan are sealed and 
permanently lubricated requiring no addition of oil or 
lubricants. 

10.11  COMBUSTION AND VENTILATION AIR 

Check frequently to be sure that the flow of combustion and 
ventilation air to the appliance is not obstructed. 
Combustion and ventilation air must be provided to the 
mechanical room with openings sized per the requirements 
of the B149 or National Fuel Gas Code. The optional 
outdoor air kit brings combustion air from the outdoors 
directly to the appliance. 

10.12  CONTROL CIRCUIT VOLTAGE 

This appliance uses a transformer to supply a low voltage 
control circuit. The voltage on the secondary side should be 
24 to 28VAC when measured with a voltmeter. A secondary 
voltage of 21VAC or less supplied to 24VAC components 
may cause operational problems. A 4A circuit breaker is 
provided on the secondary side of the transformer. The 
circuit breaker is located on the front control panel. A 
tripped circuit breaker indicates a short in the 24VAC 
controls and must be corrected.  

10.13  COMBUSTIBLE MATERIALS 

CAUTION 

Keep appliance clear from combustible materials; do not 
store GASOLINE and other flammable vapors and liquids 
in the proximity of the appliance. 

10.14  FREEZE PROTECTION 

Installations are not recommended in areas where the 
danger of freezing exists. Proper freeze protection must be 
provided for appliances installed outdoors, in unheated 
mechanical rooms or where temperatures may drop to the 
freezing point or lower. If freeze protection is not provided 
for the system, a low ambient temperature alarm is 
recommended for the mechanical room. Damage to the 
appliance by freezing is non-warrantable.  

 

Location - Heating boilers, hot water supply boilers or 
water heaters must be located in a room having a 
temperature of at least 50ºF (10ºC) 

 

Caution - A mechanical room operating under a 
negative pressure may experience a downdraft in the 
flue of an appliance that is not firing. The cold outside 
air may be pulled down the flue and freeze a heat 
exchanger. This condition must be corrected to provide 

Содержание DFH1100

Страница 1: ...property damage personal injury or death Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS o Do not try to...

Страница 2: ......

Страница 3: ...INLET AND VENT CAPS 10 2 1 9 AIR INLET DAMPER 10 2 1 10 MASONARY CHIMNEY INSULATIONS 10 2 1 11 VERTICAL VENTING TERMINATION 10 2 1 12 COMBINED COMBUSTION AIR INLET 10 2 1 13 DRAIN TEE 11 2 2 CONVENTI...

Страница 4: ...CY DRIVE VFD 29 6 3 DYNAFLAME CONTROL PANEL 30 6 4 GENERAL SYMBOL DESCRIPTION 30 6 5 MODE 1 2 SETPOINT OPERATION VIEW DISPLAY 31 6 6 MODE 1 2 SETPOINT OPERATION ADJUST DISPLAY 32 6 7 MODE 3 DEDICATED...

Страница 5: ...BUSTION AND VENTILATION AIR 49 10 12 CONTROL CIRCUIT VOLTAGE 49 10 13 COMBUSTIBLE MATERIALS 49 10 14 FREEZE PROTECTION 49 10 15 FREEZE PROTECTION FOR A HEATING BOILER SYSTEM Optional 50 PART 11 INSTAL...

Страница 6: ...ise proportion 1 1 Ratio to modulation signal allowing combustion characteristics which determine efficiency to remain the same over entire operating range DynaFlame Non Condensing In this series most...

Страница 7: ...ntarily light up during ignition trials If appliance fails to start the fan will shut down the air flow light will light up and the flame failure light will stay on continuously On a call for heat any...

Страница 8: ...urner surface The A reading can be conveniently taken at the front of the ignition module at the Flame Sense Test terminals 1 5 1 IGNITION PROCESS 1 The Ignition module supplies voltage to the Air Gas...

Страница 9: ...shall apply only when the appliance is installed in accordance with local plumbing and building codes ordinances and regulations the printed instructions provided with it and good industry practices...

Страница 10: ...kets a high temperature ceramic paper gasket under the burner flange and a stamped silicon gasket between the burner flange and fan flange Tighten fan flange mounting nuts to 20 ft lb 6 Restore electr...

