Section 7. Measurement Instructions
7-4
TCSE (Dest, Reps, Range, SEChan, TCType, TRef, MeasOfs, SettlingTime,
Integ, Mult, Offset)
S.E. Chanel
Ground
Thermocouple
This instruction measures a thermocouple with a single-ended voltage
measurement and calculates the thermocouple temperature (
°
C) for the
thermocouple type selected. The instruction adds the measured voltage to the
voltage calculated for the reference temperature relative to 0
°
C, and converts
the combined voltage to temperature in
°
C.
Voltage and Thermocouple Parameters
Parameter
& Data Type
Enter
Dest
Variable
or Array
The Variable in which to store the results of the instruction. When Reps are used the
results are stored in an array with the variable name. An array must be dimensioned to
have elements for all the Reps.
Reps
Constant
The number of repetitions for the measurement or instruction.
Range
Constant
Alpha
Code
Numeric
Code
Voltage
Range
mV5000 0
± 5000 mV
mV1000 1
± 1000 mV
mV200 2
± 200 mV
mV50 3
± 50 mV
mV20 4
± 20 mV
AutoRange 5
mV20 - mV5000 Selects range (Sect. 3.1)
mV200C
mV50C
mV20C
20
30
40
± 200 mV
± 50 mV
± 20 mV
The mV200C, mV50C, and mV20C
ranges pull the channel into common
mode range and check for open input
DiffChan
Constant
The differential channel number on which to make the first measurement. When
Reps
are
used, subsequent measurements will be automatically made on the following channels. If
the channel is entered as a negative number, all reps occur on that channel.
SEChan
Constant
The single-ended channel number on which to make the first measurement. When Reps
are used, subsequent measurements will be automatically made on the following channels.
If the channel is entered as a negative number, all reps occur on that channel.
TCType
Alpha
Code
Numeric
Code
Thermocouple Type
Constant
TypeT
0 Copper
Constantan
TypeE
1 Chromel
Constantan
TypeK
2 Chromel
Alumel
TypeJ
3 Iron
Constantan
TypeB
4 Platinum
Rhodium
TypeR
5 Platinum
Rhodium
TypeS
6 Platinum
Rhodium
TRef
Variable
The name of the variable that is the reference temperature for the thermocouple
measurements.
Содержание CR5000
Страница 39: ...Section 1 Installation and Maintenance 1 15 S A N Y O FIGURE 1 11 6 Removal of band clamp and battery ...
Страница 40: ...Section 1 Installation and Maintenance 1 16 This is a blank page ...
Страница 54: ...Section 2 Data Storage and Retrieval 2 14 This is a blank page ...
Страница 88: ...Section 4 CRBasic Native Language Programming 4 12 This is a blank page ...
Страница 94: ...Section 5 Program Declarations 5 6 This is a blank page ...
Страница 172: ...Section 7 Measurement Instructions 7 46 This is a blank page ...
Страница 206: ......
Страница 236: ...Index Index 4 This is a blank page ...
Страница 237: ...This is a blank page ...