![Camozzi PME Series Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/camozzi/pme-series/pme-series_operation-and-maintenance-instructions-manual_3055598043.webp)
Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
43
11.3.2.16.
1014h COIB-ID EMCY
This object contains the configuration of the EMCY service
BIT
VALUE
DESCRIPTION
31(MSB)
0
1
EMCY exist / is valid
EMCY
don’t
exist / isn’t valid
30
0
Reserved
29
0
1
11-bit CAN-ID
29-bit CAN-ID
28-0
X
Extended address 29 bit
11-0
X
Standard address 11 bit
11.3.2.17.
1015h Inhibit time emergency
This object contains the inhibition time of the EMCY message, it must be a multiple of 100 µs. If set
to zero it disables the inhibition time
11.3.2.18.
1017h Producer heartbeat time
This object contains the configuration of the
heartbeat
protocol, it indicates the period in which the
heartbeat
message is produced. The period must be a multiple of 1 ms, if set to zero, the
heartbeat
management is disabled
11.3.2.19.
1018h Identity object
This object contains the information about the device:
SUB-INDEX
VALUE
DESCRIPTION
0
4
Sub-index number
1
151h
Vendor ID
2
05Ch
Product code
3
001h
Revision number
4
000h
Serial number
11.3.2.20.
1019h Synchronous counter overflow value
This object contains the SYNC message configuration. If the value is zero the SYNC message will have
no parameters, if the value is between 2 and 240 then the SYNC message will have a parameter
byte, which will contain a counter.