Страница 11: ...nces is the manufacturer to be held responsible for water damage in connection with this unit or any of its components If the appliance is installed above the level of the building s radiation system...

Страница 12: ...7 Table 4 Appliance Dimensions and Specifications Table 5 Vent Sizes for a Single Appliance...

Страница 13: ...le codes All connections should be secured and sealed per the vent manufacturers specifications When a Positive vent system is disconnected for any reason the flue must be reassembled and resealed acc...

Страница 14: ...uired when operating appliance at low fire for long periods 3 C Vent 4 Equivalent or higher rated than above Exhaust Vent for Use for DynaFlame Non condensing Category lll Installations 1 Corrosion re...

Страница 15: ...e or negative pressure appliance Category II or IV If a masonry chimney is to be used the chimney MUST use a sealed metallic corrosion resistant liner system to vent flue products from this high effic...

Страница 16: ...w temperature and is being run for extended periods of time at low fire it is likely that condensation will be formed in the vent Consideration must be given to heating the room or providing a special...

Страница 17: ...to the elements The additional protection afforded by the shelter will help to minimize nuisance problems with electrical connections and will allow easier servicing of the appliance under severe wea...

Страница 18: ...minimum of 3 feet 1M horizontally and 12 inches 0 30M below the point of flue gas termination vent cap if it is located within a 10 foot 3M radius of the flue outlet 2 4 4 LENGTH OF AIR INLET PIPE Th...

Страница 19: ...ifferential air pressures are noted at full firing rate There are two pressure taps at the fan discharge and care must be taken to tee into the correct line The correct line may be identified by traci...

Страница 20: ...models 3000 and above be supplied with no more than 9 W C supply pressure This means that lockup pressure must not exceed 9 W C A suitable lockup regulator will not exceed running pressure by more tha...

Страница 21: ...The optional gas pressure switches may be provided with threaded termination points to be vented to the atmosphere outside the building The gas pressure regulation function is provided by the ratio ga...

Страница 22: ...gnition system components are protected from water dripping spraying rain etc during appliance operation and service circulator replacement control replacement etc Figure 12 Typical Space Heating Syst...

Страница 23: ...a cold system some condensation will be generated but it will be quickly evaporated once the system return temperature reaches 115 F 46 C Return Water Temperatures Required for Dynaflame Boilers Water...

Страница 24: ...nner jacket chamber at the right side of the appliance facing the appliance The CHRM is constructed from all stainless steel headers and special multiple horizontal stainless tubes This CHRM is design...

Страница 25: ...provide an extractor at the chimney outlet in order to maintain a negative draft in the chimney and allow common venting The chimney must be protected from down drafts rain and debris by using a list...

Страница 26: ...0 F 44 C it will not condense fully and therefore the CHRM will not perform to its maximum efficiency capacity If water colder than 110 F 44 C is available it can be fed to the CHRM WATER HEATER APPLI...

Страница 27: ...om the local modulating control or a remote source based on water temperature to vary the frequency of the voltage supplied to the fan motor from 20 Hz up to 60 Hz This varies the output of the combus...

Страница 28: ...5 6 1 SERVICE PARTS This appliance uses a proved electronic ignition control module and a hot surface igniter The electronic ignition module is not repairable Any modification or repairs will invalid...

Страница 29: ...se emery paper since the silica will foul the sensor surface PART 6 CONTROL PANEL 6 1 APPLIANCE TEMPERATURE CONTROLLER The appliance is provided with a control panel at the front Operating controls ar...

Страница 30: ...r pool heating Intermittent pumping provided Mode 3 For DHW control with tank sensor Controls to boiler inlet sensor Intermittent pumping provided Mode 4 For hydronic heating with outdoor reset Temper...

Страница 31: ...ature immersion well within the DHW tank to function properly The BTC 1 modulates the boiler based on the boiler inlet sensor to maintain a tank temperature at the DHW sensor An internal heat demand i...

