Appendix C. EasyFlux
®
DL CR6KH20
C-8
TABLE C-7. A21REL-12 Wiring
A21REL-12 Terminal
Connecting Terminal
Cable/Wire
+12V
12V
1/
CABLEPCBL-1,
red wire
Ground
System GND
1/
CABLEPCBL-1,
black wire
CTRL 1
VOLT116 SW5V #1
CABLE3CBL-1,
red wire
CTRL 2
VOLT116 SW5V #2
CABLE3CBL-1,
black wire
CTRL 3
VOLT116 SW5V #3
CABLE3CBL-1,
white wire
The +12V terminal on the A21REL-12 needs to be in common with the REL 1 COM, REL 2
COM, and REL 3 COM terminals. To do this, use jumper wires to connect the +12V
terminal to REL 1 COM, and then REL1 COM to REL 2 COM, and finally REL2 Com to
REL 3 COM.
1/
For the A21REL-12 power connections, c12V
and G to a system or external
power supply. Do not connect to the +12V or G terminals on the CR6 or VOLT116.
TABLE C-8. CNF4 Wiring
Sensor
Quantity
Wire Description
Color
Terminal
CNF4
0 or 1,
only use
with a
CNR4
Tachometer Output
Green
CR6 U11
Tachometer
Reference
Grey
CR6
⏚
Ventilator Power
Yellow
A21REL-12
REL 1 NO
Ventilator Ground
Brown
A21REL-12
REL G
Heater #1 Power
White
A21REL-12
REL 2 NO
Heater #1 Ground
Red
A21REL-12
REL G
Heater #2 Power
Black
A21REL-12
REL 3 NO
Heater #2 Ground
Blue
A21REL-12
REL G
C.2.3.7 Precipitation Gage
EasyFlux DL CR6KH20
can support a single TE525MM tipping rain gage. The
default wiring for the precipitation gage is shown in TABLE