Testing Air Pressure Differential Switch  

  

The  DF2500  uses  an  air  pressure  differential 

switch  to  confirm  that  the  main  blower  is 
moving enough air through the heater.   

This switch must be activated before the burner 

will  ignite.  The  switch  senses  the  difference 
between the velocity developed by the blower.  

Any  restrictions  beyond  the  set  point limit 
of  the  switch  to  the  inlet  of  the  heater  will 
cause  the  switch  to  open  and  shut  the 
burner  off

.  All  discharge  duct  work  must  be 

removed before testing the switch.  
1.  Check  the  sensing  tube  from  the  "HIGH" 

port  on  the  switch  body  to  the  port  right 
under the  switch  for  kinks  or  obstructions.  
Insure the sensing line is connected to the 
switch.  The  “HIGH”  port  sensing  tube  is 
located  perpendicular  and  facing  into  the 
air stream.  

2.  To  test  if  the  switch  is  functioning, 

disconnect and insulate wires leading to the 
switch 

N.O. 

contacts. 

Connect 

an 

ohmmeter  or  continuity  light  to  the  switch 
N.O. contacts. Place the Heat/Fan switch to 
“FAN” position. The ohmmeter should read 
low resistance or the continuity light should 
come on. When the blower is stopped the 
light  should  go  out  and  the  resistance 
reading  should  be  high.  If  the  contacts 
remain  closed  regardless  of  the  blower 
status,  the  air  switch  must  be  replaced. 

Contact  the  factory  in  the  event  the 
switch  must  be  replaced

Only  factory 

authorized  personnel  can  replace  and 
calibrate the air switch.   

 

 

 

Testing High Limit Switch  

  

The  High  limit  switch  is  a  solid-state  device. 
When  the  output  contacts  are  operating 
properly, the limit switch will allow the heater to 
run when the  Heat/Fan switch is placed in the 
“Heat” position, as long as the air temperature 
at the limit sensor is b

elow the “HIGH LIMIT that 

is  150°F

”.  Once  the  temperature  rises  above 

150°F, limit switch will open and cut the power 
to  the  burner.  A  manual  reset  push  button 

located  on  the  control  panel  needs  to  be 
pressed to restore the power to the burner.  

Содержание ECOBlaze DF2500

Страница 1: ...com pg 1 NG LP DIRECT FIRED SPACE HEATER BLAZE DF2500 WWW CAMPOEQUIPMENT COM REPORT 0367GH009S Installation Instructions Manual Maintenance Parts List CAUTION DO NOT TAMPER WITH HEATER OR ITS CONTROLS...

Страница 2: ...remain with the heater GENERAL HAZARD WARNING FAILURE TO COMPLY WITH THE PRE CAUTIONS AND INSTRUCTIONS PROVIDED WITH THIS HEATER CAN RESULT IN DEATH SERIOUS BODILY INJURY AND PROPERTY LOSS OR DAMAGE...

Страница 3: ...able to any subsequent owner The warranty period is one year from the date of purchase The warranty covers all defects in material and workmanship insofar as they are of Campo Equipment CO LTD manufac...

Страница 4: ...the material flash point Under no circumstance should any combustible material be stored in the airstream within 15 feet 4 57 m of the air discharge port or within 6 15 2cm of the top sides or ends of...

Страница 5: ...ter Use Sherlock 5 second leak of the proper temperature or soapy water on all connections to be sure they are tight Replace or tighten any connection as necessary The supply gas hose being used must...

Страница 6: ...Phase 208 to 240 V supply must be available INSTALLATION Single Phase Three Phase Up to 100 3 6 Up to 100 4 8 Up to 200 3 4 Up to 200 4 6 Up to 300 3 3 Up to 300 4 4 NOTE To power up the heater inside...

Страница 7: ...re is adequate 2 Check to make sure all manual valves are open between the fuel source and the burner 3 Check to make sure the proper voltage is supplied to the heater WARNING A qualified electrician...

Страница 8: ...ndent upon ambient air conditions Excessive pressure build up could occur in the supply line and lead to line failure Consult your local gas supplier for proper piping and gas codes When storing the h...

Страница 9: ...ch gas can pass through the modulator The more voltage that is applied to the magnet the more gas that can pass through The modulator is typically full open when a voltage of about 24 volts DC is appl...

Страница 10: ...f any mixing plates are loose or missing fasteners tighten replace as necessary Always use zinc plated or stainless fasteners 3 Observe flame pattern and if necessary take steps to correct obstructed...

Страница 11: ...The following is the method for testing major electrical components WARNING A qualified electrician should perform all tests replacements and adjustments Testing the Main Switch Before assuming the C...

Страница 12: ...he switch is functioning disconnect and insulate wires leading to the switch N O contacts Connect an ohmmeter or continuity light to the switch N O contacts Place the Heat Fan switch to FAN position T...

Страница 13: ...s power to the VFD Burner does not ignite 1 Voltage insufficient 1 Check incoming supply 2 Electrode disconnected adjusted incorrectly defective 2 Connect adjust replace electrode 3 Air Proving Sw Dis...

Страница 14: ...ctive 4 Replace Air Proving Sw 5 Flame rod dirty defective 5 Clean Replace Flame Rod 6 Inadequate fuel delivery 6 Fill Tank replace regulators valves check gas lines for obstructions TROUBLESHOOTING D...

Страница 15: ...CAMPO EQUIPMENT CO LTD ECOBLAZE 6 Carson Court Brampton ON CANADA L6T 4P8 Tel 905 793 2525 Fax 905 793 8768 www campoequipment com pg 15 WIRING DIAGRAM...

Страница 16: ...89 Digital Panel Mounted Voltmeter C70064 3 POSITION SWITCH C70069 FIXING COLLAR C70067 N O CONTACT BLOCK C80025 VFD C80023 R Fan C90025 Power On Indicator Light GREEN C90029 Outlet for Plug C70052 TI...

Страница 17: ...C82119 2 X21 2 NIPPLE C82120 2 X90 STREET ELBOW C82121 2 X11 2 REDUCER C82122 11 2 X6 NIPPLE C82123 11 2 X90 ELBOW C82124 11 2 X2 NIPPLE C82125 2 UNION C82126 1 4 X11 2 L NIPPLE C80913 1 4 NPT x 1 4...

Страница 18: ...ASSY C82191 PANEL C82192 PANEL C82193 ADAPTER PLATE C82194 R 560 FAN MOUNT ASSY C82195 CORNER STOP C82196 FAN SUPPORT BRACKET C82197 INSULATION BACK PANEL C82087 Serial Number variable data C82088 War...

Страница 19: ...P8 Tel 905 793 2525 Fax 905 793 8768 www campoequipment com pg 19 C82086 E 560 FAN MOUNT ASSY C82105 15 KVA TRANSFORMER C82106 60A CONTACTORS C50242 AUXILIARY CONTACTS C82042 VSR Relay C60205 Use With...

Отзывы: