HSEUiREG07201(R2) MANUAL

                 

Camtec Power Supplies GmbH  -  Gewerbestrasse 30  -  DE-76327  Pfinztal / Germany   

P.8/15 (03/2017.02.2) 

Tel. +49 (721) 46596 - 0  Fax +49 (721) 46596 - 77    

www.camtec-gmbh.com

   -   

[email protected]

 

(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death) 

 

Compensation Load Line Voltage Drop (Sense ++/--) battery charger operation mode 

Remote Sensing as a battery charger 

If the HSEUiREG power supply unit is used as a battery charger, it is recommended to refrain from sensing. It 
can lead to severe damage to the power supply, if the polarity of the sense line is confused (field experience: 
such error often occurs when system service is required, e.g., when the batteries are changed). If it is 
necessary to use sensing, proceed as described in the figure below. Proven approaches are 250mA for the 
fuses and 3...5A load capacity of diodes. 

WARNING!

 Reverse polarity of the sense lines can cause damages to the power supply unit. 

 
 
 
 
 
 
 

 

External Shutdown (SD)

 

The power supply is set to the Shutdown mode, when the 
control input is either shorted via a relay contact, a switch 
contact or an NPN transistor with open collector (voltage drop 
<1V, current typ. 2mA).  
 
If the shutdown repeals the power supply starts again. 
 
Using the soft-start, the current and the voltage rises within 
continuously to the default set values.  
 
 
 
 
 

 

Power-OK Relay (DC Power Good)

 

The alarm signal DC OK has potential-free relay contacts. The contacts are closed (relay 
coil is energized) when the power output is active. In shut dwon mode (SD) the contacts 
are closed.  
The contacts are open when the power output is inhibited by OT or low AC supply voltage 
at the AC inputs. Contact load (resistive load): 30Vdc/1A, 60Vdc/0.3A, 30Vac/0.5A.  
 
 
 

 

Over Voltage Protection (OVP)

 

If an over-voltage occurs to the output (for example, defective components, external feed voltage), it is followed 
by the shutdown of the power output. A periodic restart attempts (ticker operation period 400ms). 

 

Over Temperature Shutdown (OT)

 

The alarm LED OT lits when the temperature of the power supply is higher than the over-temperature 
protection threshold. 

 
 
 

 
 

Содержание HSEUiREG07201.060

Страница 1: ...ring Reference voltage f autonomous programming Remote Shutdown Sense control 2V per load line Power Good Relay DC ok Quick down programming option PS Precise dynamics on load change Series parallel o...

Страница 2: ...sembled device pass stress aging to achieve an even level and to prevent from delayed failures Our internal product engineering guidelines provide a clear target Camtec product reputation must say mou...

Страница 3: ...It is the exact and real value at the output terminals The latency signal preset to the measured value is negligible since the control circuit is constructed completely analogously Constant Voltage or...

Страница 4: ...ed yes Base Load OCP Non required open circuit protected Load Regulation Time 1ms on load switch 10 100 Accuracy Ureg 0 5 Ireg 1 5 Umon 0 5 Imon 1 5 Uref 1 0 Temperature Control yes thermal shutdown a...

Страница 5: ...2 Ureg Input 3 Ireg Input Current Programming Select 0 5V 0 10V 0 20mA 4 20mA 1 M working resistance with Vprog 500 working resistance with Iprog 4 Ireg Input 5 Umon Output Voltage Monitor Select 0 5...

Страница 6: ...bh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death Monitor Outputs Moni...

Страница 7: ...desired set point may be very long The power supply has large built in capacitors and an enormous energy reserve A similar effect occurs by skidding input energy which is not easily removed from the p...

Страница 8: ...nes can cause damages to the power supply unit External Shutdown SD The power supply is set to the Shutdown mode when the control input is either shorted via a relay contact a switch contact or an NPN...

Страница 9: ...W HSEUiREG07201 240 240Vdc 3 0A 190Vdc 3 8A 720 722W Inrush Current Protection electronic The power supply unit has an electronic current limiter 230Vac 9 8Arms 13 8Apeak It is a precisely working cir...

Страница 10: ...ors select the line length from the neutral point or from the busbar to the load as short as possible and use the maximum possible conductor cross section Up to 5 pcs HSEUiREG can be paralleled The HS...

Страница 11: ...ncrease The following formula shows dv dt i C When an electronic current sink is used the output voltage remains constant at the set value The current sink provides a quick dynamic response Fig 1 Fig...

Страница 12: ...n a failure or malfunction could result in injury or death Mechanics ST HD Baseplate Cooling Temperature Management The temperature management of the HSEUiREG series provides a direct dissipation of t...

Страница 13: ...ired and for active devices 15mm space from the sidewalls For proper air convection it is necessary to install the HSEUiREG One can use the DIN Rail installation equiped standard with our patented 35m...

Страница 14: ...5mm H2 5 12 12mm H2 5 19D BL 14mm 4 0mm H4 0 12 12mm H4 0 20 GDR 14mm 6 0mm H6 0 20 12mm H6 0 20 SW 14mm 10 0mm H10 0 12 12mm H10 0 22 EB 15mm The length of ferrules is to be chosen depending on the...

Страница 15: ...tion outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or thing...

Отзывы: