TROUBLESHOOTING  

 

 

NOTE: 

Before  replacing  any  component,  test  according  to  instructions  in  this  manual.    This 

trouble  shooting  guide  will  say  replace,  but  replacement  should  occur  only  after  appropriate 
testing.  

TROUBLESHOOTING DF2500 DIRECT FIRED HEATER 

 

PROBLEM 

 

CONDITION 

 

REMEDY 

 

Blower Motor does not 
run. (Blower mode) 

 

  

  
  

  

1. No current to heater.  

1. Turn breaker 

– safety switch 

ON.  

2. Voltage insufficient  

2. Check incoming supply.   

3. Wiring 

– connections 

disconnected 

– loose – 

broken.  

3. Connect 

– tighten – replace 

wiring connections.   

4. Main Switch OFF 

– Defective.   4. Turn Control toggle Switch 

ON 

– replace Switch.  

 

5. Defective VFD. 

5. Check to see if there is power 

to the VFD. 

Burner does not ignite.

  

  

  

  

  

  

  

  

1. Voltage insufficient.  

1. Check incoming supply.  

2. Electrode 

– disconnected – 

adjusted incorrectly 

– 

defective.  

2. Connect 

– adjust - replace 

electrode.  

3. Air Proving Sw.  

Disconnected 

– defective.  

3. Connect 

– Replace Air 

Proving Sw.  

4.Tilt switch Disconnected, or 

Unit is not on a level surface or 
defective. 

4. Connect

—Replace Tilt Switch 

or Level the Unit.  

5.Fan Over heat switch is open. 

5. Check to see if the unit is not 

running on low voltage or fan 
is not over heating. 

6. Overheat light is on. 

6. Press the overheat reset push 

button.   

7. Insufficient Gas delivery.  

7. Fill tank 

– open valves – 

replace solenoid valves.   

8. Regulators adjusted incorrectly 

– defective.  

8. Adjust 

– replace regulators.  

9. Burner gas ports 

– obstructed 

– damaged.  

9. Clean ports 

– replace burner.  

10. Flame sensor 

– damaged – 

defective.  

10. Replace Flame Sensor.  

Burner stops during 
usage.

  

1.  Heater overheating.  

1. Check to see if modulating 
valve is not stuck.  

2. Power interrupted.  

2. Restore power.  

Содержание ECOBlaze DF2500

Страница 1: ...com pg 1 NG LP DIRECT FIRED SPACE HEATER BLAZE DF2500 WWW CAMPOEQUIPMENT COM REPORT 0367GH009S Installation Instructions Manual Maintenance Parts List CAUTION DO NOT TAMPER WITH HEATER OR ITS CONTROLS...

Страница 2: ...remain with the heater GENERAL HAZARD WARNING FAILURE TO COMPLY WITH THE PRE CAUTIONS AND INSTRUCTIONS PROVIDED WITH THIS HEATER CAN RESULT IN DEATH SERIOUS BODILY INJURY AND PROPERTY LOSS OR DAMAGE...

Страница 3: ...able to any subsequent owner The warranty period is one year from the date of purchase The warranty covers all defects in material and workmanship insofar as they are of Campo Equipment CO LTD manufac...

Страница 4: ...the material flash point Under no circumstance should any combustible material be stored in the airstream within 15 feet 4 57 m of the air discharge port or within 6 15 2cm of the top sides or ends of...

Страница 5: ...ter Use Sherlock 5 second leak of the proper temperature or soapy water on all connections to be sure they are tight Replace or tighten any connection as necessary The supply gas hose being used must...

Страница 6: ...Phase 208 to 240 V supply must be available INSTALLATION Single Phase Three Phase Up to 100 3 6 Up to 100 4 8 Up to 200 3 4 Up to 200 4 6 Up to 300 3 3 Up to 300 4 4 NOTE To power up the heater inside...

Страница 7: ...re is adequate 2 Check to make sure all manual valves are open between the fuel source and the burner 3 Check to make sure the proper voltage is supplied to the heater WARNING A qualified electrician...

Страница 8: ...ndent upon ambient air conditions Excessive pressure build up could occur in the supply line and lead to line failure Consult your local gas supplier for proper piping and gas codes When storing the h...

Страница 9: ...ch gas can pass through the modulator The more voltage that is applied to the magnet the more gas that can pass through The modulator is typically full open when a voltage of about 24 volts DC is appl...

Страница 10: ...f any mixing plates are loose or missing fasteners tighten replace as necessary Always use zinc plated or stainless fasteners 3 Observe flame pattern and if necessary take steps to correct obstructed...

Страница 11: ...The following is the method for testing major electrical components WARNING A qualified electrician should perform all tests replacements and adjustments Testing the Main Switch Before assuming the C...

Страница 12: ...he switch is functioning disconnect and insulate wires leading to the switch N O contacts Connect an ohmmeter or continuity light to the switch N O contacts Place the Heat Fan switch to FAN position T...

Страница 13: ...s power to the VFD Burner does not ignite 1 Voltage insufficient 1 Check incoming supply 2 Electrode disconnected adjusted incorrectly defective 2 Connect adjust replace electrode 3 Air Proving Sw Dis...

Страница 14: ...ctive 4 Replace Air Proving Sw 5 Flame rod dirty defective 5 Clean Replace Flame Rod 6 Inadequate fuel delivery 6 Fill Tank replace regulators valves check gas lines for obstructions TROUBLESHOOTING D...

Страница 15: ...CAMPO EQUIPMENT CO LTD ECOBLAZE 6 Carson Court Brampton ON CANADA L6T 4P8 Tel 905 793 2525 Fax 905 793 8768 www campoequipment com pg 15 WIRING DIAGRAM...

Страница 16: ...89 Digital Panel Mounted Voltmeter C70064 3 POSITION SWITCH C70069 FIXING COLLAR C70067 N O CONTACT BLOCK C80025 VFD C80023 R Fan C90025 Power On Indicator Light GREEN C90029 Outlet for Plug C70052 TI...

Страница 17: ...C82119 2 X21 2 NIPPLE C82120 2 X90 STREET ELBOW C82121 2 X11 2 REDUCER C82122 11 2 X6 NIPPLE C82123 11 2 X90 ELBOW C82124 11 2 X2 NIPPLE C82125 2 UNION C82126 1 4 X11 2 L NIPPLE C80913 1 4 NPT x 1 4...

Страница 18: ...ASSY C82191 PANEL C82192 PANEL C82193 ADAPTER PLATE C82194 R 560 FAN MOUNT ASSY C82195 CORNER STOP C82196 FAN SUPPORT BRACKET C82197 INSULATION BACK PANEL C82087 Serial Number variable data C82088 War...

Страница 19: ...P8 Tel 905 793 2525 Fax 905 793 8768 www campoequipment com pg 19 C82086 E 560 FAN MOUNT ASSY C82105 15 KVA TRANSFORMER C82106 60A CONTACTORS C50242 AUXILIARY CONTACTS C82042 VSR Relay C60205 Use With...

Отзывы: