PART 9
TROUBLE SHOOTING
Note: Before troubleshooting, familiarize yourself with the field startup procedure.
STEP 1 • Turn circulating pump ON.
•
Turn gas supply to the appliance ON.
•
Turn electric power to the appliance ON.
•
Set target to desired temperature and set Diff to 5
o
F
•
Turn high limit to highest setting
STEP 2 Power Lights Turns On
Check power supply to heater
Check power breaker
Light burnt out, replace
STEP 3
Operation Light Turns On
Check for boiler demand
No Demand
STEP 4
STEP 5
STEP 6
NO
YES
NO
YES
YES
NO
NO
YES
Light Burnt Out, Replace PCB
YES
High Limit Light Turns On
YES
• Check Manual ‘Reset’ if equipped
• Check water temperature
NO
Water Flow Light Turns On
NO
• Check Water Flow
• Check Flow Switch
NO
Air Flow Light Turns On
YES
•Wait for VFD to reach soft start speed
• Check vent for blockage
• Check fan operation
• Check differential pressure switch
• Check optional Low/High gas pressure switches
NO
STEP 7 Ignition Trial Lights Turns On
YES
Check for glow on igniter
NO
• Check igniter for damage
• Check ignition control wiring
YES
Next Page
Содержание DFH1100
Страница 2: ......
Страница 12: ...7 Table 4 Appliance Dimensions and Specifications Table 5 Vent Sizes for a Single Appliance...
Страница 58: ...53 PART 12 EXPLODED VIEW...
Страница 59: ...54...
Страница 60: ...55...
Страница 66: ...61 PART 13 ELECTRICAL DIAGRAMS...
Страница 67: ...62...
Страница 68: ...63 Camus DynaFlame PCB Electrical Ladder Diagram...