Страница 32: ...tinues to circulate until the PUMP DELAY timer expires In this case it is imperative that the system pump operates continuously in order to provide constant circulation past the system sensor The wate...

Страница 33: ...eset limit is set to 210 o F and is fixed In addition to the auto reset limit Camus installs a manual reset limit set to 250 o F Figure 30 Mode 7 Piping Electrical Layout Mode 8 External Direct Drive...

Страница 34: ...High Low Voltage Input Voltage 120 220 240 460 480 01 02 2 Carrier Frequency 03 4 Stop Method 03 5 Standard Speed Source 04 03 for 2 10 VDC 19 Acceleration Time 120 sec 20 Deceleration Time 60 sec 28...

Страница 35: ...ease of startup and serviceability 6 4 GENERAL SYMBOL DESCRIPTION SYMBOL SYMBOL NAME SYMBOL DESCRIPTION Boiler Pump Shown when boiler pump is in operation DHW Pump Shown when DHW pump is in operation...

Страница 36: ...Outlet Temperature Real time Outlet Temperature to Boiler 14 to 266 o F 10 to 130 o C Boiler Inlet Temperature Real time Inlet Temperature to Boiler 14 to 266 o F 10 to 130 o C Boiler Delta T Real tim...

Страница 37: ...etpoint for the heating system Setpoint is controlled to the inlet sensor 70 to 220 o F 21 to 104 o C Default 120 o F 49 o C Differential Temperature To provide a modulation rate above and below the B...

Страница 38: ...r Inlet Temperature Real time Inlet Temperature to Boiler 14 to 266 o F 10 to 130 o C Boiler Delta T Real time temperature difference between the outlet sensor and the inlet sensor 99 to 252 o F 72 to...

Страница 39: ...trolled to the DHW sensor OFF 70 to 190 o F OFF 21 to 88 o C Default 140 o F 54 o C DHW Differential To provide a modulation rate above and below the DHW Target Temperature For example if the value is...

Страница 40: ...lable in Mode 5 14 to 266 o F 10 to 130 o C Boiler Outlet Temperature Real time Outlet Temperature 14 to 266 o F 10 to 130 o C Boiler Inlet Temperature Real time Inlet Temperature 14 to 266 o F 10 to...

Страница 41: ...reset ratio calculation for the heating system Typically set to the desired building temperature 35 to 150 o F 2 to 66 o C Default 70 o F 21 o C Boiler Design Temperature Boiler design water temperatu...

Страница 42: ...C Boiler Outlet Temperature Real time Outlet Temperature to Boiler 14 to 266 o F 10 to 130 o C Boiler Inlet Temperature Real time Inlet Temperature to Boiler 14 to 266 o F 10 to 130 o C Boiler Delta...

Страница 43: ...Modes of Operation in this manual 1 to 8 Default 1 Differential Temperature To provide a modulation rate above and below the Boiler Target temperature For example if the value is 10 o F and the Boile...

Страница 44: ...e to Boiler 14 to 266 o F 10 to 130 o C Boiler Delta T Real time temperature difference between the outlet sensor and the inlet sensor 99 to 252 o F 72 to 122 o C Modulation Real time modulating outpu...

Страница 45: ...will stop operation until all settings in the Adjust menu have been checked by the installer Outlet Sensor Short Circuit If the inlet sensor is operational the control will operate using the inlet sen...

Страница 46: ...nd related wiring The error message will clear once the error condition is corrected and a button is pressed Outdoor Sensor Short Circuit The BTC assumes an outdoor temperature of 32 o F 0 o C and con...

Страница 47: ...rod must be removed with steel wool Do not use sand paper since this will contaminate the surface 7 3 COMBUSTION AIR FAN Figure 36 Fan Burner Hot Surface Igniter and Flame Sensor Arrangement DynaFlame...

Страница 48: ...in lit If ignition is not accomplished the red flame failure light will energize and two more ignition trials will be made 15 seconds apart The control will then proceed to lockout and must be reset b...

Страница 49: ...rol to the IN temperature display Remove fan inlet filter During trial for ignition block 50 of the fan inlet opening The air flow light should de energize If it does not slowly turn the adjustment on...

