29
6.2
VARIABLE FREQUENCY DRIVE (VFD)
The VFD has a factory set security code which has to be
entered before any adjustments can be made. The VFD
has 50 parameters, which can be adjusted. At present only
the following are pertinent:
Table 13: Variable Frequency Drive Parameters
Parameter
#
Function
Settings
1
High/Low Voltage
Input Voltage 120,
220-240, 460-480
01
02
2
Carrier Frequency
03
4
Stop Method
03
5
Standard Speed
Source
04 (03 for 2- 10
VDC)
19
Acceleration Time
120 sec
20
Deceleration Time
60 sec
28
Fixed Boost
1.0
36
Preset Speed
29
38
Skip Bandwidth
3.0
45
Speed at Minimum
Signal
•
500 - 3000 Non-
Condensing: 29
or 32
•
500 – 3000 Near-
Condensing: 20-
25
•
500 – 3000
Condensing: 25
•
3500 – 6004 All
Models: 14-18
46
Speed at Maximum
Signal
•
All Models: 60
50
Fault History
View Only
51 thru 58
Miscellaneous
View Only