32
6.6
MODE 1 & 2: SETPOINT OPERATION: ADJUST DISPLAY
From the Home display;
1) Press
simultaneously to view the following parameters:
Display
Parameter
Name
Parameter Description
Parameter
Range
Mode
Operating mode for the boiler.
NOTE: A complete description of
each mode can be found in
section 8.4 Modes of Operation in
this manual.
1 to 8
Default = 1
Boiler Target
Temperature
To provide a target setpoint for
the heating system. Setpoint is
controlled to the inlet sensor
70 to 220
o
F
(21 to 104
o
C)
Default = 120
o
F
(49
o
C)
Differential
Temperature
To provide a modulation rate
above and below the Boiler
Target temperature. For example,
if the value is 10
o
F and the Boiler
Target is 160
o
F the boiler will
begin to modulate at 155
o
F and
shut off at 165
o
F.
Au, 2 to 42
o
F
(Au, -17 to 6
o
C)
Default = Au
Pump Delay
Boiler post pump time after
burner has shut off, in seconds.
OFF, 0:20 to
9:55 min, On
Default = 1:00
min
Temperature
Units
Select the desired unit of
measurement
o
F,
o
C
Default =
o
F
Содержание DFH1100
Страница 2: ......
Страница 12: ...7 Table 4 Appliance Dimensions and Specifications Table 5 Vent Sizes for a Single Appliance...
Страница 58: ...53 PART 12 EXPLODED VIEW...
Страница 59: ...54...
Страница 60: ...55...
Страница 66: ...61 PART 13 ELECTRICAL DIAGRAMS...
Страница 67: ...62...
Страница 68: ...63 Camus DynaFlame PCB Electrical Ladder Diagram...