Страница 50: ...ion Light Turns On Check for boiler demand No Demand STEP 4 STEP 5 STEP 6 NO YES NO YES YES NO NO YES Light Burnt Out Replace PCB YES High Limit Light Turns On YES Check Manual Reset if equipped Check...

Страница 51: ...Check for gas tightness at fittings on Low Gas High Gas connections at actuator Check flame sensor for cracks in the insulator or continuity to ground Check for incoming gas pressure Adjust the air pr...

Страница 52: ...ply of combustion and ventilation air 10 3 FLUE GAS PASSAGEWAYS CLEANING PROCEDURES Any sign of soot around the inner jacket outer jacket flue pipe connections burner or in the areas between the fins...

Страница 53: ...g tubes from the air ratio gas valve to the combustion air fan Remove the 4 nuts holding the fan assembly to the heat exchanger and remove the fan assembly On occasion the red silicone gasket may adhe...

Страница 54: ...m the side 10 9 RE INSTALL HEAT EXCHANGERS Carefully reinstall the heat exchanger if removed from the appliance Check all gaskets and replace if damaged Replace heat exchanger cover Reassemble outer j...

Страница 55: ...so have a properly sized expansion tank installed Typically an air charged diaphragm type expansion tank is used The expansion tank must be installed close to the boiler and on the suction side of the...

Страница 56: ...been used to maintain the temperature rise across the appliance confirm that the recommended flow for pure water has been increased by 15 and the head loss by 20 4 Turn on power to the primary system...

Страница 57: ...t be properly adjusted to achieve the specified flow rate The required temperature rise and the recommended pump size are based on the heating of potable water with a hardness of 7 5 to 17 0 grains pe...

Страница 58: ...53 PART 12 EXPLODED VIEW...

Страница 59: ...54...

Страница 60: ...55...

Страница 61: ...et Right Panel 14 6012 X X X X 14 5223 X X X X X X X X X 14 5323 X X X 7 Flue Outlet Transition 14 5290 X 8 Flue Conduit 14 5014 X X X X 14 5208 X X X X X X X X X 14 5308 X X X 9 Vent Transition Disk...

Страница 62: ...X 14 5331 X X X 23 Secondary Heat Exchanger Cover 14 5270 X 26 Electrical Box 14 0263 X 27 Vee Baffle Sets 14 6035 X X X X 14 0354 X X X X X X X X X 14 5314 X X X 28 Outer Jacket Top Wrap 14 6031 X X...

Страница 63: ...X 45 White Ceramic Gasket Under Burner Flange 33 0023 X X X X 33 0024 X X X X 33 0022 X X X X X 33 0035 X X X 46 Main Burner 500 BRN X 750 BRN X 1100 BRN X 1200 BRN X 1500 BRN X 1750 BRN X 2000 BRN X...

Страница 64: ...X GFH 5000 CH X X X GFH 6000 CH X 54 Fan Intake Filter GFIF 500 CH X GFIF 750 CH X GFIF 1100 CH X GFIF 1200 CH X GFIF 1500 CH X GFIF 1750 CH X GFIF 2000 CH X GFIF 2500 CH X GFIF 3000 CH X GFIF 3500 C...

Страница 65: ...izes ALL 500 750 1100 1200 1500 1750 2000 2500 3000 3500 4000 4500 5000 4504 5004 6004 60 Variable Frequency Drive 1 2HP 1HP 1 1 2HP 3HP 5HP SM005S X X X X SM010S X X X SM015S X X SM230S X X X X X X S...

Страница 66: ...61 PART 13 ELECTRICAL DIAGRAMS...

Страница 67: ...62...

Страница 68: ...63 Camus DynaFlame PCB Electrical Ladder Diagram...

Страница 69: ...ten replacement purchase price pro rated at the following schedule Year six 60 Year seven 65 Year eight 70 Year nine 75 Year ten 80 of the current list price of the current list price This term is red...

Страница 70: ...uilt water heaters and heating boilers as well as a into every single unit For more information supplier of specialty HVAC products Our service line is open 24 hours 7 days a week on our innovative pr...

Отзывы: