Section 7. Measurement Instructions
7-30
Parameter
& Data Type
Enter
SettlingTime
Constant
The time in microseconds to delay between setting up a measurement (switching to
the channel, setting the excitation) and making the measurement. (1 microsecond
resolution)
Entry
Voltage Range
Integration
Settling Time
0
± 20 mV
Flash
200 µS (default)
0
All but ± 20 mV,
Flash
100 µS (default)
0
All
250 µS
200 µS (default)
0
All
_50Hz, _60 Hz
3 mS (default)
>=100
All All µS
entered
Integ
The time spent on integration in microseconds for each of the channels measured.
Constant
Entry
Integration
0, 200
Flash Conversion; 200 = 2 flash conversions 100 µS apart
and averaged
250; 500-16000
250 µS; multiples of 500: 250 µS integrations starting each
500 µS and averaged
_60Hz or 16667
16,667 µS (reject 60 Hz noise)
_50 Hz or 20000
20,000 µS (reject 50 Hz noise)
Mult, Offset
Constant,
Variable,
Array, or
Expression
A multiplier and offset by which to scale the raw results of the measurement. See the
measurement description for the units of the raw result; a multiplier of one and an
offset of 0 are necessary to output in the raw units. For example, the
TCDiff
instruction measures a thermocouple and outputs temperature in degrees C. A
multiplier of 1.8 and an offset of 32 will convert the temperature to degrees F.
AO4 (Source, Reps, SDMAdress)
This instruction is used to set the voltage to an SDM-AO4 four channel analog
output device.
The AO4 instruction has the following parameters:
Parameter
& Data Type
Enter
Source
The Source parameter is the variable that hold the voltage, in millivolts, that
should be sent to the SDM-AO4. If multiple SDM-AO4s are to be triggered
with one instruction, this parameter must be an array dimensioned to the size
of the Reps.
Reps
The Reps parameter determines the number of SDM-AO4 devices to supply
a voltage using this instruction. The SDM-A04s must have sequential SDM
addresses if the Reps parameter is greater than 1.
SDMAddress
The SDMAddress parameter defines the address of the SDM-AO4 to which
a voltage should be applied. Valid SDM addresses are 0 through 14.
Address 15 is reserved for the SDMTrigger instruction.
The SDM address is entered as a base 10 number, unlike older, jumper-
settable SDM instruments that used base 4.
Содержание CR5000
Страница 39: ...Section 1 Installation and Maintenance 1 15 S A N Y O FIGURE 1 11 6 Removal of band clamp and battery ...
Страница 40: ...Section 1 Installation and Maintenance 1 16 This is a blank page ...
Страница 54: ...Section 2 Data Storage and Retrieval 2 14 This is a blank page ...
Страница 88: ...Section 4 CRBasic Native Language Programming 4 12 This is a blank page ...
Страница 94: ...Section 5 Program Declarations 5 6 This is a blank page ...
Страница 172: ...Section 7 Measurement Instructions 7 46 This is a blank page ...
Страница 206: ......
Страница 236: ...Index Index 4 This is a blank page ...
Страница 237: ...This is a blank page ...